ABB AX50-30-00-80 AC Contactor

Model Code Breakdown AX50-30-00-80 AX50: AX series general-purpose AC contactor, Dimensioni del telaio 50 30: 3-palo, 3 main Normally Open contacts (3NO), no main Normally Closed contacts 00: No built-in auxiliary contacts (0NO+0NC). Auxiliary contacts must be fitted externally with CAL5X auxiliary contact blocks. 80: Coil Code ✅ Coil Voltage: AC 220~230V 50Hz / 230~240V 60Hz ...

  • Dettagli del prodotto

Scomposizione del codice modello

AX50-30-00-80

  1. AX50: AX series general-purpose Contattore CA, Dimensioni del telaio 50
  2. 30: 3-palo, 3 main Normally Open contacts (3NO), no main Normally Closed contacts
  3. 00: No built-in auxiliary contacts (0NO+0NC). Auxiliary contacts must be fitted externally with CAL5X auxiliary contact blocks.
  4. 80: Coil Code

✅ Coil Voltage: AC 220~230V 50Hz / 230~240V 60Hz (Bobina CA)

Modello di ordine completo: AX50-30-00-80220-230V50Hz/230-240V60Hz

ABB Codice ordine: 10139897

  1. Parametri elettrici principali
ArticoloSpecifica
Poli principali3P (3 Normally Open Main Contacts)
Rated Operational Current AC-3 (400V, Carico del motore)50 UN
Matched 3-phase Motor Power @400V (AC-3)22 kW
AC-1 Resistive Load (40℃)100 UN
Tensione di isolamento nominale Ui690 V
Conventional Thermal Current Ith100 UN
Bobina di controlloAC220~230V 50Hz / 230~240V 60Hz
Resistenza meccanica≥10,000,000 operations
Resistenza elettrica (AC-3)≥1.000.000 di operazioni
Frequenza operativa massima600 operazioni/ora (Servizio AC-3)
Classe di protezioneIP20 (Terminali)
Temperatura ambiente-40℃ ~ +70 ℃
Metodo di montaggioDIN35 Rail Mount / Screw Panel Mount
  1. Contorno & Dimensioni

Width × Depth × Height: 82 mm× 110 mm× 108 mm

Peso netto: ca. 1.05 kg

Contrassegni dei terminali:

Circuito principale: 1L1, 3L2, 5L3 (Line Side); 2T1, 4T2, 6T3 (Load Side)

Terminali della bobina: A1, A2 (Bobina CA, non-polarized)

  1. Caratteristiche principali
  2. No built-in auxiliary contacts. External auxiliary contact modules CAL5X-11 (1NA+1NC), CAL5X-20, CAL5X-02 must be installed separately.
  3. Direct pluggable with ABB TA series thermal overload relays to form a complete motor starter.
  4. Compatible accessories: Soppressori di sovratensione (RC networks, varistori), interblocchi meccanici, side-mounted auxiliary contacts.
  5. Drop-in replacement for legacy A50-30-00; AX series accessories are NOT interchangeable with older A series.
  6. Same Series Selection Reference

AX50-30-00-80: No built-in auxiliary contacts (Subject Model)

AX50-30-11-80: Built-in 1NO+1NC auxiliary contacts (Codice ordine:10139700)

  1. Compatible Replacement Options

Sostituzione diretta dell'OEM

No newer superseding model; AX50 remains in mass production.

Cross-brand Equivalent Alternatives

Schneider LC1D50M7C (50UN, Bobina AC220V)

Siemens 3RT2036-1AK60

⚠️ Replacement Checkpoints: Dimensioni di montaggio, tensione della bobina, auxiliary contact configuration, plug compatibility with thermal relays.

  1. Applicazioni tipiche

Start/stop control of 3-phase motors for air compressors, pompe dell'acqua, tifosi, trasportatori, macchine per lo stampaggio ad iniezione, HVAC equipment; switching of resistive loads such as heaters and lighting circuits.

Complete Technical Document for ABB AX50-30-00-80 AC Contactor

Informazioni di base sul prodotto

Modello completo: AX50-30-00-80

Descrizione completa: AX50-30-00-80 220–230V 50Hz / 230–240V 60Hz

Codice d'ordine ABB: 10139897

ABB Product Code: 1SBL351074R8000

Customs HS Code: 85364900

Serie: AX series 3-pole AC operated contactor (Replaces legacy A50-30-00)

Origine: Tianjin, Cina

Certificazioni: CCC, CE, RoHS, Conforme alla norma CEI 60947

  1. Scomposizione del codice modello
Segmento di codiceDescrizione
AX50Serie AX, Dimensioni del telaio 50
303-palo, 3 Normally Open main contacts (3NO), no main NC contacts
0No built-in auxiliary contacts (0NO+0NC). Auxiliary contacts require external CAL5X accessories.
80Coil Code: AC220~230V 50Hz / AC230~240V 60Hz

⚠️ Distinction: AX50-30-11-80 is equipped with integrated 1NO+1NC auxiliary contacts. AX50-30-00-80 has no on-board auxiliary contacts.

  1. Rated Electrical Parameters (CEI 60947-4-1)

2.1 Parametri del circuito principale

Elemento parametroValore
Conventional Thermal Current Ith (40℃)100 UN
Tensione di isolamento nominale Ui690 V e
Rated Operational Current AC-3 (Carico del motore, 400V)50 UN
Matched 3-phase Motor Power @400V (AC-3)22 kW
Matched 3-phase Motor Power @500V (AC-3)30 kW
AC-1 Resistive Load (40℃)100 UN
Max Making Current (AC-3)500 UN
Max Breaking Current (AC-3)400 UN

2.2 Control Coil Parameters

Tensione della bobina: AC 220~230V(50Hz) / 230~240V(60Hz)

Pick-up Voltage: ≤85% Ue

Drop-out Voltage: 10% ~ 60% Ue

Consumo energetico della bobina: Pick-up ≈70 VA; Holding ≈8 VA

Terminali della bobina: A1, A2 (Non-polarized for AC)

2.3 Lifespan & Specifiche di funzionamento

Resistenza meccanica: ≥10,000,000 operations

Resistenza elettrica (AC-3, 400V, 50UN): ≥1.000.000 di operazioni

Frequenza operativa massima: 600 operazioni/ora (AC-3 load)

  1. Ambientale & Mounting Specifications
ArticoloSpecifica tecnica
Temperatura ambiente operativa-40 ℃ ~ +70 ℃
Temperatura di conservazione-50 ℃ ~ +80 ℃
Permissible Altitude≤3000m; Derating required above 2000m
Classe di protezioneIP20 for main circuit terminals; IP20 for coil terminals
Metodo di montaggioDIN35mm Rail Mount / M4 Screw Panel Mounting
Allowable Mounting Inclination±30°; Vertical installation recommended
Resistenza alle vibrazioni (IEC60068-2-6)5~150Hz, Amplitude 1mm
  1. Outline Dimensions & Peso

Width × Depth × Height: 82 mm× 110 mm× 108 mm

Peso netto: 1.05 kg

Definizione del terminale

Main Circuit Line Side: 1L1, 3L2, 5L3

Main Circuit Load Side: 2T1, 4T2, 6T3

Circuito di controllo: A1, A2

  1. Accessori opzionali (Separate Order Required)

No built-in auxiliary contacts on unit; external accessories required for status feedback

  1. CAL5X-11: Side-mounted auxiliary contact block, 1NA+1NC (Più comunemente usato)
  2. CAL5X-20: 2 Normalmente aperto; CAL5X-02: 2 Normalmente chiuso
  3. TA Series Thermal Overload Relays: TA42DU…TA75DU, direct plug-in to build motor starters
  4. RC Surge Suppressor / Varistor: Connect across A1/A2 to suppress coil overvoltage
  5. Mechanical Interlock Module: For forward/reversing contactor interlocking
  6. Copertura di protezione del terminale

⚠️ Important Notice: AX series accessories cannot be interchanged with legacy A series (A50).

  1. Standard Wiring Description
  2. Basic Motor Start-Stop Circuit

3-phase Power → 1L1/3L2/5L3; 2T1/4T2/6T3 → 3-phase Motor

Circuito di controllo: Power → Start/Stop Pushbuttons → A1, A2

  1. For running status feedback: Install CAL5X-11, use 13/14 NO contact for signal feedback
  2. Surge suppression components for coil must be wired in parallel across A1 and A2, never in series.
  3. Official Document Download Sources
  4. ABB Global Product Page (Download Datasheet, 2D Drawing, 3D CAD)

https://new.abb.com/products/1SBL351074R8000/ax50-30-00-80

  1. ABB Library library.abb.com

Search Document ID: 9AKK107492A7059 (AX Series General Manual)

  1. ABB China Online Store: Search Order Code 10139897 at mall.abb.com.cn
  2. Selezione & Guida alla sostituzione

OEM Upgrade

No superseding model; AX50 is currently in continuous production. Discontinued legacy A50-30-00 can be directly replaced by this model.

Cross-brand Equivalent Alternatives

Schneider LC1D50M7C

Siemens 3RT2036-1AK60

Replacement Verification Points: Tensione della bobina, dimensioni di montaggio, plug compatibility with thermal overload relays, auxiliary contact configuration.

  1. Precauzioni per l'applicazione & Evitare le trappole
  2. 00 designation means no built-in auxiliary contacts. Do not assume integrated 1NO+1NC contacts.
  3. Derate load current if ambient temperature >55℃ or installation altitude >2000M.
  4. Per carichi induttivi (motori), coil surge suppression is recommended to avoid PLC electromagnetic interference.
  5. Not designed for direct switching of high-voltage DC; operate only within specified AC load categories.
  6. CAL5X auxiliary blocks can only be fitted on the left and right sides of contactors; top mounting is prohibited.