ABB machinery drive ACS355-01E-02A4-2

ABB ACS355 series general machinery drive, 0.37 kW / 0.5 HP, single-phase 200–240 V input, IP20 protection, rated output current 2.4 UN. Suitable for speed control and energy-saving operation of small machinery. 1 Model Code Explanation Code Part Meaning ACS355 ABB general machinery drive series 01E Protection class IP20, for installation in enclosed electrical cabinets ...

  • Dettagli del prodotto

ABB ACS355 series general machinery drive, 0.37 kW / 0.5 HP, single-phase 200–240 V input, IP20 protection, rated output current 2.4 UN. Suitable for speed control and energy-saving operation of small machinery.

1 Model Code Explanation

Code PartSenso
ACS355ABB general machinery drive series
01EProtection class IP20, for installation in enclosed electrical cabinets
02A4Rated output current 2.4 UN
2Single-phase 200–240 V AC (±10%), 50/60 Hz input

2 Key Technical Data

ArticoloValore
Potenza nominale0.37 kW (0.5 HP)
Rated output current2.4 UN (at 40°C)
Input voltage / frequenzaSingle-phase 200–240 V AC (±10%), 50/60 Hz
Output voltage / frequenzaThree-phase 0–240 V AC, 0–500 Hz
Classe di protezioneIP20 (indoor cabinet installation)
Control methodScalar control (V/f), built-in application macros
Overload capability150% of rated current for 60 S; 180% for 2 S
Cooling methodNatural cooling
Dimensioni (L×A×P)169×70×135 mm
Pesoca. 1.2 kg
Order code3AUA0000058166
EMC performanceBuilt-in EMC filter, conforme alla norma EN 61800-3

3 Caratteristiche principali

3.1 Flexible Control

Predefined application macros: constant torque, fan/pump, PID control, ecc.

Local/remote control switching via keypad, terminals or fieldbus

Built-in PID controller for closed-loop flow, pressure, ecc.

3.2 Reliable Protection

Overcurrent, sovraccarico, sovratensione, sottotensione, overheating, phase loss protection

Motor over-temperature protection (requires external PTC)

Short-circuit and earth-fault protection

3.3 Funzionamento facile

Compatible control panel with ACS350/510/550 series

Parameter copy function for fast commissioning

MTBF > 100,000 hours for continuous operation

4 Applicazioni tipiche

Small conveyors, macchine per l'imballaggio

Tifosi, pompe (small HVAC systems)

Mixers, centrifuges and small processing machines

Automatic doors, roller shutters

Medical equipment, strumenti di laboratorio

Textile, printing and other light industrial machinery

5 Installazione & Commissioning Guidelines

5.1 Requisiti di installazione

Must be installed in an enclosed electrical cabinet

Temperatura ambiente: 0–40°C (declassare 10% at 40–50°C)

Montare verticalmente, keep ≥ 100 mm clearance above and below for cooling

Evitare la polvere, oil, gas corrosivi

Input protection: 10 A MCCB (C-curve) or fuse recommended

5.2 Basic Commissioning Steps

  1. Pre-power check: Verify wiring (L1/N input, U/V/W output), terminal torque, proper earthing
  2. Parameter initialization

Group 99: set motor rated voltage, attuale, energia, velocità

Select application macro (Standard, PID, ecc.)

  1. Control configuration

Local control: via control panel

Telecomando: via DI terminals or optional Modbus RTU

  1. Operation test

No-load test: run at 5–10 Hz, check rotation and stability

Load test: gradually apply load, verify current and temperature

Adjust acceleration/deceleration time (1–10 s recommended)

6 Cross-Brand Replacement Options (0.37 kW, 1-fase 220 V, IP20)

MarcaModelloPunti chiave di corrispondenza
SchneiderATV12HU04M20.37 kW, 1-fase 220 V, IP20, similar size
SiemensV20 6SL3210-5BB12-5UV10.37 kW, 1-fase 220 V, IP20, integrated EMC
CintoNVF2-0.37/20.37 kW, 1-fase 220 V, IP20, economical alternative
ABB alternativeACS150-01E-02A4-2Same power range, more compact design

7 Selezione & Maintenance Tips

7.1 Recommended Options

Braking function: optional braking resistor (75 OH / 50 W recommended)

Comunicazione: add RS485 module

Enhanced EMC: additional input EMC filter

7.2 Manutenzione

Clean cooling channels every 6 mesi

Check terminal torque annually

Avoid frequent starts/stops (≤ 20 times per day)

Temperatura di conservazione: -25°C fino a +60°C, dry environment

ABB ACS355-01E-02A4-2

Installation and Commissioning Manual

Overview: This manual provides complete instructions for safety, installation, cablaggio, parameter setting and commissioning of the ACS355-01E-02A4-2 drive (0.37 kW / 0.5 HP, single-phase 200–240 V) for general machinery speed control and energy saving.

1 Safety Instructions (Deve leggere)

1.1 Electrical Safety

Power-off procedure: Disconnect all power before installation, wiring or maintenance. Wait 5 minutes for internal capacitors to discharge.

Earthing: PE terminal must be reliably earthed (earth resistance ≤ 4 OH)

Protezione da sovracorrente: Install 10 A MCCB (C-curve) or fuse on input side

Prova di isolamento: Only test motor cables; do NOT apply voltage to the drive itself

1.2 Mechanical Safety

Rotating parts (shaft, coupling, pulley) must be guarded

Mount vertically on solid surface to avoid vibration

Do not modify internal circuits or structures

1.3 Environmental Safety

Temperatura operativa: 0–40°C (declassare 10% at 40–50°C)

Umidità: 5–95% RH, senza condensa

IP20: must be installed in enclosed cabinet

2 Product Overview and Model Identification

2.1 Spiegazione del modello (ACS355-01E-02A4-2)

CodiceSenso
ACS355ABB general machinery drive series
01EIP20, cabinet-mounted
02A4Rated output current 2.4 UN (40°C)
2Single-phase 200–240 V AC, 50/60 Hz

2.2 Specifiche principali

ArticoloValore
Potenza nominale0.37 kW (0.5 HP)
Input voltageSingle-phase 200–240 V AC (±10%)
Output voltageThree-phase 0–240 V AC
Output frequency0–500 Hz
Overload capacity150% for 60 S, 180% for 2 S
CoolingNatural cooling
Dimensioni (L×A×P)169×70×135 mm
Pesoca. 1.2 kg
Order code3AUA0000058166

3 Procedura di installazione

3.1 Preparation

  1. Unpack and inspect drive for damage
  2. Choose well-ventilated, dust-free location inside cabinet
  3. Utensili: Cacciavite a croce (PH2), spelafili, strumento di crimpatura, multimetro, insulation tape

3.2 Montaggio

  1. Mount vertically on flat metal plate
  2. Keep ≥ 100 mm above/below, ≥ 50 mm left/right clearance
  3. Fix with M4 screws, coppia di serraggio: 1.2–1.5 N·m

4 Electrical Wiring

4.1 Terminal Description (ACS355-01E Series)

SectionterminaleDescrizioneCablaggio
Circuito di potenzaL1/NSingle-phase 200–240 V input1.5–2.5 mm² copper
PEProtective earth≥ 2.5 mm² copper
U/V/W3-phase output to motor1.5–2.5 mm² copper
Circuito di controlloDI1–DI3Digital inputs0.5–1.5 mm², massimo 50 M
AI1/AI2Analog inputs (0–10 V / 0–20 mA)Shielded twisted pair, massimo 100 M
AO1Analog output (0–20 mA)Shielded twisted pair, massimo 100 M
+24V/GND24 Alimentazione Vcc (massimo 100 mA)0.5–1.5 mm²
RS485+/–ModBus RTUShielded twisted pair, massimo 1000 M

4.2 Passaggi di cablaggio

  1. Power wiring: L1/N to mains, PE to earth, U/V/W to motor
  2. Control wiring (Standard macro example):

DI1: Forward (FWD), DI2: Reverse (REV), DI3: Reset

AI1: Speed reference (0–10 V)

  1. Check torque, insulation, and phase sequence

5 Parameter Settings

5.1 Keypad Functions

▶/■: Inizio / Stop

▲/▼: Adjust value

ENTER: Confirm

ESC: Back

LOC/REM: Local / Remote

5.2 Quick Motor Settings (Group 99)

ParametroNomeSettingNota
9901LanguageChinese / EnglishUser choice
9902Application macro1 (Standard)General use
9903Motor type1 (Asynchronous)Standard induction motor
9904Motor rated power0.37 kWFrom nameplate
9905Motor rated voltage220/230/240 VFrom nameplate
9906Motor rated currentMotor nominalTypically ~2.1 A
9907Motor rated frequency50/60 HzFrom nameplate
9908Motor rated speedMotor nominal~1400–1450 rpm
9909Number of motor poles4Standard for 0.37 kW
9910Control mode1 (V/f)Scalar control

5.3 Common Application Parameters

GroupParametroNomeRecommended Value
101001Max frequency50/60 Hz
1002Min frequency0 Hz
202001Acceleration time3–10 s
2002Deceleration time3–10 s
212101Acc/dec type1 (Linear)
404001DI1 function1 (FWD)
4002DI2 function2 (REV)
4003DI3 function9 (RESET)
505001AI1 type1 (0–10 V)
5002AI1 minimum0%
5003AI1 maximum100%
161607Save parameters1

6 Commissioning Flow

6.1 Pre-Power Check

Correct power and control wiring

Motor and drive area clear

Cabinet ventilation OK

Input voltage: 200–240 V single-phase

6.2 First Power-Up

Close MCCB, display shows REM or LOC

Check for fault codes

Verify Group 99 motor parameters

6.3 Motor Identification (Opzionale)

Set 9910 = 2 (ID Run)

Press ENTER; drive runs motor briefly

Completed when shown COMPLETE

6.4 No-Load Test

Switch to LOCAL

Run at 5 Hz, check rotation

Increase to rated frequency, check noise and vibration

6.5 Prova di carico

Switch to REMOTE

Control speed via AI1

Check output current ≤ 2.4 UN

Adjust acc/dec to avoid overcurrent

Test protection functions

7 Risoluzione dei problemi

7.1 Common Fault Codes

FaultDescrizioneCausaRemedy
OVERCURRENTOvercurrentMotor overload, cortocircuitoControllare il carico, motore, parameters
OVERVOLTAGEOvervoltageHigh mains, fast decelerationControllare la tensione, increase dec time
UNDERVOLTAGEUndervoltageLow supply, connessione allentataCheck mains and wiring
OVERTEMPOverheatingHigh temp, blocked coolingImprove ventilation, clean heatsink
MOTOR OVERLOADMotor overloadExcessive loadCheck application, ridurre il carico
FAULT RESETTrip reset requiredFault occurredFix cause, reset via DI3 or keypad

7.2 Typical Issues

SintomoCausaSoluzione
Motor does not startWrong LOC/REM, missing DI signalCheck mode, wiring and parameters
Unstable speedAI noise, poor parametersUse shielded cable, adjust filtering
Errore di comunicazioneWrong settings, bad wiringCheck Group 98, RS485, termination

8 Manutenzione

8.1 Routine Maintenance

Clean cooling channels every 6 mesi

Check terminal torque annually

Log operating current and temperature

8.2 Long-Term Storage

Temperatura: -25°C fino a +60°C

Dry, ventilated environment

Power on for 1 hour every 6 mesi

9 Appendix: Options and Replacements

9.1 Recommended Options

Braking resistor: 100 OH / 50 W

EMC filter

RS485 Modbus RTU module

Shielded cable for control wiring

9.2 Alternative multimarca (0.37 kW, 1-fase 220 V, IP20)

MarcaModelloMatching Features
SchneiderATV12HU04M20.37 kW, 1-fase 220 V, IP20
SiemensV20 6SL3210-5BB12-5UV10.37 kW, 1-fase 220 V, IP20
CintoNVF2-0.37/20.37 kW, 1-fase 220 V, IP20
ABBACS150-01E-02A4-2Direct same-power replacement

Manual Version: V1.0 (based on ABB official ACS355 manual, adapted for ACS355-01E-02A4-2)

Effective Date: February 2026

Copyright: ABB Group, Tutti i diritti riservati