Informazioni di base
Modello:3DM486.6
Marca: B&RAutomazione
Famiglia di prodotti: Sistema 2005 (Legacy PCC Backplane System)
Tipo di modulo: Digitale Mixed I/O Module
⚠️ Status: Manufacturer Discontinued (Obsoleto). Only stock and second-hand spare parts available. New projects are recommended to migrate to the X20 series.
- Core Channel Specifications
| Articolo | Parametro |
| Ingresso digitale (DI) | 16 canali, 24 VCC, Sink/Source compatible (NPN/PNP universal) |
| Input Filter Time | 1 SM |
| Uscita digitale (FARE) | 16 canali, Transistor Sourcing Output, 24 VCC |
| Per-channel Output Current | 0.5 UN / punto |
| Maximum Total Module Output Current | 8 UN |
| Isolamento elettrico | Galvanic isolation between input bank and output bank; no isolation between individual channels |
| Diagnostica | Output short-circuit / overcurrent detection, per-channel LED status indication |
- Elettrico & Specifiche ambientali
- Consumo energetico
Backplane 5 V: 1.2 W
Campo 24 fornitura V: 2.2 W
- Funzionalità di protezione
Thermal shutdown upon output short-circuit, inductive load protection, external supply reverse polarity protection
- Condizioni ambientali
Temperatura operativa: 0 ~ +60 °C
Magazzinaggio & Temperatura di trasporto: -25 ~ +70 °C
Umidità relativa: 5%~95 %, senza condensa
Classe di protezione: IP20 (for cabinet mounting only)
- Specifiche meccaniche
Sistema 2005 single-width module
Peso: ca. 0.32 kg
- Mandatory Terminals (Not included with module, order separately)
The module is equipped with sockets; terminal blocks must be ordered separately. 2 pcs of 18-pin terminals required
7TB718.9: Morsettiera a vite, 1.5 mm²
7TB718.91: Cage Clamp spring terminal block, 1.5 mm²
X1 connector: DO1~DO16; X2 connector: DI1~DI16
- Compatibilità del software
Minimum supported Automation Studio version: V2.6
Corresponding hardware upgrade package required: V1.0.1.0
- Opzioni di sostituzione (Key Information)
1) Drop-in compatible within the same platform (Retain System2005 backplane & processore)
No direct pin-to-pin upgraded model. Similar reference within series:
3DM476.6: 16DI + 16FARE, supports DC/AC24 V inputs (different electrical characteristics for selection)
2) Platform Migration (Nuovi progetti / complete cabinet retrofit, System2005 → X20)
Functionally equivalent combination:
X20DI9371 (16DI) + X20DO9322 (16FARE)
Vantaggi: Stable long-term availability, sufficient stock, enhanced diagnostic functions.
- Applicazioni tipiche
Macchine per l'imballaggio, attrezzature tessili, printing presses, legacy production line retrofits; used for signal acquisition from proximity switches and pushbuttons, and driving small loads such as solenoid valves and indicator lamps.
⚠️ Selection & Precauzioni per la manutenzione
- Output is Sourcing type (PNP). Connect load negative terminal to 0 V; cannot be directly wired for sinking drive.
- Do not exceed 0.5 A continuous current per channel; total module output current must not exceed 8 UN.
- Freewheeling diodes must be wired in parallel for inductive loads (elettrovalvole).
- System2005 backplane modules cannot be plugged directly into X20 bases; backplane bus protocols are incompatible.
- When purchasing discontinued spare parts, distinguish refurbished / used / brand-new surplus stock and confirm warranty terms.
If required, I can provide:
1) Complete terminal pin assignment table
2) Standard DI/DO wiring schematic
3) Configuration key points for Automation Studio hardware setup
B&R 3DM486.6 Hardware Installation Manual (Field Version)
Product Platform: B&Sistema R 2005 PCC
Tipo di modulo: 16DI / 16DO Digital Mixed I/O Module
Stato: Manufacturer discontinued, for spare part use only
Ambito: Cabinet assembly, cablaggio, power-on commissioning, Risoluzione dei problemi
Sommario
- Istruzioni di sicurezza
- Prodotto & Elenco degli accessori
- Installazione meccanica (Backplane Mounting Procedure)
- Complete Terminal Pin Assignment
- Electrical Wiring Specifications (DI/DO Schematic)
- Ambientale & Dimensioni di montaggio
- Power-on Inspection & LED Indicator Definition
- Automation Studio Configuration Guidelines
- Operational Restrictions & Difetti comuni
- Aggiornamento & Replacement Guidance
- Mandatory Safety Instructions
- Module insertion / removal must be performed with power disconnected! Hot-plugging System2005 backplane modules is strictly prohibited; it may permanently damage backplane bus interfaces.
- Implement ESD protection before handling; wear anti-static wrist strap. Circuit boards are sensitive to electrostatic discharge.
- Fuses must be installed for external 24 Alimentazione VCC; reverse polarity of power supply is forbidden.
- Freewheeling diodes must be fitted in parallel to inductive loads (elettrovalvole, contattori) driven by output channels.
- Module protection rating IP20, installation inside control cabinet only. Do not expose directly to dust or moisture.
- Galvanic isolation exists between DI bank and DO bank; no channel-to-channel isolation. Separate low-level I/O cables from power cables during wiring.
- Modulo & Accessori Obbligatori
Main Module
Modello: 3DM486.6
Canali: 16×DI (24 VDC Sink/Source) + 16×DO (24 VDC Sourcing transistor output, 0.5 Uno per canale)
Terminals to be ordered separately (Not supplied with module)
7TB718.9: 18-pin screw terminal block, max conductor cross-section 1.5 mm²
7TB718.91: 18-pin Cage Clamp spring terminal block, max conductor cross-section 1.5 mm²
Quantity required: 2 morsettiere (X1 for DO, X2 for DI)
- Mechanical Installation Steps for System2005 Backplane
- Confirm complete power-off of the entire PCC rack; isolate the power supply module from mains.
- Align the bottom guide slots of the module with the DIN rail backplane guides and slide horizontally into the slot.
- Press the side latches inward until an audible click confirms the module is locked to the backplane.
- Verify the rear gold-plated bus connector is fully seated against the backplane connector without tilting or gaps.
⚠️ Do not pry the module with screwdrivers. Per rimuovere, release side latches and pull the module out parallel to the backplane.
- Vertically insert the 7TB718 terminal plugs into the lower X1 and X2 sockets of the module until fully engaged.
Mounting Clearance Requirements
Maintain minimum 25 mm ventilation space above and below each module;
Operating ambient temperature 0 ℃ ~ +60 ℃. Implement cabinet temperature reduction if operating continuously above 55 ℃.
- Complete Terminal Pin Assignment
X1 = Output Terminal (DO1~DO16)
X2 = Input Terminal (DI1~DI16)
X1 (DO Output, 18 Spillo)
| Spillo | Segnale | Descrizione |
| 1 | DO1 | Uscita digitale 1 |
| 2 | DO2 | Uscita digitale 2 |
| 3 | DO3 | Uscita digitale 3 |
| 4 | DO4 | Uscita digitale 4 |
| 5 | DO5 | Uscita digitale 5 |
| 6 | DO6 | Uscita digitale 6 |
| 7 | DO7 | Uscita digitale 7 |
| 8 | DO8 | Uscita digitale 8 |
| 9 | DO9 | Uscita digitale 9 |
| 10 | DO10 | Uscita digitale 10 |
| 11 | DO11 | Uscita digitale 11 |
| 12 | DO12 | Uscita digitale 12 |
| 13 | DO13 | Uscita digitale 13 |
| 14 | DO14 | Uscita digitale 14 |
| 15 | DO15 | Uscita digitale 15 |
| 16 | DO16 | Uscita digitale 16 |
| 17 | +24V_OUT | Common positive supply for outputs (internally routed on module) |
| 18 | 0V_GND | Common ground for outputs |
✅ Output Type: Sourcing / PNP Output
When DO is activated, +24 V is present on DO pin. Connect one terminal of load to DO, the other terminal to 0 V.
X2 (DI Input, 18 Spillo)
| Spillo | Segnale | Descrizione |
| 1 | DI1 | Ingresso digitale 1 |
| 2 | DI2 | Ingresso digitale 2 |
| 3 | DI3 | Ingresso digitale 3 |
| 4 | DI4 | Ingresso digitale 4 |
| 5 | DI5 | Ingresso digitale 5 |
| 6 | DI6 | Ingresso digitale 6 |
| 7 | DI7 | Ingresso digitale 7 |
| 8 | DI8 | Ingresso digitale 8 |
| 9 | DI9 | Ingresso digitale 9 |
| 10 | DI10 | Ingresso digitale 10 |
| 11 | DI11 | Ingresso digitale 11 |
| 12 | DI12 | Ingresso digitale 12 |
| 13 | DI13 | Ingresso digitale 13 |
| 14 | DI14 | Ingresso digitale 14 |
| 15 | DI15 | Ingresso digitale 15 |
| 16 | DI16 | Ingresso digitale 16 |
| 17 | COM+24V | Common positive for inputs (used for NPN / Sinking sensors) |
| 18 | COM_0V | Common ground for inputs (used for PNP / Sourcing sensors) |
Two DI Wiring Configurations
- PNP Sensor (Sourcing Type)
Sensor positive → DI channel; Sensor negative → 0 V; Connect module X2.18 to field 0 V
- NPN Sensor (Sinking Type)
Sensor positive connected to 24 V; Sensor output → DI channel; Connect module X2.17 to field +24 V
Input hardware filter: Fixed at 1 SM, non-adjustable via software.
- Valutazioni elettriche
Backplane 5 V power draw: 1.2 W
Campo 24 V power draw: 2.2 W
Maximum continuous per-channel output: 0.5 A DC24 V
Global module output current limit: 8 UN; prolonged overload not permitted
Isolamento: Galvanic isolation between DI bank and DO bank; no isolation between individual channels
Protezione: Thermal shutdown for output short-circuit, protezione da inversione di polarità
- Module Dimensions (mm)
Larghezza: 25 (System2005 single-width module)
Altezza: 130
Profondità: 86
Peso: ca. 320 G
- LED Indicator Definition
One LED assigned per channel on module front face:
DI LED ON: High level detected on corresponding input channel
DO LED ON: Output enabled in program and hardware output switched ON
Power status: Standby LEDs illuminated when backplane supply is normal; no LED response upon backplane communication failure.
- Automation Studio Hardware Configuration Guidelines
- Minimum supported AS version: V2.6 and above
- Hardware library selection: `3DM486.6` System 2005 DM module
- Address mapping: Follow rack slot sequence; slot numbering starts from CPU and extends backward
- Diagnostics support: Software readable faults for output short-circuit and overload
Important: Cannot be installed directly onto X20 backplane; bus protocols are incompatible!
- Fault Troubleshooting Matrix
| Sintomo di guasto | Possible Root Cause | Azione correttiva |
| No LED illumination on module | Backplane power absent / Poor module seating / Damaged backplane | Re-seat module after full power-off; Inspect 3PS465/3PS476 power supply modules |
| DO LED ON, external load inactive | Missing external 24 fornitura V, cable break, failed load | Measure voltage at X1.17/18; Inspect load wiring |
| Recurring short-circuit alarms on outputs | Shorted load, per-channel current exceeding 0.5 UN, missing freewheeling diode for inductive loads | Install freewheeling diodes; distribute load current; Inspect cables for insulation damage |
| Fluctuating DI signals | Interferenza elettromagnetica, insufficient filtering, excessively long cables | Route DI cables separately; add RC snubber circuits; check supply voltage ripple |
| Individual channel failure | Channel burned out due to overcurrent; non-repairable | Sostituire il modulo |
- Modifica & Replacement Guidance
Same Platform Compatibility (No CPU/Backplane Modification)
Similar model: 3DM476.6 (Supports AC24 V inputs; pin assignment differs, wiring modification required)
Platform Upgrade System2005 → X20 (Recommended for New Projects)
Functionally equivalent combination:
X20DI9371 (16DI) + X20DO9322 (16FARE)
Vantaggi: Long-term production availability, stable spare part supply, enhanced diagnostic capability.
- Wiring Engineering Specifications
- Separate I/O signal cables from power cables, minimum separation distance ≥30 cm; use shielded cables if separation cannot be achieved.
- Install independent fuses for all 24 VDC circuits (3~5 A recommended rating).
- Implement single-point earthing inside control cabinet; reliably connect signal ground and protective earth.
- Recommended cable cross-section: 0.75~1.0 mm².