Wechat: +86-13184948252 Whatsapp: 0086-13811255435 E-mail: kent@bestcontactor.com

Di Contatto |

CHINT CJ20-160 AC Contactor - Contattore,interruttore automatico,inverter solare,contatore elettrico,batterie solari

contattore/

CHINT CJ20-160 AC Contactor

Significato del modello & Basic Positioning Part Meaning CJ AC Contactor (China Contactor) 20 Design No. (20th generation) 160 Rated operational current 160A (AC‑3 category) CHINT CJ20‑160 is a 3‑pole AC contactor, a main model in the CJ20 series, suitable for frequent operations such as motor control. It complies with GB/T 14048.4 and IEC/EN 60947‑4‑1 standards. ...

  • Dettagli del prodotto

Significato del modello & Basic Positioning

ParteSenso
CJContattore CA (China Contactor)
20Design No. (20th generation)
160Rated operational current 160A (AC‑3 category)

CHINT CJ20‑160 is a 3‑pole AC contactor, a main model in the CJ20 series, suitable for frequent operations such as motor control. It complies with GB/T 14048.4 and IEC/EN 60947‑4‑1 standards.

2. Parametri tecnici fondamentali

Prestazioni elettriche

ArticoloValoreNote
Corrente operativa nominale (AC‑3)160UNControls motor power 85kW at 380V
Conventional thermal current (Ith)200UNLong‑time permissible current in free air
Tensione di isolamento nominale (Ui)690VMaximum voltage withstand class
Rated operational voltage (Ue)Up to 660V (50/60Hz)Main circuit voltage range
Control coil voltage110V/127V/220V/380V etc.220V and 380V are common
Coil power consumptionInrush 855VA, Holding 85.5VA (50Hz)Energy‑saving versions available
Rated operational frequency (AC‑3)1200 operazioni/oraTypical for motor control
Making/breaking capacity10 × rated current (1S)Withstands motor starting surge
Contatti ausiliariStandard 2NO+2NC (expandable)For control circuit signaling
Mechanical endurance10 milioni di operazioniElectrical endurance (AC‑3): 1 milioni di operazioni

Mechanical Structure
Double‑break direct‑acting structure, excellent arc extinguishing
Main contacts made of silver‑based alloy, arc‑resistant and anti‑welding
Overall modular design, facilità di installazione e manutenzione
Compatible with RT16‑315 fuse protection

3. Mounting Dimensions & Peso

ArticoloValore (mm)
Larghezza (UN)146
Altezza (B)187
Profondità (C)178
Distanza tra i fori di montaggio130×130 (±0.5)
Mounting hole diameter9mm
PesoApprox. 5.5kg

Montaggio: Standard 35mm DIN rail or bolt fixing

4. Application & Selection Guide

Ambito di applicazione
1. CA 50/60 Hz, power circuits up to 660V
2. Remote switching on/off, frequent control of three‑phase asynchronous motors
3. Combined with thermal overload relays (per esempio., NR2 series) into magnetic starters for overload protection
4. Typical uses: tifosi, pumps, compressori, conveyors and other industrial equipment

Note sulla selezione
For motor control, select according to AC‑3 category (160A ≈ 85kW/380V)
Coil voltage must match control circuit (commonly 220V/380V)
Auxiliary contact quantity to meet control requirements (expandable)
Consider operating frequency and environment (temperature, umidità, altitude)

5. International Brand Replacements

MarcaModello sostitutivoCompatibilità
Siemens3RT2036‑1AP00Same current class, similar dimensions
ABBA165‑30‑11165UN, direct replacement
SchneiderLC1D15000M7C150UN, suitable for light loads
SchneiderLC1D18000M7C180UN, suitable for heavy loads
Eaton (Moeller)DIL M175175UN, high performance match

6. Operation & Manutenzione

1. Inspect integrity before installation, remove packaging
2. Ensure terminals are tightly secured to avoid overheating
3. Regularly check contact wear; replace silver alloy contacts at 1/3 thickness
4. Clean arc chute to remove carbon deposits
5. Do not use without arc chute to prevent arc short‑circuit
6. Coil voltage range: 85%–110% of rated value

7. CJ20 Series Model List

ModelloCorrente nominale (UN)Control Power (kW/380V)Ith (UN)
CJ20‑10104.516
CJ20‑16167.525
CJ20‑25251140
CJ20‑40402263
CJ20‑636330100
CJ20‑10010055140
CJ20‑16016085200
CJ20‑250250132315
CJ20‑400400200500
CJ20‑630630315800

The mechanical endurance of CHINT CJ20‑160 is 10 milioni di operazioni, the standard design index for no‑load cycles under normal conditions.

Additional Info
1. Electrical endurance: Under AC‑3 (motor control), 1.2 million operations – lower due to arcing and contact wear
2. Series difference: CJ20‑10 ~ CJ20‑160: 10 milioni di operazioni; CJ20‑250/400/630: 6 milioni di operazioni
3. Life factors: Actual service life depends on frequency, environment, and maintenance

CHINT CJ20 Series: Core Advantages vs Other Series

The CJ20 series is a classic CHINT contactor line with strong advantages in heavy‑duty performance, potere di interruzione, durability and compatibility, especially compared with CJX2, NC1 and CJ40 series.

1. Structural & Performance Advantages

1.1 Excellent Breaking & Arc Extinguishing
Double‑break direct‑acting structure; models above 40A use ceramic longitudinal or grid arc chutes, better than CJX2
Breaking capacity up to 10× rated current (1S), withstands heavy motor starting
Silver‑based alloy main contacts: low resistance, stable temperature rise

1.2 Long Mechanical & Electrical Endurance

SerieMechanical Endurance (160UN)Electrical Endurance (AC‑3)Caratteristiche
CJ2010 million1 millionFull series 10M (250A+: 6M)
CJX26–10M0.6–1MSmaller sizes lower
NC16–10M0.6–1MNewer, better energy saving

1.3 Modulare & Versatile
Independent auxiliary contacts: standard 2NO+2NC, expandable
Compatible with RT16‑315 fuses and protection modules
35mm DIN rail or bolt mounting

2. Advantages vs Other CHINT Series

2.1 vs CJX2 (Economic Type)

ArticoloCJ20CJX2Application
Heavy‑dutyUp to 630A, 315kWMax 95A, ~45kWCJ20 for large industrial equipment
BreakingStrong, for frequent/ reverse startingMedio, normal dutyCJ20 for crushers, mills
AmbienteRobust, dust/ heat resistantCompatto, clean environmentsCJ20 for metallurgy, minerario

2.2 vs NC1 (New Energy‑Saving)
Proven stable platform: decades of field use, low failure rate, ideal for retrofit projects
AC/DC energy‑saving modules (≥63A): low noise
Better price in same size

2.3 vs CJ40 (High‑Performance)
Wider compatibility with thermal relays (per esempio., NR2)
Simpler installation & maintenance, standard dimensions

3. Key Application Strengths
1. High‑power motors: 85kW (160UN) to 315kW (630UN)
2. Frequent starting & reversing: fino a 1200 operazioni/ora
3. Long‑distance control in large plants, mines
4. Harsh environments: –25°C to +40°C, polvere, vibrazione

Core Value of CJ20 Series

CJ20 stands out for maturity, reliability, heavy‑duty capability and strong breaking performance. It is the top choice for heavy industrial control. While slightly less compact or energy‑efficient than CJX2/NC1, it excels in robustness and durability for demanding traditional industry and equipment upgrades.