Ordine n.: 208281, Alias: XTCEXSBR11 Positioning: Side-mounted auxiliary contact module for high-power DILM/DILH series contactors (Serie Moeller) ✅ Model Code Explanation DILM820-X: Accessory for high-frame DILM power contactors HI11: 1NO + 1NC (1 make, 1 break) E: Side Install (side mounting; differentiated from SA & V variants) ✅ Key Contact Characteristics (Critico) Interlocked Mirror Contact, ...

  • Dettagli del prodotto

Ordine n.: 208281, Alias: XTCEXSBR11

Posizionamento: Side-mounted ausiliario contact module for high-power DILM/DILH series contactors (Serie Moeller)

✅ Model Code Explanation

DILM820-X: Accessory for high-frame DILM power contactors

HI11: 1NO + 1NC (1 make, 1 break)

E: Side Install (side mounting; differentiated from SA & V variants)

✅ Key Contact Characteristics (Critico)

Interlocked Mirror Contact, conforme alla CEI 60947-5-1 Annex L and IEC 60947-4-1 Annex F

The NC contact is a mirror contact, designed for safety circuits, incastro, emergency stop feedback and PLC safety signal acquisition. It is NOT a late-break NC contact

Configurazione dei contatti: 1 Normalmente aperto + 1 Normalmente chiuso

Terminazione: M3.5 screw terminals, coppia di serraggio: 1.2 Nm

Corrente termica convenzionale Ith: 10 UN (A 60 °C)

AC-15 control capacity:

230 V: 6 UN

400 V: 4 UN

500 V: 1.5 UN

Tensione nominale di isolamento Ui: 690 V; Ump: 6 kV; Categoria di sovratensione III, Grado di inquinamento 3

Isolamento elettrico: Coil-to-auxiliary contacts and auxiliary-to-main contacts meet AC 440V isolation level

✅ Compatible Base Contactors (Only for this high-power frame)

DILM250 ~ DILM1000, DILH600 ~ DILH2600, DILDC300 ~ DILDC600 DC contactors

Massimo. 1 module on each side (Sinistra & Giusto), massimo 2 modules per contactor

✅ Dimensions & Peso

W15 mm × H77 mm × D77 mm, Peso netto: 37 G

✅ Cross-Series Comparison (Guida alla selezione)

DILM820-XHI11-SI: Side mount, terminali a vite, interlocked mirror contact (modello standard, this part)

DILM820-XHI11V-SI: Side mount, vibration-resistant reinforced version

DILM820-XHI11-SA: Standard interlocked contact (non-mirror), not for safety EDM monitoring

✅ Certifications

CE, UL, CSA, CCC; compliant with railway standard EN 45545 and vibration standard IEC 61373. Suitable for cranes, compressori d'aria, tifosi, high-power motor circuits, safety gate interlocks and inverter bypass feedback.

✅ Typical Applications

Safety interlock circuits, contactor status feedback to PLC, forward/reverse electrical interlocking, fault feedback, safety relay input signals.

This side-mounted IEC 60947-5-1 Annex L mirror contact module (1NO+1 mirror NC) is exclusively for DILM250~DILM1000 and DILH high-power contactors. It is mainly used in safety-related control circuits, high-power motor control and fault diagnosis feedback, and cannot be replaced by standard auxiliary contacts for safety validation.

  1. Safety Circuits (Più comune, Mandatory for Safety Audits)
  2. EDM External Device Monitoring for Safety Relays

The mirror NC contact is wired into the EDM channel of the safety relay to monitor welding/sticking of the contactor main contacts. If the NC fails to reset after coil de-energization, the safety relay triggers a lockout. It meets ISO 13849 PLd/PLe and SIL2/3, which is the standard solution for Eaton VES, Pilz and Schneider XPS safety circuits.

  1. Cancello di sicurezza / Light Curtain Interlocking

The mirror NC verifies the true open state of the contactor after the safety gate is opened, preventing unexpected motor operation caused by welded main contacts.

  1. Emergency Stop State Verification

After E-stop cuts off the contactor coil, the mirror contact confirms the contactor is physically open, eliminating hidden risks from welded main contacts despite valid E-stop signals.

  1. High-Power Motor Control Circuits
  2. Hardware Electrical Interlock for Forward/Reverse Contactors (Preferred for Large Fans, Pumps and Hoists)

The mirror NC of each contactor is wired in series into the coil circuit of the opposing contactor, forming hardwired interlock to prevent simultaneous closure and phase-to-phase short circuit. For DILM high-power contactors, safety auditors will not approve ordinary auxiliary contacts for this interlock.

III. Performance Comparison Table

Tipo di contattoActuation MechanismPerformance under Welded Main ContactsAmbito di applicazione
Standard NC Auxiliary ContactMechanically coupled only to the armature, no welding test certificationFollows armature position without standard validationIndicator lights, ordinary PLC feedback; FORBIDDEN for EDM monitoring
DILM820-XHI11-SI Mirror NCRigid mechanical linkage + internal positive interlock, factory-tested for contact weldingNC remains open when main contacts are welded, maintaining safe contact gapSafety relay EDM, safety interlocking, contact sticking diagnosis
  1. Limitazioni (Derived from Mechanical Design)
  2. Only fits DILM250~DILM1000 / DILH high-power contactors; smaller frames do not match the mechanical stroke.
  3. Designed exclusively for control signals: Ith=10 A, AC-15 230V=6A; cannot carry main power loads.
  4. The mirror NC only detects welded closed main contacts. It cannot detect poor contact or increased contact resistance.

Full Model List for DILM820-XHI Series

Soltanto 3 mass-produced variants: all side-mounted 1NO+1NC positive-interlock contacts; differences are mirror (E) / standard (SU) and vibration-resistant (V) versioni.

  1. Regole di codifica del modello

DILM820-XHI: Side auxiliary contact module for DILM/DILH high-power contactors (DILM250 ~ DILH2600)

11: 1NO + 1NC (1 make + 1 break)

S: Side mounted

E: Mirror Contact (CEI 60947-4-1 Annex F, approved for EDM welding monitoring)

SU: Standard positive interlock contact (CEI 60947-5-1 Annex L only; NOT allowed for safety relay EDM)

V: Vibration-resistant reinforced construction (ferrovia, heavy vibrating equipment)

  1. Complete Product List
ModelloOrdine n.Configurazione dei contattiTipoApplicazione principale
DILM820-XHI11-SI2082811NO + 1 mirror NCMirror contact (E)Circuiti di sicurezza, EDM welding detection, forward/reverse hard interlock, PLC sticking alarm (your selected model)Eaton
DILM820-XHI11-SA2082821NO + 1 standard NCStandard positive interlock (SU)Ordinary PLC feedback, pilot lights, basic electrical interlock; strictly prohibited for EDM safety monitoringfiles.kemp…
DILM820-XHI11V-SI2082831NO + 1 mirror NCVibration-resistant mirror contact (V+SI)Veicoli ferroviari, overhead cranes, mining machinery with heavy vibration; identical electrical performance to standard SI, with reinforced mechanical structurefiles.kemp…
  1. Key Selection Distinction

(1) SI vs SA (Most Critical)

E: NC is a certified mirror contact. It stays open when main contacts are welded, satisfying ISO 13849 PLd / SIL2-3 and approved for safety relay EDM loops.

SU: Only mechanical positive interlock without welding test certification. Only for ordinary control; rejected by safety audits.

(2) V-SI Variant

Mechanically reinforced for higher shock & resistenza alle vibrazioni (CEI 61373). Electrical specs are identical to standard SI. Used for hoisting, mining and railway rolling stock.

  1. Universal Installation Restrictions

Montaggio: Only side-fit on DILM250~DILM1000 and all DILH series contactors.

Quantità: Massimo. 1 module per side, total maximum 2 modules per contactor.

Valutazione: Ith=10 A, AC-15 230V=6A; strictly for control circuits only, no power loads.

  1. No Other Variants

No XHI22 (2NO+2NC) version available.

No top-mount version; only side-mount (S) modelli.

No spring-cage terminals; all models use M3.5 screw terminals.

  1. Equivalente multimarca

Eaton DILM820-XHI11-SI ↔ Siemens 3RT1956-4G (mirror contact); Schneider LADN13C is only standard auxiliary contact and cannot replace the mirror type for safety EDM.