Convertitore di frequenza vettoriale LENZE E82EV551_4C - Contattore,interruttore automatico,inverter solare,contatore elettrico,batterie solari

Wechat: +86-13184948252 Whatsapp: 0086-13811255435 E-mail: kent@bestcontactor.com

Di Contatto |

Convertitore di frequenza vettoriale LENZE E82EV551_4C - Contattore,interruttore automatico,inverter solare,contatore elettrico,batterie solari

inverter solare/elettrico/

Convertitore di frequenza vettoriale LENZE E82EV551_4C

Model Code Interpretation E82EV551_4C E82EV:8200 Vector series frequency inverter 551:Power code → 0.55 kW 4:3-phase input 380…480 V AC CStandard hardware version Key Electrical Specifications Item Specification Rated Power 0.55 kW Input Voltage 3-phase 380~480 V AC ±10% Input Frequency 50 / 60 Hz Rated Input Current 1.8 A Rated Output Current 1.6 A Output ...

  • Dettagli del prodotto

Interpretazione del codice modello

E82EV551_4C

E82EV:8200 Serie vettoriali frequency inverter

551:Power code → 0.55 kW

4:3-phase input 380…480 V AC

C:Standard hardware version

  1. Specifiche elettriche principali
ArticoloSpecifica
Potenza nominale0.55 kW
Tensione in ingresso3-phase 380~480 V AC ±10%
Frequenza di ingresso50 / 60 Hz
Corrente di ingresso nominale1.8 UN
Corrente di uscita nominale1.6 UN
Frequenza di uscita0~480 Hz
Modalità di controlloControllo V/F, Controllo vettoriale senza sensori
Metodo di raffreddamentoRaffreddamento ad aria naturale (no built-in fan)
  1. Hardware & Interfacce
  2. Interfacce standard

RS232 (Lenz diagnosis port for X500 commissioning)

Digital inputs/outputs, analog inputs/outputs (0–10 V / 4–20mA)

Relay fault output

  1. Optional Communication Modules (slot extension)

Profibus DP, CANopen, ModBus, DeviceNet, ecc.

Module examples: E82ZAFPC001 (Profibus), E82ZAFCC001 (CANopen)

  1. Specifiche ambientali

Temperatura operativa: 0~+45℃ (nessun declassamento); massimo. 55℃ with current derating

Classe di protezione: IP20 (cabinet mounting)

Temperatura di conservazione: -20~+70℃

Altitudine: ≤1000 m without derating; current derating required above 1000 M

  1. Dimensioni & Montaggio

Montaggio: Montaggio su guida DIN / fissaggio a vite

Form factor: Compact book-style

Larger models in the same series: E82EV751_4C(0.75kW), E82EV152_4C(1.5kW)

  1. Commissioning Software

Software: Lenze EASY Starter

Commissioning cable: X500 dedicated cable (E82ZBC)

  1. Informazioni sulla sostituzione (Important)

E82EV series is Obsolete / Interrotto

✅ Official upgrade series: i500 frequency inverter

Recommended equivalent model: I5AE055A1000 (0.55 kW, 380 Classe V)

⚠️ Notes:

  1. Terminal definition and parameter codes are incompatible with 8200; parameters must be re-commissioned.
  2. Communication modules cannot be directly interchanged.
  3. Mounting dimensions differ slightly; cabinet modification may be required.
  4. Applicazioni tipiche

Piccoli trasportatori, tifosi, pompe, compact packaging machinery, trasportatori a nastro, simple spindle drives.

  1. General Operation Notes
  2. This model has no integrated brake transistor. An external brake unit must be used if brake resistors are required.
  3. An output reactor is recommended for long motor cables to suppress dv/dt and protect motor insulation.
  4. Factory default mode: Controllo V/F. Activate vector control via parameters if required.

Available supporting documents upon request:

Complete terminal wiring diagram

Factory default parameter list

i500 alternative parameter comparison table

Fault code list

LENZE 8200 Vector Fault Code List (Applicable to E82EV Series including E82EV551_4C)

Display code | Internal No. | Fault Name | Cause & Risoluzione dei problemi

Distinguish TRIP faults (locked shutdown) and Warnings (continuous operation)

  1. Current-Related Faults (Più comune)
Display CodeInternal No.Fault NameCause & Risoluzione dei problemi
OC111Hardware Short-Circuit Fault (Hardware Overcurrent)Inter-phase short circuit in motor cable, shorted motor winding, output earth short circuit; damaged IGBT
Risoluzione dei problemi: Power on with motor disconnected. If OC1 still occurs → inverter hardware failure; if fault disappears → motor/cable fault
OC212Guasto della Terra (Leakage to Ground)Damaged motor cable contacting ground, breakdown of motor winding insulation; long cables without output reactor
OC313Overcurrent during AccelerationCambio di carico improvviso, mechanical seizure, tempo di accelerazione troppo breve, parametri motore errati
OC414Overcurrent during DecelerationInsufficient deceleration time, high inertia load; DC bus fluctuation triggering overcurrent without brake resistor
OC515Overcurrent at Constant SpeedHeavy load fluctuation, seized bearing, perdita di fase del motore, failed motor identification for vector control
OC616Motor I²t OverloadProlonged heavy load, motor thermal overload; mismatched power rating
LP132 / 182Motor Phase Loss Detection (Active when C0597 enabled)Cablaggio allentato, open circuit of one motor phase; false alarm possible for low-power drives under no-load
Risoluzione dei problemi: Stringere i terminali; adjust threshold C0599
  1. DC Bus Voltage Faults
Display CodeInternal No.Fault NameCause & Risoluzione dei problemi
LUSottotensione bus CCLow 3-phase supply voltage, input phase loss, poor contactors, voltage drop during power-up
⚠️ E82EV551_4C has no built-in input fuse; prioritize checking upstream circuit breakers and terminals
OUDC Bus OvervoltageRapid deceleration, regenerative energy from high inertia loads; excessive mains voltage; missing brake resistor
This model has no integrated brake transistor. An external brake unit + resistor is mandatory for frequent start-stop operation

III. Overtemperature Faults

Display CodeInternal No.Fault NameCause & Risoluzione dei problemi
OH50Inverter Heatsink OvertemperaturePoor cabinet ventilation, temperatura ambiente >45℃; dust blocking cooling channels
E82EV551_4C adopts natural cooling without fan, highly dependent on ambient cooling conditions
OH353PTC Motor Overtemperature TripOverheated motor PTC thermistor; open/short-circuited PTC wiring; temperature monitoring enabled via C0119
OH51203PTC Overtemperature Pre-WarningMotor temperature approaching protection threshold, advance warning
FAn195Fan Fault (Not applicable to this model! E82EV551 has no fan, this code will not appear)Only applicable to higher-power models equipped with cooling fans
  1. Communication Bus Faults (Only with optional communication modules)
Display CodeInternal No.Fault NameCause & Risoluzione dei problemi
Ce060LECOM Communication Fault (X500 diagnostic port)Loose commissioning cable, damaged E82ZBC cable
Ce161CAN-IN1 Communication FaultFaulty CANopen wiring, missing termination resistor, incorrect node address
Ce262CAN-IN2 Synchronous Communication FaultLoss of bus synchronization signal
Ce565BUS-OFF StatusSevere bus interference or short circuit; drive automatically disconnects from bus
Action: Controllare la messa a terra dello schermo, 120惟 termination resistor and bus polarity
Ce666CAN Bus TimeoutNo response from master station; communication monitoring time C0126 set too short
  1. Parametro & Internal Hardware Faults
Display CodeInternal No.Fault NameCause & Risoluzione dei problemi
CCr71Controller Internal FaultSevere electromagnetic interference, main control hardware damage
Test: Restore factory settings first; replace drive if fault persists
Pr075Damaged Parameter Set 0Parameter modified during power-off, EEPROM abnormality; restore factory settings C0002=10
Pr1~Pr576~80Damaged Parameter Set 1~5Corrupted parameter bank; re-download parameters or perform factory reset
id1140Invalid Motor Identification DataMotor identification interrupted, motor disconnected; re-run motor identification C0148
H05105Hardware Detection FaultSelf-test failure of power board / drive circuit; hardware damage
  1. External Control Status & Faults
Display CodeFault NameDescrizione
EErExternal Fault (Triggered via digital input)External emergency stop or external fault terminal activated; check X3 external fault signal
QSPQuick Stop ActiveQuick stop terminal enabled; status message, NOT a trip fault
inhController InhibitEnable condition not satisfied; no trip, drive cannot start

Important Practical Tips for E82EV551_4C

  1. Distinguish status vs fault: inh, QSP, DCB are operating statuses, not trip faults and do not require reset. OC/LU/OH/CCr are trip faults requiring manual reset.
  2. Fault reset methods: RESET key on panel, bus command reset, power cycle.
  3. Fault history storage: Parameter C0084 Latest Fault, C0087 Previous Fault, C0088 Second Previous Fault for historical fault review.
  4. No-load test method: Disconnect motor cables and power on, to judge whether the fault originates from the inverter itself or external wiring/motor.
  5. This model has no built-in brake transistor. If OU overvoltage frequently occurs during deceleration, external brake unit is required.

Prec:

Lascia una risposta

Lasciate un messaggio