AJ65: CC-Link remote I/O unit serie
SBT: CC-Link remote module
B1: Compact terminal block type
16D: 16-point DC digital input module (Ingresso digitale)
Posizionamento: CC-Link remote input station, occupante 1 station address. It is used for remote DI signal acquisition, compatible with Q/A/L series master PLCS, and is one of the most widely used remote DI modules for CC-Link fieldbus.
Specifiche tecniche principali
| Articolo | Parametro |
| Punti di I/O | 16-punto di ingresso DC24V |
| Valutazione degli ingressi | DC24V; allowable voltage range: DC19.2~26.4V, ondulazione ≤5%; input current per point approx. 7mAMITSUBISHI… |
| ON Condition | ≥14V / ≥3.5mA; OFF Condition: ≤6V / ≤1.7mAMITSUBISHI… |
| Input Response Time | ≤1,5 ms (ON↔OFF) |
| Terminale comune | Sink/source compatible (supports both NPN and PNP sensors); 1 common terminal for all 16 punti; single-row terminal block |
| Isolamento | Photo-coupler isolation |
| Occupazione della stazione | 1 stazione |
| Alimentazione del modulo | DC24V; consumo energetico ca. 35mAMitsubishi… |
| Dimensioni complessive | W118 × H50 × D40 mm; peso ca. 0.18kgMitsubishi… |
| Condizioni ambientali | Temperatura operativa: 0~55℃; temperatura di conservazione: -20~75℃; humidity 10~90%RH (nessuna condensa) |
| Certificazioni | UL, cUL, CE, RoHS, KC |
Linee guida per il cablaggio
- Morsettiera: 16 DI channels + COM terminal. COM supports both positive and negative common, so NPN and PNP sensors can be wired directly.
- Bus terminals: E, DB (CC-Link signal lines) + FG shield earth.
- Alimentazione elettrica: Module powered by DC24V. Use the same power supply for the module and sensors, and keep common ground.
- Terminating resistor: Install 110Ω CC-Link terminating resistor at the first and last stations on the bus.
- Station address setting: Set the CC-Link station number (1~64) via the DIP switch on the side of the module; settings take effect after power cycle.
Scenari applicativi
Distributed DI acquisition on production lines: Photoelectric sensors, interruttori di prossimità, pulsanti, limit switches and E-stop signals collected remotely.
Cabinet split wiring: Main PLC installed in central control cabinet; AJ65SBTB1-16D mounted locally on equipment control boxes to eliminate long-distance multi-core cables, only one CC-Link bus cable is needed.
Compatible master stations: Q, UN, L series PLCs (with CC-Link master modules QJ61BT11N / AJ61BT11, ecc.)
Software di programmazione: GX funziona2 / GX funziona3. Configure remote I/O stations in CC-Link network parameters; remote input soft elements are assigned automatically.
Risoluzione dei problemi
- RUN indicator off: Check DC24V power supply and polarity.
- LERR indicator flashing: Numero di stazione duplicato, bus breakage, DA/DB reversed, missing terminating resistor, or communication interference.
- No input signal: Check sensor power supply, COM wiring, input voltage, or damaged optocoupler.
- Input permanently ON: Shorted sensor or short circuit to ground on field wiring.
Sostituzione & Cross-model Reference
AJ65SBTB1-16D1: 16DI with faster 0.2ms response (high-speed version).
AJ65SBTB1-32D: 32-point DC input (stessa serie, 1 station occupied).
AJ65SBTB1-16DT: Mixed 8DI+8DO I/O module.
New generation replacement: NZ2GF2B1-16D (CC-Link IE Field Basic remote DI, consigliato per nuovi progetti).
Engineering Application Cases for AJ65SBTB1-16D
Posizionamento centrale: 16-point DC24V digital input remote station over CC-Link, distributed field DI collection to reduce extensive hardwiring. Compatible master stations: Q/L/A series PLC + QJ61BT11N, FX3U+FX3U-16CCL-M, FX5+FX5-CCL-MS; one module occupies one CC-Link station address.
Caso 1: Pushrod Accumulating Conveyor with Wire Breakage Detection (Diagnostic Type)
- Transistor Output Modules (FARE, T=Transistor, Sink/NPN Type)
8-point Output
- AJ65SBTB1-8T: 8-point transistor output, 1.5ms response
- AJ65SBTB1-8T1: 8-point low leakage current version
- AJ65SBTB1-8TE: 8-point with protective circuit
16-point Output
- AJ65SBTB1-16T: 16-point standard transistor output
- AJ65SBTB1-16T1: 16-point low leakage current version
32-point Output
- AJ65SBTB1-32T: 32-point transistor output
- AJ65SBTB1-32T1: 32-point low leakage current
- AJ65SBTB1-32TE1: 32-point enhanced protection version
III. Moduli I/O misti (DI+DO, DT=Input+Output)
16-point Mixed (8DI+8DO)
- AJ65SBTB1-16DT: Standard 8DI+8DO
- AJ65SBTB1-16DT1: High-speed response version
- AJ65SBTB1-16DT2: With wire breakage diagnosis
- AJ65SBTB1-16DT3: High-reliability revised version (most popular new model)
32-point Mixed (16DI+16DO)
- AJ65SBTB1-32DT: Standard 16DI+16DO
- AJ65SBTB1-32DT1: Versione ad alta velocità
- AJ65SBTB1-32DT2: With wire breakage detection (KDT type)
- AJ65SBTB1-32KDT2: Wire breakage diagnosis + protezione da cortocircuito
- AJ65SBTB1-32KDT8: 32-point mixed, high diagnostic grade
- AJ65SBTB1-32DT3: Revised stable model
- AJ65SBTB1-32DTE1: With surge absorption protection-
- Suffix Code Rules (Identificazione rapida)
Nessun suffisso: Standard response time 1.5ms
1: Risposta ad alta velocità (0.2SM); low leakage current output
2: Wire breakage diagnosis function
3: Revised circuit, improved anti-interference performance
K: Wire breakage detection (diagnostic module)
E: Output surge protection added
- Distinction Between Adjacent Series (Avoid Wrong Selection)
- AJ65SBTB1: Single-row terminal block, compact type (this series)
- AJ65SBTB2: Double-row terminals, higher output current
- AJ65SBT32: Large-size 32-point remote I/O
- AJ65SBTC1/C4: Terminali a molla (tipo plug-in, not part of TB1 series)
- Simplified Selection Table for Project Use
| Applicazione | Modello preferito | High-speed Alternative |
| 16-point DI collection | AJ65SBTB1-16D | AJ65SBTB1-16D1 |
| 32-point DI collection | AJ65SBTB1-32D | AJ65SBTB1-32D1 |
| 16-point DO output | AJ65SBTB1-16T | AJ65SBTB1-16T1 |
| 8DI+8DO mixed I/O | AJ65SBTB1-16DT3 | AJ65SBTB1-16DT2 |
| 16DI+16DO mixed I/O | AJ65SBTB1-32DT3 | AJ65SBTB1-32KDT2 |