CS1W: Prefix for CS-series PLC expansion modules
DI: Output Digital, modulo di uscita digitale
231: Model revision number
Famiglia di prodotti: OMRON CS1 series large-scale PLC (rack-mounted module, used with CS1 CPU backplane)
Specifiche chiave
| Articolo | Parametro |
| Tipo di modulo | Uscita a transistor (sinking NPN) |
| Numero di uscite | 32 punti |
| Rated Load Voltage | DC 12~24V |
| Current per Point | 0.5UN / punto; max common group current 4A |
| Output Isolation | Isolamento del fotoaccoppiatore |
| Terminali | 2 × 20-pin connectors (2 gruppi, 16 points per group) |
| Tempo di risposta | OFF→ON: ≤0,1 ms; ON→OFF: ≤0.4ms |
| Compatible Backplane | CS1W-BC series backplane (Cremagliera CS1) |
| Consumo energetico | 5A DC: 0.35UN (powered from PLC backplane) |
| Circuito di uscita | 32 points divided into 2 common groups, 16 points sharing one COM per group |
Descrizione della funzione
- 32-channel NPN transistor sinking output: Load connected to positive DC24V. When the output point turns ON, it pulls the signal down to GND.
- Suitable loads: DC24V small relays, spie luminose, solid state relays (RSS). Not for direct drive of high-power solenoid valves (intermediate relay required for current amplification).
- This is a CS1-series I/O expansion module and cannot operate standalone. It must be installed on a CS1 CPU rack or expansion rack.
- I/O Address: Automatically assigned by CS1 PLC according to the slot position on the backplane.
Linee guida per il cablaggio
COM terminals connect to DC24V negative (for NPN sinking)
Output terminal → Load → DC24V+
Carichi induttivi (bobine) are recommended to connect a freewheeling diode in parallel to suppress reverse EMF and prevent transistor damage.
Common Alternatives & Compatibilità
Stesso confronto tra serie:
CS1W-OD211: 16-point transistor output
CS1W-OD231: 32-punto NPN che affonda (più ampiamente utilizzato)
CS1W-OD261: 32-point PNP sourcing
Nota di sostituzione: Sinking and sourcing outputs cannot be swapped directly. Verify field load wiring before substitution.
Risoluzione dei problemi
- No output action: Check slot number, PLC I/O allocation, program output bit status; measure COM power supply and load circuit.
- Single channel failure: Usually caused by inductive loads without freewheeling diodes, resulting in permanent transistor breakdown.
- Module error: Insufficient backplane 5V power supply or poor module contact. Rimuovere il modulo, clean gold fingers and re-seat.
HS Code Reference (Foreign Trade)
85371011 (Digital input/output module for programmable logic controllers)
Scenari applicativi
Automation production lines, macchine per l'imballaggio, metallurgical and HVAC complete sets of equipment; high-density DC24V discrete output for CS1 large PLC systems.
CS1W-OD231 Replacement Schemes
CS1W-OD231: CS1 series, 32-punto di uscita del transistor affondante NPN, DC12–24V, 0.5A/punto, 2×20-pin connectors. The CS1 series has been discontinued. Three replacement categories: Same rack direct replacement (minor modification), Cross-series upgrade (complete system retrofit), Domestic compatible replacement.
Schema 1: Same CS Rack Replacement (Priorità, Modifica minima)
Applicable when original CS1 CPU + CS1 backplane remain intact, only the I/O module needs replacement.
- New spare: CS1W-OD231 (original stock / used tested unit)
✅ Identical I/O address, programma, wiring and connectors. Zero program modification, plug-and-play replacement.
⚠️ Discontinued by manufacturer; only surplus stock or tested second-hand units available. Inspect gold fingers and test output channels before use.
- Alternativa della stessa serie: CS1W-OD232
Consistent specifications, 32-point NPN; hardware pin compatible.
Differenza: Updated internal circuit revision. No program modification required, sostituzione diretta.
Attenzione: Do not confuse with CS1W-OD261 (32-point PNP sourcing). COM polarity is reversed, direct replacement will burn loads.
Schema 2: System Upgrade to CJ Series (Official OMRON Recommendation for Discontinued Product)
Modello consigliato: CJ1W-OD231 (32-punto NPN che affonda, fully matched parameters to CS1W-OD231)
Key Specification Comparison
| Articolo | CS1W-OD231 | CJ1W-OD231 |
| Produzione | 32-point NPN sinking DC12–24V | 32-point NPN sinking DC12–24V |
| Current per Point | 0.5UN | 0.5UN |
| Connettore | 2×20-pin | 2×20-pin |
| Allocazione I/O | Slot-based automatic assignment | Slot-based automatic assignment |
Critical Retrofit Differences
- Backplane incompatibility: CS backplane cannot accommodate CJ modules. CJ-series CPU and CJ backplane must be replaced.
- Programma: Most instructions compatible. CX-Programmer project can be saved and converted; verify and adjust special instructions, memory addresses and CPU bus commands.
- Two wiring options
Opzione A (cost saving, recrimp cables): Replace XW2Z cables and XW2R terminal blocks, rewire all field connections.
Opzione B (minimal rewiring, official adapter): CJ1W-AT631 conversion adapter. Reuse original CS1W-OD231 terminal block and field cables without re-routing, significantly reduce site commissioning work.
CJ2 Series Upgrade Option (Higher Performance)
CJ2M/CJ2H racks support CJ1W-OD231 (CJ1W I/O modules work on CJ2 backplanes);
CJ2M CPU cannot accept CS modules directly due to different backplane structure.
Schema 3: Serie NX (Full System Renewal for New Projects)
NX series NX-OD6121, 32-punto di uscita a transistor NPN, EtherCAT bus module.
✅ Higher performance, supporta l'I/O remoto;
❌ Heavy modification: Full system replacement with NX CPU + Bus EtherCAT. Original backplane and I/O addressing structure discarded, extensive program reconstruction required. Suitable for whole-line technical transformation, not single module replacement.
Schema 4: Domestic Compatible Replacement (Cost-Optimized for New Projects / Pezzi di ricambio)
Domestic PLC modules (Innovazione, Xinje etc.), 32-point NPN DC24V transistor output modules.
Vantaggi: Short lead time, costo inferiore;
Svantaggi: Incompatible rack, bus and I/O addressing logic. Program rewrite + full rewiring required. Only for complete PLC replacement, not single module swap.
Replacement Risk Checklist (Mandatory Before Onsite Replacement)
- ✅ Confirm output type: Affondamento della NPN. Load wiring: OUT → Load → DC24V+, COM a 0 V; avoid PNP sourcing by mistake.
- ✅ Inductive loads (elettrovalvole, relay coils) must use parallel freewheeling diodes to protect output channels.
- ✅ Single-point load current ≤0.5A, module total output current ≤4A.
- ✅ Connectors: 2 × 20-pin, cable series XW2Z, terminal block XW2R.
- ✅ Program: After CS→CJ migration, perform I/O address validation and forced output test to prevent address offset.
Riepilogo della selezione
- Existing CS system healthy, only damaged module replacement: Prioritize original CS1W-OD231 stock / tested second-hand units;
- CS main unit aging, plan PLC upgrade but avoid large-scale rewiring: CJ1W-OD231 + CJ1W-AT631 conversion adapter;
- Whole line retrofit with EtherCAT requirement: NX series;
- Budget basso, full PLC replacement: Domestic modules.
No domestic rack module can be directly inserted into the original CS1 backplane or use the CS1 CPU private backplane bus (CS1 backplane protocol is proprietary OMRON protocol, domestic PLC backplanes are mutually incompatible).
Domestic replacement falls into two categories:
- Complete machine retrofit: Replace entire PLC with domestic rack PLC, select domestic 32-point NPN sinking DO module matching CS1W-OD231 specifications
- Distributed remote I/O solution: Retain original CS1 CPU, add bus coupler + domestic remote 32DO NPN module. No backplane disassembly required, minor program modification.
Core target specifications matching CS1W-OD231: 32-point DC24V NPN sinking transistor output; 0.5A/punto; isolamento del fotoaccoppiatore; 2 gruppi COM (16 punti ciascuno); response time ≤0.4ms
- Rack-mounted Domestic PLC Modules (Full PLC Replacement, Marche consigliate)
- Innovazione (Grande / Medium Rack PLC, Mainstream Industrial)
AM400 series: AM401-32DO-N
Specifiche: 32-point NPN sinking DC24V transistor output; 0.5A/punto; 2 groups of 16-point common terminals, isolamento del fotoaccoppiatore; bus backplane, rack mounting.
Applicazione: Replace complete CS1 system; original program needs porting/rewrite.
GL20 series: GL20-32DO-N (Compact rack module)
Specifiche: 32 NPN DC24V, 0.5A/punto; EtherCAT backplane, risposta rapida; suitable for high-density I/O cabinets.
- HollySys (Domestic Large PLC, Widely Used in Automation Projects)
LK series LK610
Specifiche: 32-point DC24V NPN transistor output, 0.5A/punto; grouped COM terminals, backplane del rack, domestic large PLC module.
Applicazione: Metallurgia, HVAC, complete equipment packages, high reliability applications.
- Xinje (Medium Rack PLC, Conveniente)
XF series XF-E32YT-N
Specifiche: 32-point NPN sinking DC24V transistor output; 0.5A/punto; expansion rack module for XF/XSF CPU.
Caratteristiche: Domestic medium PLC, basso costo, suitable for packaging and general automation lines.
- NA Technology (Domestic Independent Controllable PLC)
NA series NA911: 32-point DC24V NPN transistor output rack module, 0.5A/punto, for localization technical transformation projects.
- Domestic Distributed Remote I/O Modules (Retain Original CS1 CPU, Preferred Retrofit Option)
Principio: Add EtherCAT/ModbusTCP coupler to CS1 CPU, domestic remote I/O connected to bus. No CS backplane removal needed; only communication configuration and I/O mapping required.
- Hongchuang HC-32DO-N
32-point NPN sinking DC24V; 0.5A/punto; EtherCAT/Profinet optional; isolamento del fotoaccoppiatore, grouped COM. Terminal block version, direct field cable connection.
- Chenyue, Huatai, Inovance remote I/O
Inovance AM600-RTU-32DO-N: Modbus RTU remote 32DO NPN.
- Deckerwell, Lingkong distributed I/O
32DO-NPN EtherCAT module, widely deployed in industrial sites with proven stability.
III. Domestic Replacement Comparison Table
| Articolo | OMRON CS1W-OD231 | Inovance GL20-32DO-N | Xinje XF-E32YT-N | Hongchuang HC-32DO-N (I/O remoto) |
| Tipo di uscita | 32-point NPN sinking DC24V | 32-point NPN sinking DC24V | 32-point NPN sinking DC24V | 32-point NPN sinking DC24V |
| Current per Point | 0.5UN | 0.5UN | 0.5UN | 0.5UN |
| Grouping | 2×16 COM groups | 2×16 COM groups | 2×16 COM groups | 2×16 COM groups |
| Montaggio | CS1 rack backplane | GL20 rack backplane | XF rack backplane | DIN rail remote bus |
| Compatible with Original CS Backplane | ❌ Proprietary OEM bus | ❌ | ❌ | ✅ Connect to CS1 CPU via bus coupler |
| Modifica del programma | Nessuno (original module) | Full rewrite | Full rewrite | I/O address mapping, minor edits |
- Replacement Risk Checklist (Punti chiave)
- Backplane non-interchangeable! All domestic rack modules cannot plug into CS1 backplane. This is a common misunderstanding. Only remote I/O scheme keeps original CS1 CPU.
- Output polarity must be NPN sinking. Do not purchase PNP sourcing modules, wiring is reversed and may damage loads.
- Carichi induttivi (elettrovalvole, relè) require parallel freewheeling diodes, same requirement for domestic modules.
- Total current limit: Module total current ≤4A, same as original CS1W-OD231.
- Address mapping: Remote I/O scheme requires FINS/Modbus/EtherCAT address mapping inside CS1 program. Control logic remains unchanged but I/O tags must be remapped.
- Raccomandazione di selezione
- Retain original CS1 CPU and backplane, only replace I/O points: Select EtherCAT domestic remote I/O (HC-32DO-N / Deckerwell 32DO-NPN) with EtherCAT coupler for CS1. Minimal modification.
- Full PLC aging, plan complete replacement to domestic system: Inovance AM400/GL20, HollySys LK; HollySys preferred for large complete projects, Inovance for general machinery.
- Budget limitato, small equipment retrofit: Xinje XF series full replacement.