Codice ordine completo: UNO-PS/2AC/24DC/90W/C2LPS Phoenix Contact UNO POWER Series 2-Phase Input DIN Rail Power Supply ✅ Key Specifications Input: 2-phase AC 400~500 V AC (Ampia gamma: 264–575 V AC) Produzione: 24 A DC, corrente nominale 3.75 UN, 90 W Adjustable output voltage: 24~28 V DC (via potentiometer) Output ripple: <50 mVpp Overvoltage protection (OVP): ≤35 ...

  • Dettagli del prodotto

Codice ordine completo: UNO-PS/2AC/24DC/90W/C2LPS

Contatto della Fenice UNO POWER Series 2-Phase Input Alimentatore su guida DIN

✅ Key Specifications

Ingresso: 2-phase AC 400~500 V AC (Ampia gamma: 264–575 V AC)

Produzione: 24 A DC, corrente nominale 3.75 UN, 90 W

Adjustable output voltage: 24~28 V DC (via potentiometer)

Output ripple: <50 mVpp

Protezione da sovratensione (OVP): ≤35 V DC

Consumo energetico a vuoto: <0.7 W

Power factor cosφ: 0.48

Classe di protezione: IP20

Montaggio: NS35 DIN rail

Temperatura operativa: -25℃ ~ +70 ℃; declassamento 2.5% per Kelvin above 55℃

Terminali: Screw-type clamping terminals

C2LPS = NEC Class 2 output certification + hazardous area approval (Classe I, Divisione 2, T4). The output circuit can be wired per Class 2 requirements without extra isolation or protective sheathing, suitable for powering PLCs, sensors and valve islands in explosion-proof cabinets.

No parallel or series connection allowed

✅ Typical Applications

Control cabinets with 400V two-phase power supply, hazardous locations, construction machinery, HVAC, wind turbine auxiliary control systems; power supply for PLCs, interruttori di prossimità, solenoid valves and HMIs.

Distinzione importante: Unlike conventional single-phase 220V UNO power supplies, this model is a high-voltage two-phase input version, which is frequently misselected on site.

✅ Replacement Reference

Single-phase counterpart in the same series: 2902994 (UNO-PS/1AC/24DC/90W/C2LPS), input range 85–264 V AC. Do not interchange the two models.

For higher power with the same structure: UNO 150W & 240W two-phase variants.

✅ Troubleshooting Guide

  1. DC OK indicator off: First verify two-phase input voltage. The unit will not start under phase loss or input voltage below 264 V e.
  2. Excessive voltage drop under load: Check for overcurrent or temperature-induced derating.
  3. Frequent protection trips: Load short circuit or output earth fault. Classe 2 models feature highly sensitive short-circuit protection.

FENICE 2904371 (UNO-PS/2AC/24DC/90W/C2LPS) Manuale di installazione

Precondizione di sicurezza: Indoor cabinet mounting only, Grado di protezione IP20. C2LPS stands for Class 2 output plus Class I Division 2 hazardous area certification. All installation in explosive environments must comply strictly with ISA-12.12.01 standards.

  1. Panoramica del prodotto

Ordine n.: 2904371

Serie: UNO POWER 2-phase DIN rail power supply

Ingresso: 2-phase AC 264–575 V (400V two-phase, NOT single-phase 220V)

Produzione: 24 A DC, 3.75 UN / 90 W, adjustable 24–28 V

Montaggio: NS35 DIN rail (EN60715), installazione orizzontale

Larghezza alloggiamento: 55 mm

  1. Requisiti di autorizzazione (Mandatory for Heat Dissipation)

Side-by-side horizontal installation: 0 mm minimum clearance (units may be mounted tightly together)

Vertical stacking: Minimo 30 mm upper and lower clearance for cooling air flow

No upside-down or side mounting; only horizontal installation with terminals facing forward/downward

Do not install adjacent to heat-generating components (contattori, resistenze di frenatura); high ambient temperature will trigger power derating

Altitude derating: Power rating and insulation voltage must be reduced above 2000 m elevation

  1. Installazione su guida DIN & Rimozione
  2. Hook the top latch onto the NS35 rail first
  3. Press down the unit until the latch clicks securely into place
  4. Rimozione: Insert a flat screwdriver into the bottom latch tab, pry upward to release the lock and pull the unit off the rail

Resistenza alle vibrazioni: Compliant with industrial cabinet vibration standards; no extra locking screws required once clipped firmly.

  1. Specifiche di cablaggio (M3 Screw Terminals)

Tipo di terminale: Screw clamping terminals

Dimensione del conduttore: Solid wire 0.2–2.5 mm²; stranded wire 0.2–2.5 mm²; AWG24~AWG14

Strip length: 8 mm

Cable temperature rating: ≥75℃ for ambient <55℃; ≥90℃ for 55~70℃ ambient

Coppia di serraggio: 0.5–0.7 Nm (evitare di stringere eccessivamente per evitare danni alla filettatura)

Definizione del terminale (Critico: Two-phase input, no neutral N!)

Terminali di ingresso: L1, L2 (two-phase 400V AC, neutral N is not connected); PE protective earth terminal

Terminali di uscita: +24 V, 0 V (24 A DC)

Adjustment potentiometer: ADJ (24~28 V fine-tuning; factory preset to 24 V)

Indicatore: DC OK (green light ON = normal output; OFF = no output or protection active)

⚠️ Critical Warning: This is a 2-phase AC power supply. Never wire it as a single-phase L+N unit; incorrect wiring will cause failure or permanent damage.

  1. Wiring Sequence (Lockout-Tagout Safety Procedure)
  2. Confirm upstream circuit is de-energized and apply lockout-tagout
  3. Connect PE protective earth first (reliable earthing is mandatory)
  4. Wire the two-phase input lines L1/L2
  5. Terminate the 24V DC load cables
  6. Inspect for short circuits and earth insulation; confirm no shorted load circuits
  7. Apply power and verify the DC OK green LED illuminates; trim the ADJ potentiometer to set target output voltage
  8. Classe 2 (C2LPS) wiring rule: Output cabling shall follow NEC Class 2 specifications; no shared trunking with high-voltage power cables without isolation barriers.
  9. Funzioni di protezione & Diagnosi dei guasti

Protezione da cortocircuito: Constant current limiting. Classe 2 versions feature high sensitivity; short-circuit triggers immediate shutdown, auto-recovery after fault removal.

Protezione da sovraccarico: Current exceeding 105% rated value activates current limiting

Protezione da sovratensione (OVP): Output shuts down above 35 A DC

Thermal protection: Over-temperature shutdown; auto-restart after cooling down

Sottotensione / perdita di fase: No start-up if input voltage drops below 264 V e; DC OK light remains off.

  1. Ambientale & Limitazioni all'installazione

Temperatura operativa: -25℃ ~ +70 ℃; 2.5%/K power derating above 55℃

Umidità: 5%~95% senza condensa

Forbidden applications: Outdoor direct mounting, dusty/corrosive atmospheres, water splash exposure

Explosion-proof installation (Class I Div.2 T4): Cabinet-only mounting; external wiring must not create ignition sources, comply with flameproof/enclosure standards.

  1. Parallelo & Series Connection

❌ This model does NOT support parallel current expansion or series voltage boosting. Select the QUINT series if multi-unit parallel operation is required.

  1. EMC & Messa a terra

The PE terminal must connect securely to cabinet protective earth; floating earth is prohibited

Upstream overcurrent protection recommendation: C-curve MCB, 1 A o 2 UN (for 400V two-phase circuit)

Classe 2 output circuits normally do not require additional fuses; se richiesto, implement UL1310 Class 2 current-limiting designs.

  1. Commissioning Checklist

Unit fully clipped onto DIN rail with no play

PE earth connection solid and reliable

L1/L2 two-phase input voltage stays within 264–575 V AC

No short circuit or earth fault on output wiring

DC OK green LED stays steady ON after power-up

Measured output voltage matches the set value

30 mm vertical cooling clearance is maintained top and bottom

III. UNO-PS Full Model List

3.1 UNO-PS / 1AC Single-phase Standard Models (24V Output)

Ordine n.Modello completoEnergiaCorrente nominale
2902991UNO-PS/1AC/24DC/30W30 W1.25 UN
2902992UNO-PS/1AC/24DC/60W60 W2.5 UN
2902993UNO-PS/1AC/24DC/100W100 W4.2 UN
1088851UNO-PS/1AC/24DC/100W/H100 W High-altitude version—
2904376UNO-PS/1AC/24DC/150W150 W6.25 UN
2904377UNO-PS/1AC/24DC/240W240 W10 UN

3.2 Other Output Voltages (12V / 15V / 48V)

Ordine n.Modello completoValutazione dell'uscita
2902998UNO-PS/1AC/12DC/30W12 V / 30 W
2902999UNO-PS/1AC/12DC/55W12 V / 55 W
2902997UNO-PS/1AC/12DC/100W12 V / 100 W
2903000UNO-PS/1AC/15DC/30W15 V / 30 W
2903001UNO-PS/1AC/15DC/55W15 V / 55 W
2903002UNO-PS/1AC/15DC/100W15 V / 100 W
2902995UNO-PS/1AC/48DC/60W48 V / 60 W
2902996UNO-PS/1AC/48DC/100W48 V / 100 W
  1. UNO-PS/2AC Two-phase Standard Models (Non-C2LPS, No Class 2 Explosion Protection)
Ordine n.Modello completoPotenza nominale
2904371UNO-PS/2AC/24DC/90W/C2LPS90 W (C2LPS explosion-proof variant, il tuo modello)
2904376UNO-PS/2AC/24DC/150W150 W (standard two-phase model)
2904377UNO-PS/2AC/24DC/240W240 W (standard two-phase model)
  1. Regola di denominazione del modello (For Selection Reference)

UNO-PS / 1AC/2AC / 24DC / 90W / C2LPS

  1. 1AC = Single-phase input; 2AC = Two-phase 400V input (L1+L2, no neutral N)
  2. 24DC = 24 Uscita V CC
  3. 90W = Nominal output power
  4. C2LPS = Class 2 produzione + Divisione di prima classe 2 hazardous area certification (only available for the 90W model)
  5. Note supplementari
  6. Only two C2LPS explosion-proof models are available:

Monofase: 2902994

Bifase: 2904371 (il tuo modello). No higher-power two-phase C2LPS variants exist.

  1. No parallel current expansion for the entire UNO series. Use the QUINT series if parallel operation is required.
  2. All units come with screw terminals (SC). The second-generation UNO models use push-in PT terminals and are not mechanically interchangeable with this housing.