Nome completo del modello: MCR-T-UI, programmable temperature transmitter (custom ordered version: Pt100, 3-filo, -200~+850℃, 4-20mA output) Stato: Discontinued by manufacturer Basic Specifications Series: MCR-T isolated temperature transmitter, DIN rail mount Input: Termoresistenza Pt100, 3-wire type, measuring range -200℃ ~ +850℃ Output: 4…20 mA analog output Power supply: 24V DC Mounting: NS35 rail, screw connection Functions: segnale ...

  • Dettagli del prodotto

Nome completo del modello: MCR-T-UI, programmabile temperature transmitter (custom ordered version: Pt100, 3-filo, -200~+850℃, 4-20mA output)

Stato: Interrotto dal produttore

Specifiche di base

Serie: MCR-T isolated temperature transmitter, Montaggio su guida DIN

Ingresso: Termoresistenza Pt100, 3-wire type, measuring range -200℃ ~ +850℃

Produzione: 4…20 mA analog output

Alimentazione elettrica: 24A DC

Montaggio: NS35 rail, screw connection

Funzioni: signal isolation, temperature transmission, linear conversion, software configurable (this variant is factory preset with fixed range)

Classe di protezione: IP20, for cabinet installation

Cross-reference of models in the same series

2814090: MCR-T-UI (standard programmable version)

2814100: MCR-T-UI-NC

2814113: MCR-T-UI custom fixed-parameter version (Pt100 / 3-filo / -200~850℃ / 4-20mA)

Recommended replacement model (nuova generazione Fenice)

MACX MCR-T-UI-UP, Ordine n.: 2811394

Supports RTD / termocoppia / voltaggio / current multi-input, enhanced isolation, fully configurable; mechanically compatible for rail installation, the mainstream replacement for this series.

Note importanti

  1. 2814113 is a factory pre-configured fixed-range version, not a blank programmable base module. Do not directly replace it with 2814090 because the range settings differ.
  2. When purchasing second-hand spare parts, verify the input type, wiring method and output signal upon receipt.
  3. Software: MCR configuration software can read and verify internal parameters (legacy MCR configuration tool).

Tabella comparativa: 2814113 (MCR-T-UI-E) VS 2811394 (MACX MCR-T-UI-UP)

Articolo2814113 MCR-T-UI-E (Original spare part)2811394 MACX MCR-T-UI-UP (Modello sostitutivo)
Ordine n.28141132811394
StatoInterrotto, factory preloaded fixed parameters: Pt100, 3-filo, -200~850℃, 4-20mAProdotto attivo, all parameters fully configurable
Alimentazione elettrica18~30 VCC, typical 24VDC, ≤60mA18~30VDC wide-range power supply
Isolamento3-way isolation (Ingresso / Produzione / Energia)4-way isolation (Ingresso, Produzione, Energia, Relay circuit), higher noise immunity
Sensori supportatiRTD Pt/Ni/Cu, termocoppia, potentiometer; this unit locked to Pt100 3-wireRTD Pt/Ni/Cu (2/3/4-filo), all common thermocouples, mV, potentiometer
Measurement rangeFisso: Pt100 -200 ~ +850℃Freely configurable: RTD -250~850℃, thermocouple up to 2500℃
Uscita analogicaFixed 4…20mA4-20mA / 0-20mA / 0-10V / ±10V etc., forward/reverse range selectable
Additional outputNo relay alarm contactIntegrato 1 PDT limit relay output (allarme / threshold)
Configuration methodMCR / PI-CONF-WIN legacy software; this unit is factory locked to fixed range and cannot be modified freelyFDT framework software (PACTware) + DTM, online read/write via USB adapter
Safety certificationCE onlySIL2 / PL d, suitable for safety-related circuits
InstallazioneNS35 DIN rail, terminali a viteNS35 DIN rail, terminali a vite; rail footprint compatible for direct mounting
Precisione≤0.1%FS≤0.1%FS, better cold junction compensation performance
Disposizione del terminaleLegacy MCR terminal definitionDifferent terminal numbering! Cannot be wired directly when swapping, wiring modification is mandatory

✅ Critical Risk Reminder: It fits on the DIN rail mechanically, but terminal pinout is NOT compatible. Do not connect wiring directly without modification!

  1. Standard Wiring for 2814113 (MCR-T-UI-E), Pt100 3-wire

Terminal definition per original drawing

1, 2, 3: RTD input (3-wire Pt100)

1: One end of RTD

2: Compensation wire (for 3-wire measurement)

3: The other end of RTD

5, 6: Analog 4-20mA output (5+, 6-, current loop to PLC AI)

11, 12: Alimentazione DC24V (11=24V+, 12=0V/GND)

Osservazione: 2814113 is pre-configured, no DIP switch setting required. Power on and ready: -200℃ = 4mA, 850℃ = 20mA

  1. Wiring of Replacement 2811394 MACX MCR-T-UI-UP (Target setting: Pt100 3-wire, -200~850℃, 4-20mA)

RTD 3-wire sensor: 4.1 /4.2 /4.3 (RTD input)

Uscita di corrente analogica: 2.1(OUT+), 2.2(OUT-) → PLC 4-20mA AI channel

Alimentazione elettrica: 1.1=24V+, 1.2=GND

2.3/2.4: Threshold relay contacts (leave unused if not required)

Strip length 7mm, tightening torque 0.5~0.6Nm, conductor 0.2~2.5mm²

  1. Commissioning Procedure for On-site Replacement
  2. Spegnimento: Cut power to the module, sensor and PLC; mark and label all wire numbers
  3. Remove old module from rail and clip 2811394 to the same rail position
  4. Rewire according to new terminal definition; confirm the 3-wire Pt100 compensation core is not swapped
  5. Prepare PACTware + MACX DTM, Phoenix USB configuration cable (2902829)
  6. Accendere, connect software to module and download parameters:

Sensore: Pt100, IEC60751, 3-filo

Allineare: Lower limit -200℃, upper limit +850℃

Modalità di uscita: 4…20mA, inoltrare (low temperature = 4mA, high temperature = 20mA)

Filtro: default 0.5s (increase value for heavy interference)

Relè: disable threshold function if not needed

  1. Calibrazione & verification (obbligatorio)

Cold junction check: Compare Pt100 resistance and PLC current reading at ambient temperature

Simulation test: Use resistance box to simulate Pt100 resistance values, verify 4mA /20mA endpoints

  1. Save parameters into module, power cycle and re-test to confirm parameters are retained after power loss
  2. Archive parameter record, replacement complete
  3. Elenco di controllo per la risoluzione dei problemi (applies to both old and new modules)

Fixed 4mA output: Circuito aperto del sensore, broken 3-wire compensation line, loose sensor terminals

Fixed 20mA output: Input short circuit, Pt100 resistance out of upper limit

Instabile / lettura altalenante: Sensor cable routed together with power cables, ground interference; check isolation and single-end shield grounding

New module cannot be detected by software: USB driver, DTM version, insufficient supply voltage, terminali allentati

Phoenix Contact Temperature Transmitter Model & Elenco dei numeri d'ordine

Groups: Legacy MCR-T (interrotto, compreso 2814113)|MACX MCR-T (mainstream attuale, SIL2)|MINI MCR‑2 compact type|Loop-powered TS series (passive OLP)|Explosion-proof EX version

Abbreviation guide:

RST: Resistance temperature detector Pt100/Pt1000; TC: Termocoppia; UI: Ingresso universale; REL: With relay alarm; SU: Universal power; P.T: Push-in connection; C: Customer pre-configured

  1. Legacy MCR-T Series (Interrotto, DIN screw terminal, 3-way isolation)
ModelloOrdine n.Brief Description
MCR-T-UI2814090Universal temperature transmitter, blank programmable standard
MCR-T-UI-NC2814100Blank unconfigured, no default parameters
MCR-T-UI-E (your part)2814113Factory fixed config: Pt100 3-wire, -200~850℃, 4-20mA (key item)
MCR-T-UI-E/NC2814126Enhanced isolation, blank unconfigured
  1. MACX MCR‑T Series (Primary replacement, active, 4-way isolation, SIL2/PL d, terminale a vite)
ModelloOrdine n.Brief Description
MACX MCR-T-UI-UP2811394Universal RTD/TC/mV, uscita analogica (recommended for 2814113 sostituzione)
MACX MCR-T-UIREL-UP2811378Ingresso universale + 3 limit alarm relays, SIL2
  1. MINI MCR‑2 Compact Temperature Transmitter (6.2mm slim, vite / Push-in PT)
ModelloOrdine n.Descrizione
MINI MCR-2-RTD-UI2902055RTD dedicated, terminale a vite, programmabile
MINI MCR-2-RTD-UI-C2902053RST, vite, customer pre-configured
MINI MCR-2-RTD-UI-PT2905249RTD dedicated, Push-in connection
MINI MCR-2-RTD-UI-PT-C2905248RST, Push-in, pre-configured
MINI MCR-2-TC-UI2902049Thermocouple TC dedicated, terminale a vite
MINI MCR-2-TC-UI-C2902048TC, vite, pre-configured
MINI MCR-2-TC-UI-PT2902052Thermocouple TC dedicated, Push-in
MINI MCR-2-TC-UI-PT-C2902051TC, Push-in, pre-configured
MINI MCR-2-T-I2902037Temperature input directly to 4-20mA output, vite
MINI MCR-2-T-I-PT2902038Temperature to 4-20mA, Push-in
MINI MCR-2-T-REL2909887Temperatura + relè di allarme, vite
MINI MCR-2-T-REL-PT2909886Temperatura + relè di allarme, Push-in
MINI MCR-2-T-2RO2906877Dual relay temperature alarm, vite
MINI MCR-2-T-2RO-PT2906876Dual relay temperature alarm, Push-in
  1. MACX MCR‑TS Loop-powered Type (OLP, 2-wire loop supply, no separate 24V, HART optional)
ModelloOrdine n.Descrizione
MACX MCR-TS-I-OLP2908662Loop-powered temperature transmitter, vite, standard
MACX MCR-TS-I-OLP-SP2908664Loop-powered, HART version
MACX MCR-1TS-I-OLP-SP1145196Monocanale, HART, Push-in

5.Explosion-proof EX Intrinsically Safe Version (Zona 0/1/2, chemical hazardous area)

ModelloOrdine n.Descrizione
MACX MCR-EX-TS-I-OLP2908660Explosion-proof loop-powered temperature transmitter
MACX MCR-EX-TS-I-OLP-SP2908661A prova di esplosione + HART
FA MCR-EX-FD-TUI-UI-2REL-UP2907781Field-mounted explosion-proof multi-function temperature module
  1. Matching Configuration Accessories
NomeOrdine n.Scopo
MCR-PAC-T-USB2309000USB configuration cable for legacy MCR-T (2814xxx)
IFS-USB-PROG2902829Universal USB configuration adapter for MACX / MINI MCR‑2 (PACTware DTM)

Sostituzione preferita: 2811394 MACX MCR-T-UI-UP (full function coverage, SIL2, configurable for Pt100 3-wire -200~850℃ 4-20mA)

With alarm relay requirement: 2811378

Cabinet space limited, slim type: MINI MCR‑2‑RTD‑UI (2902055)

Passive 2-wire loop power supply: TS-I-OLP (2908662)

Prec:

Lascia una risposta

Lasciate un messaggio