(Altivar Process ATV650)
Model code explanation: ATV650 = Altivar Process IP55 wall-mounted guidare; D30 = 30 kW normal duty rating; N4 = 3-phase 380~480V, without integrated input disconnect switch (version with switch carries suffix E: ATV650D30N4E)
✅ Core Electrical Specifications
Potenza nominale: 30 kW normal duty / 22 kW heavy duty (40HP / 25HP)
Fornitura: 3-phase 380…480V, 50/60 Hz
Corrente di uscita, dovere normale: 61.5 UN; heavy duty current: 39.2 UN (4 kHz carrier frequency)
Dimensioni del telaio: Frame B (Frame B covers 30~45 kW range)
Enclosure rating: IP55, wall-mounted design for local field installation, no additional control cabinet required
Raffreddamento: Raffreddamento ad aria forzata
Motori compatibili: Asynchronous motors, synchronous reluctance motors
Filtro EMC integrato: Classe C2 (motor cable ≤50 m), Class C3 (motor cable ≤150 m)
✅ Interfaces & Comunicazione
Integrated Dual-port Ethernet (ModBus TCP) + RS485Modbus
I/O digitali: 8 DI, 3 configurable relay outputs
I/O analogico: AI / AL; on-board process PID, flow estimation, energy metering dashboard
Espansione: Supports Profibus-DP, Profinet, EtherNet/IP communication option cards
Accessori standard: Chinese graphic keypad, QR code for maintenance access, equipment asset monitoring, drift alarm, Fermare&Go energy-saving function
✅ Typical Applications
Water supply pumps, wastewater pumps, Ventilatori HVAC, torri di raffreddamento, chemical fluid handling, air compressors and other process fluid loads. Focused on energy saving, asset management and predictive maintenance; adatto per polverosi, humid field environments (IP55)
✅ Cross-series Comparison & Sostituzioni
1. ATV650D30N4E: Stessa potenza, with integrated load disconnect switch
2. ATV630D30N4: Stessa potenza, IP20 cabinet-mounted bare drive (no outer enclosure)
3. Upgrade replacement: ATV660D30N4; for heavy-duty impact loads, select ATV950
✅ Important Notes
IP55 units have stricter heat dissipation requirements; reserve vertical ventilation clearance above and below when wall mounting
Dual rating mode (Dovere normale / Servizio pesante) can be switched in parameter group 5.2
Software di messa in servizio: Quindi Muoviti, firmware version V4.6IE47
ATV650 (Altivar Process ATV600 Series) Fault Code List
1. Fornitura & Input Side Faults
1. IPF / IPL Input phase loss / 3-squilibrio di fase
Causa: Missing input phase, blown fuse, severe 3-phase voltage unbalance, 3-phase detection enabled incorrectly for single-phase supply
Rimedio: Check incoming circuit breaker / fusibili; set IPL to nO to disable phase loss detection if running on single-phase supply
2. OVF DC bus overvoltage
Causa: Mains voltage too high, deceleration time too short, regenerative energy from high-inertia loads
Rimedio: Increase deceleration time; fit braking resistor; activate adaptive deceleration brA
3. ObF Overvoltage stall (trip due to excessive DC bus voltage)
Causa: Fast deceleration, high load inertia, excessive regenerative energy
Rimedio: Estendere il tempo di decelerazione; enable stall prevention; installare l'unità di frenatura + resistor
4. UVF DC bus undervoltage
Causa: Mains dip, momentary power loss, loose incoming connections, contactor chatter
Rimedio: Controllare l'alimentazione; extend undervoltage delay; improve wiring connections
5. PHF Supply phase sequence error
Rimedio: Swap any two incoming phases L1/L2/L3
2. Produzione & Motor Side Faults
1. OCF Output overcurrent
Causa: Motor locked rotor, shorted output cable, rottura dell'isolamento del motore, rapid acceleration/deceleration
Rimedio: Disconnect motor and run no-load test; reduce acceleration/deceleration ramps; test cable insulation to earth with megger
2. SCF Output short-circuit / guasto a terra
Causa: Damaged motor cable shorted to earth, motor winding earth fault, failed drive IGBT
Rimedio: Disconnect motor and test drive output separately; measure motor winding insulation to earth
3. OPF2 / OPF Output phase loss (perdita di fase del motore)
Causa: Loose motor terminals, open output contactor, small motor running at light load
Rimedio: Tighten motor wiring; disable OPL phase loss detection if an output contactor is used; disable phase loss protection for small motors
4. OLF Motor thermal overload
Causa: Continuous overloading, rotore bloccato, motor thermal current ITH parameter set too low
Rimedio: Ridurre il carico; adjust motor thermal current ITH; wait for motor to cool before reset
5. OLC Drive hardware current limit overload
Rimedio: Ridurre il carico; check output for short circuits; lower carrier frequency
6. OTF1 / OTF2 Motor PTC thermistor overheat
Causa: Motor winding overtemperature, broken or shorted PTC probe
Rimedio: Check motor temperature; measure PTC resistance; disable this protection if no temperature probe is fitted
3. Drive Overheating Faults
1. OHF Drive heatsink overtemperature (common fault)
Causa: Ventola di raffreddamento guasta, clogged filter, insufficient mounting clearance, temperatura ambiente elevata, heavy dust accumulation
Rimedio: Clean air filter; check cooling fan; set fan permanent ON mode; maintain vertical ventilation clearance; monitor heatsink temperature parameter THD
2. OHFd DC reactor overtemperature
Rimedio: Ridurre il carico; improve enclosure ventilation
4. Braking Circuit Faults
1. bUF Braking circuit fault
Causa: Open braking resistor, failed braking IGBT, cablaggio allentato
Rimedio: Check braking resistor resistance and connections; test braking unit at no load
2. bOF Braking resistor overload
Rimedio: Select higher resistance braking resistor; prolungare il tempo di decelerazione
5. Safety Circuit Faults (STO Safe Torque Off)
1. SAFF STO safety circuit fault
Causa: Mismatched timing between STOA and STOB (time difference >1 S), broken wiring, internal hardware fault
Rimedio: Check both STO wiring paths; ensure STOA and STOB switch simultaneously; both paths must be shorted together for bypass
2. SdF Safety function active (normal stop, not a hardware fault)
Stato: STO terminals open, drive locked; reset only after restoring STO wiring
6. Comunicazione & Analog Signal Faults
1. CnF1~CnF4 Communication link fault (ModBus TCP / RS485)
Causa: Damaged Ethernet cable, incorrect termination resistor, Conflitto di indirizzi IP, electrical noise interference
Rimedio: Inspect cables; use shielded communication cable; verify IP settings; reduce baud rate
2. AIF Analog input wire break (4–20 mA current signal)
Causa: Broken sensor cable, circuito aperto, signal below 4 mA
Rimedio: Check transmitter and signal wiring; lower wire-break threshold if required
3. AOF Analog output fault
7. Internal Hardware Faults (InF series, generally hardware damage)
1. InF8 Internal power supply fault (power board supply abnormal)
Rimedio: Full power cycle; repeated fault = replace power board
2. InFL (InF21) Real-time clock fault, keypad communication failure
Rimedio: Remove keypad, remove battery and re-power; replace keypad; if fault persists, sostituire la scheda di controllo
3. InF1~InF7, InF9~InF30 Other internal hardware errors
Rimedio: Ciclo di alimentazione; fault cannot be cleared → control board / power board damaged, requires repair or replacement
8. Process-specific Faults (Pompa / fluid functions exclusive to ATV650)
1. iPPF Low inlet pressure protection (dry-run / low suction protection)
Causa: Insufficient inlet pressure, faulty pressure transmitter, protection threshold set too high
Rimedio: Check pipeline suction pressure; calibrate pressure transducer; reduce low-pressure threshold
2. HPF High pressure protection, LPF Low pressure protection, FLF Flow fault
3. DryF Dry-run protection (pump running without fluid)
Rimedio: Verify pump suction availability; adjust dry-run current threshold
9. Other General Faults
1. FrF Frequency feedback fault (encoder wire break)
2. USF Motor autotune failed on power-up
3. CLF Cooling circuit fault (water-cooled versions only)
4. tJF Motor stall protection
10. Fault Reset Methods
1. Auto-reset: Enable automatic retry via parameter Atr
2. Ripristino manuale: Assign DI terminal function rSF for remote reset; reset via keypad
3. Internal hardware faults (InF codes): Require full power cycle; some faults need board replacement
Model Prefix Rules
ATV650: Altivar Process IP55 wall-mounted variable speed drive (3-fase 380~480V)
U: Low power range (0.75~7.5 kW); D: Medium power range (11~90 kW); C: High power floor-standing unit (110 kW and above, IP54)
N4: Without integrated disconnect switch; N4E: With integrated load disconnect switch
Enclosure rating: All wall-mounted units = IP55; floor-standing C models = IP54
Wall-mounted IP55 Full Model List (N4 without switch / N4E with switch, main domestic variants)
Frame A (0.75~22 kW)
| Potenza nominale | Model without switch | Model with switch |
| 0.75 kW | ATV650U07N4 | ATV650U07N4E |
| 1.5 kW | ATV650U15N4 | ATV650U15N4E |
| 2.2 kW | ATV650U22N4 | ATV650U22N4E |
| 3 kW | ATV650U30N4 | ATV650U30N4E |
| 4 kW | ATV650U40N4 | ATV650U40N4E |
| 5.5 kW | ATV650U55N4 | ATV650U55N4E |
| 7.5 kW | ATV650U75N4 | ATV650U75N4E |
| 11 kW | ATV650D11N4 | ATV650D11N4E |
| 15 kW | ATV650D15N4 | ATV650D15N4E |
| 18.5 kW | ATV650D18N4 | ATV650D18N4E |
| 22 kW | ATV650D22N4 | ATV650D22N4E |
Frame B (30~45 kW, includes your D30N4)
| Potenza nominale | Model without switch | Model with switch |
| 30 kW | ATV650D30N4 | ATV650D30N4E |
| 37 kW | ATV650D37N4 | ATV650D37N4E |
| 45 kW | ATV650D45N4 | ATV650D45N4E |
Telaio C (55~90 kW)
| Potenza nominale | Model without switch | Model with switch |
| 55 kW | ATV650D55N4 | ATV650D55N4E |
| 75 kW | ATV650D75N4 | ATV650D75N4E |
| 90 kW | ATV650D90N4 | ATV650D90N4E |
High Power Floor-standing Units (C range, IP54, installazione verticale)
Model format: ATV650CxxN4F (all fitted with disconnect switch)
110/132/160/200/250/315 kW:
ATV650C11N4F, C13N4F, C16N4F, C20N4F, C25N4F, C31N4F
Confusable Series Comparison
1. ATV650: IP55 wall-mounted, for local field installation (the series you are using)
2. ATV630: Stessa potenza, IP20 cabinet bare drive, no outer enclosure
3. ATV660: Newer generation, upgrade replacement for ATV650
4. ATV950: Azionamento per carichi pesanti, for shock loads other than fans and pumps
Ulteriori informazioni chiave
Suffix U = low power; D = medium power; C = high power floor-standing
Suffix E = integrated load disconnect switch; no E = no switch
Standard features for all units: Dual-port Modbus TCP + RS485, built-in Class C2/C3 EMC filter, Chinese graphic keypad, STO Safe Torque Off