Specifiche tecniche & Guida all'applicazione
- Panoramica del prodotto
Schneider LUCA32BL is a standard control unit from the TeSys Ultra series (formerly TeSys U series), a component of three-phase motor starters. It must be used with LUB series power bases (such as LUB32 / LUB38) to form a complete motor starting and protection system. It features thermal-magnetic protection and is suitable for industrial applications requiring basic motor protection including overload, cortocircuito, perdita di fase, phase imbalance, and earth fault protection.
- Parametri tecnici fondamentali
| Articolo | Specifica | Descrizione |
| Tipo di prodotto | Standard Control Unit | For TeSys Ultra series motor starters |
| Tensione di controllo | 24 VCC | Coil supply voltage, requires separate external power supply |
| Current Setting Range | 8 A ~ 32 UN | Adjustable overload protection range |
| Tensione del circuito principale | Fino a 690 VCA | For three‑phase power systems |
| Classe di protezione | Classe 10 | Trip time approx. 20 s at 1.5 × corrente nominale |
| Potenza motore adatta | 15 kW (400 V) / 18.5 kW (690 V) | For three‑phase self‑cooled motors |
| Frequenza operativa | 40–60 Hz | Compliant with global power grid standards |
| Temperatura operativa | -25 °C~ +70 °C | Wide temperature range for industrial environments |
| Approvazioni | UL 508, CSA C22‑2, CEI/EN, CCC | Meets international and Chinese standards |
- Caratteristiche
- Protezione completa: Sovraccarico, cortocircuito, perdita di fase, phase imbalance, and earth fault protection
- Ripristino manuale: Enables quick restart after fault clearance
- Modbus Communication: Supports configuration and data transfer for remote monitoring and diagnostics
- Flexible Mounting: Compatible with various TeSys Ultra power bases
- Alta compatibilità: Suitable for utilization categories AC-41 / AC-43 / AC-44
- Design compatto: Saves cabinet space and increases mounting density
- Applicazioni
– General machinery including fans, pompe, e compressori
– Industrial line equipment such as conveyors and mixers
– Small factory automation systems
– Applications requiring basic motor protection with 24 VDC control signals
– Replacement for traditional thermal relay + contactor combinations, offering more reliable protection and easier installation
- Istruzioni per l'uso
- Installation Requirement: Must be used with a matching LUB series power base with correct electrical connections
- Regole di cablaggio: Stabile 24 VDC supply for control circuit; three-phase power for main circuit
- Setting Recommendation: Adjust overload setting according to motor rated current within 8 A–32 A
- Maintenance Note: Regularly check control unit status to ensure proper protection operation
- Communication Setup: Configure Modbus parameters per manual if communication is required
- Informazioni sulla compatibilità
Compatible Power Bases: TeSys Ultra series including LUB32 (32 UN), LUB38 (38 UN)
Sostituzione: Can replace some traditional thermal relay + contactor assemblies with an integrated solution
Percorso di aggiornamento: For advanced functions such as built-in soft starting and energy monitoring, consider TeSys T or TeSys Giga series
The Schneider LUCA32BL is a cost-effective standard motor control unit. Con il suo design compatto, protezione completa, e ampia compatibilità, it is an ideal choice for starting and protecting three-phase motors in industrial automation, especially for cost-sensitive applications requiring basic protection.
TeSys Ultra (formerly TeSys U) Standard Control Unit Range & Power Bases
- Complete List of Standard Control Units (LUCA Series)
TeSys Ultra standard control units use thermal-magnetic protection and provide overload, cortocircuito, perdita di fase, phase imbalance, and earth fault protection. They are only compatible with standard power bases (Serie LUB) and not with advanced bases (LUBxxx0 series). All models are Class 10, 3-palo (3P) three-phase devices.
| Current Setting Range | 24 VCC | 48–72 V AC/DC | 110–240 V AC/DC | 24 VCA | Potenza del motore (400 V) |
| 0.35–1.4 A | LUCA1XBL | LUCA1XES | - | LUCA1XB | 0.75 kW |
| 1.25–5 A | LUCA05BL | LUCA05ES | LUCA05FU | LUCA05B | 2.2 kW |
| 3–12 A | LUCA12BL | LUCA12ES | LUCA12FU | LUCA12B | 5.5 kW |
| 4.5–18 A | LUCA18BL | LUCA18ES | LUCA18FU | LUCA18B | 7.5 kW |
| 8–32 A | LUCA32BL | LUCA32ES | LUCA32FU | LUCA32B | 15 kW |
Convenzione di denominazione dei modelli
LUC: Prefix for TeSys Ultra control units
UN: Standard control unit (Advanced versions: C/D/M)
XX: Current range code (1X = 0.35–1.4 A, 05 = 1.25–5 A, 12 = 3–12 A, 18 = 4.5–18 A, 32 = 8–32 A)
Suffisso: BL = 24 VCC, ES = 48–72 V AC/DC, FU = 110–240 V AC/DC, B = 24 VCA
- Complete List of Power Bases (LUB Series)
TeSys Ultra power bases are divided into standard bases (nessun suffisso) and advanced bases (suffisso 0), both 3P three-phase, for different control unit types.
2.1 Standard Power Bases (For LUCA Series Standard Control Units)
| Modello | Corrente nominale | Tensione nominale | Contatti ausiliari | Compatible Control Units | Max Motor Power (400 V) |
| LUB12 | 12 UN | 690 V | Opzionale | LUCA1X / LUCA05 / LUCA12 | 5.5 kW |
| LUB32 | 32 UN | 690 V | Opzionale | Full LUCA series | 15 kW |
| LUB38 | 38 UN | 690 V | Opzionale | Full LUCA series | 18.5 kW |
2.2 Advanced Power Bases (For LUCC / LUCD / LUCM Advanced Control Units)
| Modello | Corrente nominale | Tensione nominale | Contatti ausiliari | Compatible Control Units | Max Motor Power (400 V) |
| LUB120 | 12 UN | 690 V | 1NO + 1NC | LUCC/LUCD/LUCM (1.25–12 A) | 5.5 kW |
| LUB320 | 32 UN | 690 V | 1NO + 1NC | LUCC/LUCD/LUCM (full range) | 15 kW |
| LUB380 | 38 UN | 690 V | 1NO + 1NC | LUCC/LUCD/LUCM (full range) | 18.5 kW |
2.3 Reversing Power Bases (For Reversing Control Units)
| Modello | Corrente nominale | Tensione nominale | Compatible Reversing Control Units | Max Motor Power (400 V) |
| LU2B12 | 12 UN | 690 V | LU2A1X / LU2A05 / LU2A12 | 5.5 kW |
| LU2B32 | 32 UN | 690 V | Full LU2A series | 15 kW |
| LU2B38 | 38 UN | 690 V | Full LU2A series | 18.5 kW |
- Key Matching Rules
- Standard Control Unit (LUCA) + Standard Base (LUBxx): Basic motor protection with thermal-magnetic protection and standard control
- Advanced Control Unit (LUCC/LUCD/LUCM) + Advanced Base (LUBxx0): Premium protection with diagnostics, comunicazione, and extended functions
- Control unit current range ≤ base rated current: per esempio., LUCA32BL (8–32 A) may only be used with LUB32 (32 UN) or LUB38 (38 UN), not LUB12 (12 UN)
- Control voltage is independent of main voltage: Control unit powered via terminals A1/A2 on the base, tipicamente 24 VDC/AC, 48–72 V AC/DC, or 110–240 V AC/DC
- Note applicative
- Montaggio: Control unit plugs directly into power base and locks with a clip; no additional tools required
- Protezione: Basic protection including Class 10 sovraccarico, cortocircuito (13 × Ir max), phase imbalance, perdita di fase, and earth fault (equipment protection)
- Comunicazione: Supports Modbus (with optional communication module) for remote monitoring and diagnostics
- Ambiente: Temperatura operativa -25 °C~ +70 °C, suitable for most industrial environments
La combinazione di unità di controllo standard TeSys Ultra (serie LUCA) e basi di potere (Serie LUB) fornisce una soluzione flessibile e affidabile per l'avviamento e la protezione dei motori, covering three-phase motors from 0.75 kW a 18.5 kW. Selection should be based on motor rated current, tensione di controllo, and protection requirements to ensure safe and stable operation.
Contattore,interruttore automatico,inverter solare,contatore elettrico,batterie solari