Harmony Magelis Easy GXU Series (Interrotto). Sostituzione consigliata: HMI ET6400
✅ Model Code Explanation
HMI: Interfaccia uomo-macchina
GXU: Easy GXU economy HMI series
3: 7-schermo largo pollici
5: Universal version (dual serial ports + Ethernet)
12: Equipped with RTC real-time clock
📌 Core Hardware Specifications
| Articolo | Specifica |
| Display | 7-inch wide TFT LCD, tocco resistivo |
| Risoluzione | 800×480 WVGA |
| Color Depth | 65536 colori |
| Backlight Lifespan | 20000 ore |
| Alimentazione elettrica | DC24V |
| Memoria | Application flash: 48MB; DDR RAM:128MB; Backup memory:128KB |
| Orologio in tempo reale | Built-in RTC |
| Dimensione del ritaglio | 190 mm× 135 mm |
| Grado di protezione | Pannello frontale IP65 |
🔌 Interface Configuration
- COM1 (DB9 male): RS232C
- COM2 (DB9 male): RS422 / RS485
- Ethernet: 10/100BASE-TX, massimo. 48 connected slaves
- Mini-B USB (Device port): Scaricamento del programma
- USB-A (Host port): Unità flash USB, mouse and other peripherals
🛠️ Configuration Software
Vijeo Designer Basic. Supporta Schneider PLC (M218/M241/M251 etc.), ModBus RTU/TCP, compatible with 3rd-party Modbus devices.
📋 Application Scenarios
Piccolo & medium automation projects: macchine per l'imballaggio, HVAC, linee di produzione, piccole stazioni di pompaggio, local operator panels for low-voltage cabinets.
🔄 Discontinuation & Informazioni sulla sostituzione
HMIGXU3512: No new orders accepted, spare parts maintenance phase
Sostituzione consigliata ufficialmente: HMIET6400 (Harmony ET6 series 7″)
Same 7-inch 800×480, dual serial ports + Ethernet + USB, DC24V
Aggiornato a 16 million colors, stronger hardware performance, compatible cutout dimension; configuration software changed to EcoStruxure Machine Expert HMI (formerly SoMachine HMI)
⚠️ Nota: GXU project files cannot be imported directly into ET6. Screens need re-configuration, most communication protocols remain available.
🧰 Troubleshooting for HMIGXU3512 Common Faults
- Black screen at power-on: Check 24V power supply, blown fuse; backlight aging (rated 20000h life)
- Touch unresponsive: Damaged touch panel, loose flat cable; corrosion in humid environment
- Errore di comunicazione seriale: Verify COM1/COM2 wiring, RS232/485 dip switch, station number, baud rate and parity
- Ethernet disconnection: Check network cable & interruttore; HMI supports up to 48 schiavi, do not exceed limit
- Time loss: Depleted backup battery on mainboard, replace internal battery of HMI
📎 Spare Parts & Accessori
Download cable: Mini-B USB cable
Serial communication cable: DB9 serial cable (RS485/232)
Replacement parts: touch panel, backlight module, power board (repair components)
HMIGXU3512 Alternative Models (Schneider OEM alternatives + 3rd-party compatible models)
Original unit: 7″ WVGA, dual serial ports + Ethernet + USB, RTC, DC24V, cutout 190×135mm, Magelis GXU, Vijeo Designer Basic.
- Schneider OEM Alternatives (Raccomandato, consistent brand & stable spare parts supply)
- HMIET6400【Official Direct Replacement】
Schermo:7-inch wide 800×480, 16 million colors, tocco resistivo
Interfacce: COM1/COM2 (RS232/485/422), 10/100 Ethernet, USB Host+Device, built-in RTC
Power DC24V, fully compatible cutout size 190×135mm, front panel IP65
Software: EcoStruxure Machine Expert HMI (SoMachine HMI)
Vantaggi: Official designated replacement, hardware interfaces match one-to-one, nessuna modifica del mobile richiesta
Svantaggi: GXU project cannot be imported directly, re-design screens required; download port changed to Micro USB instead of Mini-B
- HMIET5400【Economical OEM alternative, preferred for new projects】
7-pollice, 800×480, dual serial ports + Ethernet + USB, RTC, DC24V
Cutout dimension 190×135mm, fori di montaggio compatibili, lower price than ET6400
Software: EcoStruxure Machine Expert HMI
Applicazione: Bulk new project procurement, renovation projects with limited budget
Descrizione: ET5 series is Schneider’s new entry HMI, long-term main replacement product for GXU.
- HMIGXU3500 (Same-series old stock spare part, NOT recommended for new projects)
Same GXU series 7-inch HMI, niente Ethernet, no RTC
Only for equipment using serial communication only, no Ethernet or time function; discontinued spare with unstable stock, only emergency replacement.
- Upgrade option: HMIDT351 (Magelis GTU, mid-range higher performance)
7-inch WVGA, dual serial ports + Ethernet + USB, larger storage & prestazioni migliori
Software: Vijeo Designer (partial GXU screen migration available)
Svantaggi: Much higher price, different cutout dimension, cabinet cutout modification required; for high-reliability machinery.
- 3rd-party Compatible Alternatives (Retain original PLC communication, brand change for cost-down retrofit)
All support Modbus RTU/TCP to connect Schneider M218/M241/M251 PLCs, screen projects need full rework.
- Weinview TK8072IP / MT8072IP
7-pollice, dual serial ports + Ethernet, DC24V; ampio inventario di mercato, user-friendly software, prestazione ad alto costo; similar cutout, minor cabinet modification.
- MCGS TPC7022Ni
Mainstream domestic HMI, MCGS configuration software, mature Modbus communication; widely used in domestic machinery, convenient local after-sales service.
- FLEXEM FE6070W
7-schermo largo pollici, dual serial ports + Ethernet, RTC; many industrial application cases in packaging & HVAC.
- Pro-face PFXGP4402WADW (Schneider subsidiary brand)
7-pollice, elevata stabilità, widely used in high-end industrial machines; relatively high price.
📌 Selection & Replacement Comparison Table
| Replacement Option | Mounting Modification | Project Reuse | Costo di approvvigionamento | Recommended Application |
| HMIET6400 | Almost none | Cannot reuse, full reconfiguration | Medio | Machine retrofit, OEM spare part requirement |
| HMIET5400 | Almost none | Cannot reuse, full reconfiguration | Basso | New project bulk order |
| HMIDT351 | Cutout modification required | Partial screen migration possible | Alto | High-end equipment, high reliability requirement |
| Weinview TK8072IP | Minor cutout adjustment | Full rework | Basso | Cost-down retrofit, brand unrestricted |
⚠️ Important Notes for Replacement
- Compatible cutout ≠ compatible project: GXU (Vijeo Designer Basic) project files cannot be imported to ET5/ET6. Screens, tags and alarms must be rebuilt; protocolli di comunicazione (ModBus RTU/TCP) can be retained.
- Cablaggio: COM pin assignment differs between HMIGXU3512 and replacement models. Verify serial pin definition before power-on to avoid communication port burnout.
- Orologio RTC: ET5/ET6 have built-in RTC, supports time retention after power loss same as original unit.
Schneider Magelis Easy GXU (HMIGXU) Elenco completo dei modelli
Series Description: Easy GXU economy HMI, all models discontinued. Software di configurazione: Vijeo Designer Basic; 65536-color TFT, DC24V, front panel IP65, built-in RTC real-time clock.
| Modello | Dimensioni dello schermo | Dimensione del ritaglio | Configurazione dell'interfaccia | Memoria del programma | Posizionamento |
| HMIGXU3500 | 7-inch wide 800×480 | 190×135 mm | COM: RS422/485; Mini-B USB download; Niente Ethernet, no USB-A host | 32 MB | Modello base, single serial port |
| HMIGXU3512 | 7-inch wide 800×480 | 190×135 mm | COM1 RS232 + COM2 RS422/485; 10/100 Ethernet; Mini-B download; USB-A host | 48 MB | Modello universale (your target model) |
| HMIGXU5500 | 10.1-inch wide 800×480 | 255×185 mm | COM: RS422/485; Mini-B USB download; Niente Ethernet, no USB-A host | 32 MB | Modello base, single serial port |
| HMIGXU5512 | 10.1-inch wide 800×480 | 255×185 mm | COM1 RS232 + COM2 RS422/485; 10/100 Ethernet; Mini-B download; USB-A host | 48 MB | 10-inch universal model |
✅ Model Coding Rule (GXU Series)
HMIGXU 3 5 12
- 3 = 7 pollice; 5 =10.1 inch
- 5 = GXU series
- Ultime due cifre:
00: Versione base, Solo RS485, niente Ethernet & USB-A
12: Full version, dual serial ports + Ethernet + USB-A host port
📌 Corresponding OEM Replacement Models (One-to-one mapping for 4 GXU models)
| Original GXU Model | Schneider Recommended Replacement | Cutout Compatible |
| HMIGXU3500 | HMIET5400 / HMIET6400 | ✅ 190×135mm |
| HMIGXU3512 | HMIET5400 / HMIET6400 | ✅ 190×135mm |
| HMIGXU5500 | HMIET5500 / HMIET6500 | ✅ 255×185mm |
| HMIGXU5512 | HMIET5500 / HMIET6500 | ✅ 255×185mm |
Osservazioni: ET5 = Economy replacement; ET6 = High-performance OEM replacement; GXU projects cannot be imported directly to ET series, screens need re-configuration.
HMIGXU3512 Full Detailed Specifications (Schneider Magelis Easy GXU)
Stato del prodotto: Interrotto; Software di configurazione: Vijeo Designer Basic
- Display & Tocco
Dimensioni dello schermo: 7-inch wide TFT LCD
Risoluzione: 800 × 480 WVGA
Color Depth: 65536 colori (16-morso)
Tocca Tipo: Resistive touchscreen
Retroilluminazione: Retroilluminazione a LED, rated lifespan 20000 ore
Built-in RTC real-time clock with replaceable backup battery for time retention during power loss
- Memoria
Application Flash: 48 MB
DDR RAM: 128 MB
Backup Memory: 128 KB (for recipe, alarm log and small data storage)
- Specifiche dell'interfaccia
- COM1 (DB9 male): RS232C
- COM2 (DB9 male): RS422 / RS485
- Ethernet: 10/100BASE-TX, ModBus TCP; massimo 48 dispositivi schiavi
- Mini-B USB (Dispositivo): Scaricamento del programma, connect to PC
- USB-A (Ospite): Unità flash USB, USB mouse, project upload / alarm log export
- Specifiche elettriche
Fornitura nominale: CC 24 V
Intervallo di tensione operativa: DC 20.4 ~ 28.8V
Consumo energetico tipico: Approx.7W
Peso: 0.56 kg
- Dimensione meccanica & Protezione
Overall Panel Size: 204 × 149 mm
Cabinet Cutout: 190 × 135 mm
Front Panel Protection: IP65 (anteriore), rear IP20
Montaggio: Embedded panel mounting
- Condizioni ambientali
Temperatura operativa: 0 ~ +50 ℃
Temperatura di conservazione: -20 ~ +60 ℃
Operating Humidity: 10% ~ 90%, senza condensa
Vibration Compliance: norma CEI
Certificazioni: CE, RoHS
- Protocolli di comunicazione supportati
ModBus RTU (Seriale)
ModBus TCP (Ethernet)
Schneider native protocol: compatible with M218/M241/M251 SoMachine PLCs
Supports multi-device networking, serial port and Ethernet work simultaneously
- Funzioni del software
Software di configurazione: Vijeo Designer Basic
Funzioni: Screen display, button operation, data monitoring, allarme, trend chart, recipe, time scheduler, project backup/restore via USB flash drive
No advanced script function, economy-class HMI
- OEM Replacement Models
Sostituzione consigliata: HMIET6400 (fully compatible cutout, software upgraded to EcoStruxure Machine Expert HMI)
Economy replacement: HMIET5400
Contattore,interruttore automatico,sensore,Codificatore,PLC,Convertitore