- Full Model Interpretation
| Model Part | Descrizione | Details |
| CVS | Serie di prodotti | EasyPact CVS series MCCB, for distribution protection and motor protection |
| 250 | Corrente del fotogramma | 250A frame size, suitable for rated current range 100~250A |
| F | Breaking Capacity Class | 36kA@415V AC, standard breaking capacity (N=50kA, H=70kA optional) |
| 3P | Number of Poles | 3-interruttore automatico, for three‑phase circuit protection |
| 250UN | Corrente nominale | Rated operational current 250A (a 40 ℃), adjustable thermal‑magnetic trip 175~250A |
| TM-D | Tipo di unità di sgancio | Thermal‑magnetic trip (TM), D‑type adjustable (long‑time delay adjustable) |
| LV525333 | Official Part Number | Standard SKU corresponding to CVS250F-3P-250A |
- Key Technical Specifications
| Articolo | Valore | Note |
| Tensione nominale (Ui/Ue) | 690V/415V AC 50/60Hz | Compatible with global mainstream voltage systems |
| Corrente nominale (Iu/In) | 250A/250A (40℃) | Thermal‑magnetic trip adjustable range: 175~250A |
| Capacità di interruzione (Icu/Ics) | 36kA/36kA (415V) | Ics=100%Icu; 70kA@220/240V AC |
| Rated Impulse Withstand Voltage (Uimp) | 8kV | Complies with EN/IEC 60947-2 |
| Instantaneous Trip Current (Ii) | 2000UN | Fixed value for short‑circuit protection |
| Mechanical/Electrical Endurance | 20,000 / 10,000 operazioni | At 415V In, è conforme alla CEI 60947-2 |
| Degree of Protection | IP40 | Dust‑tight and splash‑proof, adatto per ambienti industriali |
| Connection Type | Front wiring / Rear wiring | Flexible for various installation requirements |
| Dimensioni (W×H×D) | 105×226×86mm | Compact design, saves panel space |
| Pollution Class | 3 | Suitable for industrial pollution conditions |
- Core Product Advantages
- Comprehensive Protection: Thermal‑magnetic trip provides long‑time overload protection and instantaneous short‑circuit protection; long‑time delay adjustable (Ir=0.7~1.0In) for various load characteristics.
- High‑Reliability Breaking: 36kA high breaking capacity, Ics=100%Icu, ensures reliable fault interruption and equipment safety.
- Installazione flessibile: Supports front/rear wiring; 3P/4P available, adaptable to different switchboard layouts.
- Eco‑Compliant: Green Premium certified, Conforme alla direttiva RoHS, free of hazardous substances, meets sustainable development requirements.
- Manutenzione facile: Progettazione modulare, replaceable trip unit, convenient for maintenance and upgrade, reduces lifecycle cost.
- Enhanced Safety: Standard isolation function, improves operational safety, è conforme alla CEI 60947-2 isolation requirements.
- Operating Principle
CVS250F-3P-250A uses thermal‑magnetic tripping protection:
- Protezione da sovraccarico (Long Time Delay): Bimetal strip bends under heat and triggers the trip mechanism. Delay decreases as current increases; Ir adjustable 175~250A.
- Short‑circuit Protection (Istantaneo): Electromagnetic coil generates strong magnetic force, attracts armature and triggers instant trip at fixed 2000A without delay.
- Caratteristica di intervento: Conforme all'IEC 60947-2, Category A for distribution protection, protects cables and equipment against overload and short‑circuit damage.
- Applicazioni tipiche
- Distribuzione dell'energia industriale: Main protection for three‑phase power equipment in factories and workshops, such as air compressors, pumps, tifosi.
- Edifici commerciali: Distribution mainline protection for offices, centri commerciali, hotels, ensuring power continuity.
- Centri dati: Power protection for UPS systems and server racks, preventing overload/short‑circuit impact on critical loads.
- Infrastructure: Electrical system protection for hospitals, schools, public facilities, ensuring public safety.
- Renewable Energy: AC‑side protection for PV inverters and energy storage systems, suitable for new energy applications.
- Installazione & Operation Guidelines
- Ambiente: Install in dry area below 40℃, avoid moisture, corrosion, vibrazione; max installation altitude 2000m.
- Cablaggio: Use copper/aluminum conductors suitable for 250A (≥95mm² copper recommended), torque per Schneider specifications.
- Protection Coordination: Coordinate with downstream breakers/fuses to ensure selective protection and avoid non‑selective tripping.
- Setting: Adjust long‑time delay current Ir (175~250A) according to load for accurate protection.
- Manutenzione: Regularly check mechanism and terminals for looseness or overheating; full inspection at least once per year.
- Series Models & Alternatives
7.1 Full Model List – CVS250F Series (250Una cornice)
| Modello | Trip Type | Corrente nominale | Adjustable Range | Official SKU |
| CVS250F-3P-160A | TM-D | 160UN | 112~160A | LV525331 |
| CVS250F-3P-200A | TM-D | 200UN | 140~200A | LV525332 |
| CVS250F-3P-250A | TM-D | 250UN | 175~250A | LV525333 |
| CVS250F-3P-150A | MA | 150UN | Fisso | LV525439 |
| CVS250F-3P-220A | MA | 220UN | Fisso | LV525439 |
| CVS250F-4P-250A | TM-D | 250UN | 175~250A | LV525334 |
7.2 Replacement & Upgrade Options
| Demand | Recommended Model | Caratteristiche |
| Standard Upgrade | CVS250N-3P-250A | Breaking capacity up to 50kA, for high short‑circuit risk |
| Electronic Trip | CVS250F-3P-250A ETS | Electronic trip unit with short‑time delay for critical loads |
| Earth Fault Protection | CVS250F-3P-250A Vigi | With Vigi residual current module (30mA~5A adjustable) |
| Domestic Alternative | CHINT NM1-250S/3300-250A | 36kA breaking, conveniente, similar performance |
| ABB Alternative | Tmax T2N250-3P-250A | International brand, close performance, global service |
CVS250F-3P-250A is a core product of Schneider EasyPact CVS series, integrating reliable protection, flexible installation and high cost‑performance. It is an ideal solution for industrial and commercial power distribution.
With 36kA breaking capacity, adjustable thermal‑magnetic trip and compact design, it adapts to a wide range of applications and safeguards both equipment and personnel.
Core Features of Schneider MCCB CVS250F-3P-250A
- Excellent Protection Performance
- Precise Thermal‑Magnetic Protection System
Adopts TM‑D adjustable thermal‑magnetic trip, long‑time protection range 175~250A (0.7~1.0In), suitable for various loads.
Fixed instantaneous short‑circuit trip at 2000A, fast fault interruption without delay, protects equipment from damage.
Conforme all'IEC 60947-2 Category A for distribution, effectively protects cables and equipment.
- Reliable Breaking Capacity
36kA@415V AC (Class F), Ics=100%Icu, ensures reliable fault interruption.
Up to 70kA at 220/240V AC, suitable for different voltage systems.
Double‑break arc extinguishing system improves current limitation and reduces thermal stress on the network.
- Comprehensive Safety Features
- Standard Isolation Function
Conforme all'IEC 60947-2 isolation requirements, can be used as a disconnecting device, improves operational safety.
Class II front panel, compatible with Class II switchboards without derating insulation.
- Operational Safety
Clear contact position indicator shows real‑time status.
Locking device available to secure in OFF position and prevent misuse.
| IP40 protection, adatto per ambienti industriali.
- Fault Indication
Optional SDE fault trip indicator for fast troubleshooting.
Excellent coordination with downstream devices for selective protection, avoids total outage.
- Installazione flessibile & Manutenzione facile
- Versatile Installation
Supports front / rear wiring for various panel layouts.
Compact dimensions 105×226×86mm, saves cabinet space.
Same mounting as ComPacT series, easy for system upgrade.
- Design modulare
Replaceable trip unit for easy maintenance and upgrade, reduces lifecycle cost.
Clip‑on accessories, plug‑and‑play, no special tools required.
3P/4P available for three‑phase and three‑phase four‑wire systems.
- Efficient Maintenance
Vita meccanica 20,000 operazioni, electrical life 10,000 operazioni (415V In).
Universal accessories across series, reduce inventory cost.
Adjustable long‑time current without replacing the breaker.
- High Reliability & Durabilità
- Robust Mechanical Structure
Double‑break mechanism ensures high fault current limitation and stable performance.
| Shock and vibration resistant for harsh industrial environments.
Rated impulse withstand voltage 8kV, complies with EN/IEC 60947-2.
- Strong Environmental Adaptability
Rated ambient temperature 40℃, operating range -5℃~+60℃.
Suitable up to 2000m altitude without derating.
Pollution Class 3 for industrial conditions.
- Stable Electrical Performance
Rated insulation voltage 690V, operational voltage 415V, global compatibility.
Terminals accept copper/aluminum conductors, suitable for 95mm²+ cables for 250A.
Stable long‑term operation, low contact resistance, bassa perdita di potenza.
- Eco‑Compliance & Cost Efficiency
- Green Design
Green Premium certified, Conforme alla direttiva RoHS, halogen‑free.
Low power consumption, supports energy saving.
- High Cost‑Performance
Balanced performance and cost, ideal for mass industrial and commercial use.
Low maintenance cost, alta affidabilità, lunga durata.
Universal accessories reduce total cost of ownership.
- Lifecycle Value
18‑month warranty.
Global service network for fast support.
Extensible with accessories (earth fault, contatti ausiliari, alarms).
- Key Application Adaptability
- Industrial Distribution: Main protection for pumps, tifosi, compressors with heavy‑duty starting.
- Edifici commerciali: Main and sub‑main distribution for offices, malls, hotels.
- Centri dati: Protection for UPS, PDUs, and critical power branches.
- Infrastructure: Hospitals, schools, public facilities requiring high safety and continuity.
As a core model of the Schneider EasyPact CVS series, CVS250F-3P-250A provides accurate protection, full safety, flexible installation, high reliability and excellent cost‑performance, making it the preferred choice for industrial and commercial power distribution systems.
Contattore,interruttore automatico,inverter solare,contatore elettrico,batterie solari




















NH42-63-318x560.png)