Serie: Modulo di comunicazione for LOGO! 8 / 8.2
Nome: CMK2000
Posizionamento: Connect LOGO! to KNX (EIB) building bus to realize logic linkage between building automation and LOGO!
Specifiche principali
Alimentazione elettrica: DC24V (19.2~28,8 V), rated current 0.04A, massimo. power consumption 1.1W
Interfacce:
1 × RJ45 Ethernet (100M) for web configuration, diagnosis and time synchronization
1 × KNX bus terminal (KNX/EIB, 9600 bit/i)
Communication objects: Fino a 50 KNX communication objects, KNX clock synchronization supported
Montaggio: Guida DIN, 4IL (71.5 larghezza mm)
Classe di protezione: IP20
Temperatura operativa: 0 ~ +55℃
Peso: ca. 0.13~0.14 kg
Origine: Germania, product status: Attivo
Controller compatibili
✅ LOGO! 8, LOGO! 8.2 (firmware version FS4 and above)
❌ Not compatible with older LOGO! 6 / 7
Scenari applicativi tipici
Edificio automazione, smart lighting, air conditioning fans, roller blind shading, energy consumption acquisition. LOGO! executes local logic, while CMK2000 acts as a gateway for two-way interaction with the KNX system. It can also be configured and commissioned directly via web pages, without writing all logic through dedicated KNX commissioning software.
Configuration Guidelines
- Add CMK2000 in LOGO!Soft Comfort and define KNX objects (read/write)
- Access the module IP via browser to set KNX parameters, group addresses and perform diagnostics on the web page
- The KNX side can read and write LOGO! internal variables, markers, timers and analog values
Sostituzione & Note sulla compatibilità
No direct hardware replacement model; CMK2000 (6BK1700-0BA20-0AA0) is the only option for KNX connection of LOGO! 8 serie
If KNX is not required and only Ethernet communication is needed, select LOGO! models with built-in Ethernet (PN variants marked 6ED1052)
Risoluzione dei problemi comuni
KNX bus communication failure: Check KNX polarity, bus power supply and bus wiring; wire cross-section 0.6~1.0 mm²
Web page inaccessible: Confirm the PC is in the same network segment as LOGO! and wait for module startup completion after power-on
Communication objects not refreshed: Verify LOGO! firmware version and mapping direction (input/output) of group addresses
6BK1700-0BA20-0AA0|LOGO! CMK2000 KNX Communication Module
Posizionamento: Dedicated KNX/EIB bus gateway for LOGO!8 / 8.2, enabling bidirectional data exchange between LOGO! logic controllers and the KNX building bus
- Parametri di alimentazione
Tensione nominale: CC 24 V
Permissible voltage range: DC 19.2V ~ 28.8V (SELV safety extra-low voltage)
Maximum current consumption: 0.04 UN
Maximum power consumption: 1.1 W
- Interfacce di comunicazione
- Ethernet Interface X1
Connettore: RJ45
Velocità: 100 Mbit/s, TCP/IP
Scopo: Web configuration, diagnosi, time synchronization, communication with LOGO! host
- KNX/EIB Bus Terminal X2
Velocità di trasmissione: 9600 bit/i
Sezione del filo consigliata: 0.6 ~ 1.0 mm²
Autobus: Standard KNX bus, KNX clock synchronization supported
Maximum communication objects: 50 KNX communication objects (bidirectional access to LOGO! digital inputs/outputs, markers, analog values and timers)
Built-in web server: Supports browser-based configuration and online diagnosis; S7 basic communication is not supported
- Compatible Host Units
Supportato: LOGO! 8, LOGO! 8.2 (firmware FS4 and above)
Non supportato: LOGO! 6, LOGO! 7
- Meccanico & Montaggio
Montaggio: 35 Guida DIN standard da mm
Dimensioni (L × A × P): 71.5 mm× 90 mm× 58.5 mm (4IL)
Peso netto: ca. 0.13~0.14 kg
Classe di protezione: IP20 (solo per installazione in armadio)
- Condizioni ambientali
Temperatura operativa (montaggio orizzontale): 0 ℃ ~ +55 ℃
Magazzinaggio / temperatura di trasporto: -40 ℃ ~ +70 ℃
Umidità relativa: 10% ~ 95 %, senza condensa
Atmospheric pressure: 795 hPa ~ 1080 hPa
- EMC & Certificazioni
Emission standards: IN 55011 Classe B (suitable for residential areas), IN 61000-6-3
Certificazioni: CE, UL, cULus, CSA, RoHS
Stato del prodotto: PLM PM300, Attivo, made in Germany
- Indicatori
CORRERE: Operation status
P.T: KNX programming mode
KNX: KNX bus communication status
- Full Model List of LOGO! CMK2000 (KNX Gateway)
CMK2000 has only one standard order number, no standard variants or SIPLUS extended temperature versions:
- 6BK1700-0BA20-0AA0 (only available active model, PLM PM300)
Nome: LOGO! CMK2000 KNX communication module
Alimentazione elettrica: DC24V; Interfacce: RJ45Ethernet + KNX bus
Communication objects: fino a 50; compatible with LOGO! 8 / 8.2 (firmware FS4 and above)
Nota importante:
The 6BK1700 prefix also covers another product line of SIPLUS HCS heating control modules (2BA suffix), not belonging to the LOGO! CMK2000 series, do not mix them up.
- All 6BK1700 Prefix Models (Two Product Lines Separated)
Linea di prodotti 1: LOGO! CMK2000 (KNX communication module, 1 model only)
6BK1700-0BA20-0AA0 (LOGO! CMK2000, KNX gateway)
Linea di prodotti 2: SIPLUS HCS724I Heating Control System (Non-LOGO!, 2BA suffix)
- 6BK1700-2BA00-0AA0
- 6BK1700-2BA20-0AA0 (interrotto)
- 6BK1700-2BA30-0AA0
- 6BK1700-2BA70-0AA0
- 6BK1700-2BA80-0AA0
- 6BK1700-4BA50-0AA0
- Other LOGO! Communication Modules for Reference
- CMK2000 (KNX): 6BK1700-0BA20-0AA0
- CMR2020 (GPRS): 6GK7142-7BX00-0AX0
- CMR2040 (LTE/4G): 6GK7142-7EX00-0AX0
- CSM12/24 (4-interruttore della porta): 6GK7177-1MA20-0AA0
- CIM (ModBus TCP/RTU + cloud): Not covered by 6BK1700, order number series 6BK1701
LOGO! CMK2000 KNX module: only one available model 6BK1700-0BA20-0AA0, no sub-variants
All 6BK1700-2BAxx / 4BAxx are HCS heating system modules and not LOGO! moduli di comunicazione.
Application Cases for 6BK1700-0BA20-0AA0 (CMK2000)
Principio fondamentale: LOGO!8/8.2 executes local logic, tempistica, threshold comparison and interlocking; CMK2000 works as a bidirectional gateway to connect KNX bus panels, actuators and sensors. Massimo. 50 KNX communication objects. ETS5/ETS6 is used for KNX side configuration, and LOGO!Soft Comfort for LOGO! programming and object mapping.
Caso 1: KNX Astronomical Timer + Central Lighting Control (Siemens official sample ID:109745699)
Scenario: Ufficio, corridor and public area lighting with automatic timing plus manual override via KNX panels
Hardware: LOGO!8 controllore + CMK2000 + KNX 3-gang push-button panel + KNX lighting actuator
Funzioni:
- LOGO! built-in astronomical timer (sunrise/sunset), weekly/yearly timer automatically sends ON/OFF commands to KNX actuators
- Button signals from KNX panels are uploaded to LOGO! for forced switching and scene selection; panel LEDs receive status feedback from LOGO!
- KNX bus provides time synchronization for LOGO!; time and status can be viewed on TDE text display and LOGO! built-in web page
Object allocation: ca. 8~12 KNX objects
Vantaggi: No KNX timers required. Leverage LOGO!’s flexible annual calendar and holiday disable logic for automatic lighting shutdown during holidays.
Caso 2: Zoned Control for Multi-Room Movable Partition (Official sample ID:109748585)
Scenario: Conference room, multi-function hall, automatic lighting and air conditioning zoning when movable partitions are opened or closed
Hardware: LOGO!8 + CMK2000 + KNX panels, KNX dimming actuators, KNX damper actuators, partition position switches (LOGO! local DI)
Funzioni:
- Partition position signals are sent to LOGO!; LOGO! judges whether the space is a single large hall or multiple independent rooms
- Zone status is synchronized to KNX bus; when a scene is triggered on the KNX panel, LOGO! enables lighting and air conditioning according to zoning logic
- Cross-zone interlock: When partitions are separated, the panel of zone A cannot control loads in zone B
Vantaggi: KNX only handles panels and actuators, while complex zoning interlocking logic runs in LOGO!, greatly simplifying ETS projects.
Caso 3: Illuminance Threshold Dimming Control (Official sample ID:109748587)
Scenario: Daylight harvesting dimming for offices and exhibition halls
Hardware: LOGO!8 + CMK2000 + KNX light sensor, KNX 0-10V dimming actuator
Funzioni:
- KNX illuminance value (0~255) is uploaded to LOGO! analog variable
- Threshold comparison and hysteresis filtering are implemented in LOGO! to avoid frequent flickering
- LOGO! sends dimming percentage to KNX dimmer; manual dimming via panel retains higher priority
Caratteristiche: LOGO! performs filtering, limit protection and delay; KNX only transfers measured values and control values.
Caso 4: HVAC Temperature / Umidità + CO₂ Ventilation Interlock (Fresh air for buildings or small server rooms)
Scenario: Small server rooms, laboratori, exhibition halls; interlock for fresh air fans, electric heating and dehumidification
Hardware: LOGO!8 + CMK2000 + KNX temperature/humidity/CO₂ sensors, KNX damper actuators, local contactor outputs on LOGO!
Funzioni:
- KNX sensors upload temperature, RH and CO₂ concentration to LOGO!
- LOGO! executes PID or threshold logic: increase fresh air when CO₂ exceeds limit, start heating at low temperature, activate dehumidification at high humidity
- Operation status, fault signals and setpoints are sent back to KNX for display on central panels or touch screens
Fitment: LOGO! has native analog processing, delay and alarm functions; CMK2000 bridges KNX sensors and LOGO! logica.
Caso 5: Cancello / Garage Door Safety Interlock (Official sample ID:109748589)
Scenario: Underground garage roller shutter doors, access control and safety light curtain interlock
Hardware: LOGO!8 + CMK2000 + KNX access control panel, local safety light curtain DI, door motor contactor
Funzioni:
- KNX access button sends opening authorization signal to LOGO!
- LOGO! performs safety interlock: door opening permitted only when the light curtain is clear and limit switches are normal; auto-close after timeout
- Door status, fault and lock status are fed back to KNX panel LED indicators
Valore: Safety interlock logic runs locally in LOGO!; protection remains valid even if the KNX bus is offline.
Caso 6: Peak Load Limiting (Gestione energetica, proven overseas solution)
Scenario: Shops, apartment heating circuits, charging pile group power limitation
Hardware: LOGO!8.3+ firmware + CMK2000 + KNX energy meter gateway, multiple heating / charging pile contactors
Funzioni:
- Real-time active power from KNX meter is uploaded to LOGO!
- LOGO! implements priority sequencing for 8 carichi; high-priority loads are retained and low-priority loads are shed when total power exceeds threshold
- Shedding status and current power are sent back to KNX supervision system
Critical requirement: Firmware ≥ FS4, otherwise KNX object binding fails.
Caso 7: Auxiliary Industrial Skid (Armadi di controllo HVAC, pompe dell'acqua, dust removal units integrated into building KNX)
Scenario: Factory auxiliary equipment, chiller units, exhaust fan cabinets; upload equipment status to the building KNX automation system
Hardware: LOGO!8 + CMK2000
Funzioni:
LOGO! collects pump run status, colpa, hand-auto mode, temperature and pressure via local DI/AI
Stato, alarms and setpoints are uploaded to KNX through CMK2000; start/stop and setpoints can be issued from KNX side
Vantaggi: LOGO! provides reliable local control for industrial equipment; expensive KNX IO modules are not required for interconnection between industrial control and building bus.
General Implementation Notes (Applicable to all cases)
- Maximum communication objects: 50, bidirezionale (KNX→LOGO / LOGO→KNX), mapped to LOGO! DI/DO, markers M, variables V and timers
- Workflow for commissioning:
LOGO!Morbido comfort: Write logic, add CMK2000, define KNX objects and direction
CMK2000 web page: Configurazione IP, KNX parameters, diagnostics and online monitoring
ETS5/ETS6: KNX device database, group address binding and download to KNX bus devices
- Bus accessories: Standard KNX bus power supply is mandatory; KNX cable J-Y(ST)Y 2×2×0.8, only red/black pair is used
- Limitazioni: S7 protocol is not supported, only KNX TP1; communication with LOGO! runs over Ethernet, not backplane bus.
Riferimento alla selezione
For simple direct load control by KNX panels: CMK2000 is not needed
Where complex timing, astronomical clock, incastro, filtraggio, local IO acquisition and offline protection are required: CMK2000 + LOGO! is a cost-effective solution.
Contattore,interruttore automatico,sensore,Codificatore,PLC,Convertitore