ABB ACS355 series general machinery drive, 0.37 kW / 0.5 HP, single-phase 200–240 V input, IP20保護, rated output current 2.4 あ. Suitable for speed control and energy-saving operation of small machinery.
1 Model Code Explanation
| Code Part | 意味 |
| ACS355 | ABB general machinery drive series |
| 01E | Protection class IP20, for installation in enclosed electrical cabinets |
| 02A4 | Rated output current 2.4 あ |
| 2 | Single-phase 200–240 V AC (±10%), 50/60 Hz input |
2 Key Technical Data
| アイテム | 価値 |
| Rated power | 0.37 kW (0.5 HP) |
| Rated output current | 2.4 あ (at 40°C) |
| Input voltage / frequency | Single-phase 200–240 V AC (±10%), 50/60 Hz |
| Output voltage / frequency | Three-phase 0–240 V AC, 0–500 Hz |
| 保護クラス | IP20 (indoor cabinet installation) |
| Control method | Scalar control (V/f), built-in application macros |
| Overload capability | 150% of rated current for 60 s; 180% のために 2 s |
| Cooling method | Natural cooling |
| 寸法 (幅×高さ×奥行き) | 169×70×135 mm |
| 重さ | 約. 1.2 kg |
| Order code | 3AUA0000058166 |
| EMC performance | Built-in EMC filter, compliant with EN 61800-3 |
3 主な特長
3.1 Flexible Control
Predefined application macros: constant torque, fan/pump, PID control, 等.
Local/remote control switching via keypad, terminals or fieldbus
Built-in PID controller for closed-loop flow, プレッシャー, 等.
3.2 Reliable Protection
過電流, 過負荷, 過電圧, 不足電圧, 過熱, phase loss protection
Motor over-temperature protection (requires external PTC)
Short-circuit and earth-fault protection
3.3 Easy Operation
Compatible control panel with ACS350/510/550 series
Parameter copy function for fast commissioning
MTBF > 100,000 hours for continuous operation
4 代表的な用途
Small conveyors, 包装機械
Fans, パンプス (small HVAC systems)
Mixers, centrifuges and small processing machines
Automatic doors, roller shutters
医療機器, 実験器具
Textile, printing and other light industrial machinery
5 インストール & Commissioning Guidelines
5.1 インストール要件
Must be installed in an enclosed electrical cabinet
周囲温度: 0–40°C (derate 10% at 40–50°C)
垂直に取り付ける, keep ≥ 100 mm clearance above and below for cooling
Avoid dust, 油, 腐食性ガス
Input protection: 10 A MCCB (C-curve) or fuse recommended
5.2 Basic Commissioning Steps
- Pre-power check: Verify wiring (L1/N input, U/V/W output), terminal torque, proper earthing
- パラメータの初期化
Group 99: set motor rated voltage, 現在, 力, スピード
Select application macro (標準, PID, 等)
- Control configuration
Local control: via control panel
リモコン: via DI terminals or optional Modbus RTU
- Operation test
無負荷試験: run at 5–10 Hz, check rotation and stability
負荷試験: gradually apply load, verify current and temperature
Adjust acceleration/deceleration time (1–10 s recommended)
6 Cross-Brand Replacement Options (0.37 kW, 1-段階 220 V, IP20)
| ブランド | モデル | 主要な一致点 |
| シュナイダー | ATV12HU04M2 | 0.37 kW, 1-段階 220 V, IP20, similar size |
| シーメンス | V20 6SL3210-5BB12-5UV1 | 0.37 kW, 1-段階 220 V, IP20, integrated EMC |
| チント | NVF2-0.37/2 | 0.37 kW, 1-段階 220 V, IP20, economical alternative |
| ABB alternative | ACS150-01E-02A4-2 | Same power range, more compact design |
7 Selection & Maintenance Tips
7.1 Recommended Options
Braking function: optional braking resistor (75 Ω / 50 W recommended)
コミュニケーション: add RS485 module
Enhanced EMC: additional input EMC filter
7.2 メンテナンス
Clean cooling channels every 6 月
Check terminal torque annually
Avoid frequent starts/stops (≤ 20 times per day)
Storage temperature: -25°C ~ +60°C, dry environment
ABB ACS355-01E-02A4-2
Installation and Commissioning Manual
Overview: This manual provides complete instructions for safety, installation, wiring, parameter setting and commissioning of the ACS355-01E-02A4-2 drive (0.37 kW / 0.5 HP, single-phase 200–240 V) for general machinery speed control and energy saving.
1 Safety Instructions (必読)
1.1 Electrical Safety
Power-off procedure: Disconnect all power before installation, wiring or maintenance. Wait 5 minutes for internal capacitors to discharge.
Earthing: PE terminal must be reliably earthed (earth resistance ≤ 4 Ω)
過電流保護: Install 10 A MCCB (C-curve) or fuse on input side
絶縁試験: Only test motor cables; do NOT apply voltage to the drive itself
1.2 Mechanical Safety
Rotating parts (shaft, coupling, pulley) must be guarded
Mount vertically on solid surface to avoid vibration
Do not modify internal circuits or structures
1.3 Environmental Safety
動作温度: 0–40°C (derate 10% at 40–50°C)
湿度: 5–95% RH, non-condensing
IP20: must be installed in enclosed cabinet
2 Product Overview and Model Identification
2.1 Model Explanation (ACS355-01E-02A4-2)
| コード | 意味 |
| ACS355 | ABB general machinery drive series |
| 01E | IP20, cabinet-mounted |
| 02A4 | Rated output current 2.4 あ (40℃) |
| 2 | Single-phase 200–240 V AC, 50/60 Hz |
2.2 Core Specifications
| アイテム | 価値 |
| Rated power | 0.37 kW (0.5 HP) |
| Input voltage | Single-phase 200–240 V AC (±10%) |
| Output voltage | Three-phase 0–240 V AC |
| Output frequency | 0–500 Hz |
| Overload capacity | 150% のために 60 s, 180% のために 2 s |
| Cooling | Natural cooling |
| 寸法 (幅×高さ×奥行き) | 169×70×135 mm |
| 重さ | 約. 1.2 kg |
| Order code | 3AUA0000058166 |
3 Installation Procedure
3.1 準備
- Unpack and inspect drive for damage
- Choose well-ventilated, dust-free location inside cabinet
- ツール: プラスドライバー (PH2), ワイヤーストリッパー, 圧着工具, multimeter, insulation tape
3.2 取り付け
- Mount vertically on flat metal plate
- Keep ≥ 100 mm above/below, ≥ 50 mm left/right clearance
- Fix with M4 screws, tightening torque: 1.2–1.5 N·m
4 Electrical Wiring
4.1 Terminal Description (ACS355-01E Series)
| Section | Terminal | 説明 | Wiring |
| Power Circuit | L1/N | Single-phase 200–240 V input | 1.5–2.5 mm² copper |
| PE | Protective earth | ≥ 2.5 mm² copper | |
| 紫外線/紫外線/紫外線 | 3-phase output to motor | 1.5–2.5 mm² copper | |
| 制御回路 | DI1–DI3 | Digital inputs | 0.5–1.5 mm², 最大 50 メートル |
| AI1/AI2 | Analog inputs (0–10 V / 0–20 mA) | Shielded twisted pair, 最大 100 メートル | |
| AO1 | Analog output (0–20 mA) | Shielded twisted pair, 最大 100 メートル | |
| +24V/GND | 24 V DC電源 (最大 100 ミリアンペア) | 0.5–1.5 mm² | |
| RS485+/– | Modbus RTU | Shielded twisted pair, 最大 1000 メートル |
4.2 Wiring Steps
- Power wiring: L1/N to mains, PE to earth, U/V/W to motor
- Control wiring (Standard macro example):
DI1: Forward (FWD), DI2: Reverse (REV), DI3: Reset
AI1: Speed reference (0–10 V)
- Check torque, 絶縁, and phase sequence
5 Parameter Settings
5.1 Keypad Functions
▶/■: 始める / 停止
▲/▼: Adjust value
入力: Confirm
ESC: Back
LOC/REM: 地元 / Remote
5.2 Quick Motor Settings (Group 99)
| パラメータ | 名前 | Setting | 注記 |
| 9901 | Language | 中国語 / English | User choice |
| 9902 | Application macro | 1 (標準) | General use |
| 9903 | Motor type | 1 (Asynchronous) | Standard induction motor |
| 9904 | Motor rated power | 0.37 kW | From nameplate |
| 9905 | Motor rated voltage | 220/230/240 V | From nameplate |
| 9906 | Motor rated current | Motor nominal | Typically ~2.1 A |
| 9907 | Motor rated frequency | 50/60 Hz | From nameplate |
| 9908 | Motor rated speed | Motor nominal | ~1400–1450 rpm |
| 9909 | Number of motor poles | 4 | Standard for 0.37 kW |
| 9910 | Control mode | 1 (V/f) | Scalar control |
5.3 Common Application Parameters
| Group | パラメータ | 名前 | 推奨値 |
| 10 | 1001 | Max frequency | 50/60 Hz |
| 1002 | Min frequency | 0 Hz | |
| 20 | 2001 | Acceleration time | 3–10 s |
| 2002 | Deceleration time | 3–10 s | |
| 21 | 2101 | Acc/dec type | 1 (Linear) |
| 40 | 4001 | DI1 function | 1 (FWD) |
| 4002 | DI2 function | 2 (REV) | |
| 4003 | DI3 function | 9 (リセット) | |
| 50 | 5001 | AI1 type | 1 (0–10 V) |
| 5002 | AI1 minimum | 0% | |
| 5003 | AI1 maximum | 100% | |
| 16 | 1607 | Save parameters | 1 |
6 Commissioning Flow
6.1 Pre-Power Check
Correct power and control wiring
Motor and drive area clear
Cabinet ventilation OK
Input voltage: 200–240 V single-phase
6.2 First Power-Up
Close MCCB, display shows REM or LOC
Check for fault codes
Verify Group 99 motor parameters
6.3 Motor Identification (オプション)
Set 9910 = 2 (ID Run)
Press ENTER; drive runs motor briefly
Completed when shown COMPLETE
6.4 No-Load Test
Switch to LOCAL
Run at 5 Hz, check rotation
Increase to rated frequency, check noise and vibration
6.5 負荷テスト
Switch to REMOTE
Control speed via AI1
Check output current ≤ 2.4 あ
Adjust acc/dec to avoid overcurrent
Test protection functions
7 トラブルシューティング
7.1 一般的な故障コード
| 故障 | 説明 | 原因 | Remedy |
| OVERCURRENT | 過電流 | Motor overload, 短絡 | 負荷を確認する, モーター, parameters |
| OVERVOLTAGE | 過電圧 | High mains, fast deceleration | 電圧を確認してください, increase dec time |
| UNDERVOLTAGE | 不足電圧 | Low supply, 接続が緩い | Check mains and wiring |
| OVERTEMP | Overheating | High temp, blocked cooling | 換気を改善する, clean heatsink |
| MOTOR OVERLOAD | Motor overload | Excessive load | Check application, 負荷を減らす |
| FAULT RESET | Trip reset required | Fault occurred | Fix cause, reset via DI3 or keypad |
7.2 Typical Issues
| 症状 | 原因 | 解決 |
| Motor does not start | Wrong LOC/REM, missing DI signal | Check mode, wiring and parameters |
| Unstable speed | AI noise, poor parameters | Use shielded cable, adjust filtering |
| 通信障害 | Wrong settings, bad wiring | Check Group 98, RS485, termination |
8 メンテナンス
8.1 定期的なメンテナンス
Clean cooling channels every 6 月
Check terminal torque annually
Log operating current and temperature
8.2 Long-Term Storage
温度: -25°C ~ +60°C
Dry, ventilated environment
Power on for 1 hour every 6 月
9 Appendix: Options and Replacements
9.1 Recommended Options
Braking resistor: 100 Ω / 50 W
EMC filter
RS485 Modbus RTU module
Shielded cable for control wiring
9.2 クロスブランドの代替品 (0.37 kW, 1-段階 220 V, IP20)
| ブランド | モデル | Matching Features |
| シュナイダー | ATV12HU04M2 | 0.37 kW, 1-段階 220 V, IP20 |
| シーメンス | V20 6SL3210-5BB12-5UV1 | 0.37 kW, 1-段階 220 V, IP20 |
| チント | NVF2-0.37/2 | 0.37 kW, 1-段階 220 V, IP20 |
| ABB | ACS150-01E-02A4-2 | Direct same-power replacement |