微信: +86-13184948252 ワッツアップ: 0086-13811255435 電子メール: kent@bestcontactor.com

について 接触 |

ABB VBC7-30-01220-240V DC ミニチュア可逆コンタクタ - コンタクタ,サーキットブレーカー,ソーラーインバーター,電気メーター,太陽電池

接触器/

ABB VBC7-30-01220-240V DC ミニチュア可逆コンタクタ

モデルセグメントDescription
ABBBrand Logo
VBC7Series Name: VBC7 Series Miniature Reversing Contactor (equipped with mechanical interlock, for motor forward and reverse rotation control)
30Main Contact Configuration: 3-pole Normally Open (3いいえ)
1Auxiliary Contact Configuration: 1 通常閉 (1ノースカロライナ州)
220-240ワシントンDCでCoil Control Voltage: DC 220-240V
*Special Version Identifier (may be a customized or market-specific version)

  • 製品詳細
  1. モデルの解釈
モデルセグメントDescription
ABBBrand Logo
VBC7Series Name: VBC7 Series Miniature Reversing Contactor (equipped with mechanical interlock, for motor forward and reverse rotation control)
30Main Contact Configuration: 3-pole Normally Open (3いいえ)
1Auxiliary Contact Configuration: 1 通常閉 (1ノースカロライナ州)
220-240ワシントンDCでCoil Control Voltage: DC 220-240V
*Special Version Identifier (may be a customized or market-specific version)

Full Model: VBC7-30-01-05 (スタンダードモデル, corresponding to 220-240V DC coil)

  1. コア技術パラメータ
  2. Basic Electrical Parameters
パラメータ項目価値備考
Rated Current of Main Contacts16あ (AC-3) / 20あ (AC-1)AC-3: Control of 5.5kW three-phase motor at 400V
定格動作電圧690VとComplies with IEC 60947-4-1 標準
Coil Control Voltage220-240ワシントンDCでWide voltage range, allowing 卤15% fluctuation
コイル消費電力Pick-up: 約. 5WDC coil operates with no noise or humming
保持: 約. 5W
Mechanical Service Life10 100万操作Under standard operating conditions
Electrical Service LifeAC-1: 1 100万操作Under rated load
AC-3: 100,000 operations
  1. Performance Indicators
パラメータ項目価値Applicable Conditions
Mechanical InterlockBuilt-in reliable mechanical interlockPrevents simultaneous closing of forward and reverse contactors
Overvoltage ProtectionBuilt-in surge suppression diodeProtects coil and control circuit
Switch Position IndicationVisual position markingFacilitates fault diagnosis and status confirmation
Insulation ClassClass FComplies with IEC standards
保護等級IP20Must be installed inside control cabinet
  1. Environmental and Installation Parameters
パラメータ項目価値Standard/Remarks
動作温度-25℃~+60℃Storage Temperature: -40℃~+85℃
取付方法35mm DIN rail mounting / screw mountingSpace-saving and easy to integrate
端子の種類ネジ端子Suitable for 22-10 AWG stranded wires
重さ約. 250gCompact design with light weight

Ⅲ. 機能的な特徴

  1. Dedicated for Reversing Control: Built-in mechanical interlock ensures that forward and reverse contactors cannot be closed simultaneously, ensuring safety and reliability.
  2. Quiet Operation: DC coil design eliminates the humming noise common in AC contactors, enabling silent operation.
  3. 幅広い電圧適応性: The coil supports a wide voltage range of 220-240V DC, adapting to different power supply conditions.
  4. Overvoltage Protection: Built-in surge suppression diode effectively protects the coil and control circuit from voltage spikes.
  5. Status Indication: Clear switch position indication facilitates on-site operation and fault diagnosis.
  6. Flexible Installation: Supports both DIN rail and screw mounting methods, adapting to various control cabinet layouts.
  7. High Reliability: With a mechanical service life of up to 10 million operations and long electrical service life, it is suitable for frequent operation scenarios.
  8. 適用範囲
  9. モーター制御: Forward and reverse rotation control of three-phase asynchronous motors, のような:

Small conveyors and hoists

Fans and pumps (requiring reversible operation)

Packaging machinery and printing machinery

  1. 産業オートメーション:

Control of auxiliary equipment in production lines

Output actuator for small PLC control systems

Equipment interlock control circuits

  1. Commercial and Building Applications:

Fan control in air conditioning systems

Elevator door motors and small lifting platforms

Automatic door and rolling shutter door control

  1. Other Applications:

Control of battery-powered equipment (compatible with DC coil)

Auxiliary circuits of solar inverters

Small load control in marine and rail transit systems

  1. 選択の提案
  2. ロードマッチング:

AC-3 loads (motor starting/operation): Max. 5.5kW (400V), rated current 16A

AC-1 loads (resistive loads): Max. 20あ, 690V

  1. Control Voltage Confirmation: Ensure the coil voltage matches the system DC power supply (220-240ワシントンDCで).
  2. Auxiliary Contact Requirements: Standard configuration is 1NC; for more contacts, select the VBC7-30-10 series (1いいえ) or expansion modules.
  3. 設置環境:

温度が40℃を超える場合はディレーティングが必要です (rated current decreases by 10% for every 10℃ rise)

Additional protective measures are needed in dusty and humid environments

  1. Accessory Selection:

It is recommended to match with a surge suppressor (built-in for DC coils)

Optional auxiliary contact modules and thermal overload relays (例えば, TA25DU series)

  1. 代替モデル:

Non-reversing version: BC7-30-01-05 (without mechanical interlock)

Different coil voltages: VBC7-30-01-01 (24ワシントンDCで), VBC7-30-01-07 (12ワシントンDCで)

  1. トラブルシューティング
故障現象考えられる原因トラブルシューティング方法
コンタクタが引き込まれない1. No voltage or low voltage at the coil1. Check the control circuit voltage (220-240ワシントンDCで)
2. コイル断線2. Measure the coil resistance (約. 10k惟 under normal conditions)
3. 機械的な妨害3. Inspect contacts and mechanical mechanism, and remove foreign objects
Contactor releases immediately after pulling in1. Excessive voltage fluctuation1. Stabilize the control voltage and check the power supply capacity
2. Poor coil contact2. Tighten the coil terminals
3. Overload protection activation3. Check the status of the thermal overload relay
Contact heating/welding1. Load current exceeds the rated value1. Replace with a contactor of larger capacity or use it with derating
2. Contact oxidation or contamination2. Clean or replace the contacts
3. Frequent overload operation3. Inspect the load and eliminate overload causes
インターロック故障1. Damage to the mechanical interlock mechanism1. Inspect the interlock mechanism and replace if necessary
2. Improper installation leading to interlock release2. Reinstall to ensure proper engagement of the interlock mechanism
Severe coil heating1. 過度の高電圧1. Adjust the control voltage to the rated range
2. Coil short circuit2. Measure the coil resistance and replace the damaged coil
3. 周囲温度が高い3. Improve heat dissipation conditions and reduce the ambient temperature

Ⅶ. Installation and Wiring Key Points

  1. 設置前, confirm that the coil voltage is 220-240V DC, matching the control power supply.
  2. For reversing control, ensure that the mechanical interlock of the two contactors (forward/reverse) is correctly installed to prevent phase-to-phase short circuit.
  3. Main circuit wiring: Connect L1, L2, L3 to the power supply, and T1, T2, T3 to the motor; pay attention to the phase sequence (when switching between forward and reverse rotation).
  4. Control circuit wiring: Connect coil terminals A1 and A2 to the 220-240V DC power supply; pay attention to polarity (some models have no polarity requirements).
  5. Auxiliary contact wiring: The 1NC contact can be used for interlock control or status indication; pay attention to the rated current of the contact (usually 5A).
  6. Installation spacing: Keep a distance of at least 5mm from other components to ensure good heat dissipation.
  7. Pre-power-on inspection:

Check if the mechanical interlock operates flexibly and reliably

Check if the contacts are in good contact

Check if the coil wiring is correct

ABB VBC7-30-01 Core Parameter and Price Comparison Table with Same Series and Competitor Models

  1. Comparison of ABB Same Series Models (Core Parameters)
パラメータ項目VBC7-30-01-05VBC7-30-10-05BC7-30-01-05違いの説明
(220-240ワシントンDCで)(220-240ワシントンDCで)(220-240ワシントンDCで)
タイプMiniature reversing contactorMiniature reversing contactorMiniature non-reversing contactorVBC7 with mechanical interlock; BC7 without interlock
主な連絡先3いいえ (3-ポールは通常オープンです)3いいえ (3-ポールは通常オープンです)3いいえ (3-ポールは通常オープンです)Identical
補助接点1ノースカロライナ州 (1 通常は閉まっている)1いいえ (1 通常は開いています)1ノースカロライナ州 (1 通常は閉まっている)Different auxiliary contact types
定格電流16あ (AC-3) / 20あ (AC-1)16あ (AC-3) / 20あ (AC-1)16あ (AC-3) / 20あ (AC-1)Identical, suitable for 5.5kW (400V) モーター
定格電圧690Vと690Vと690VとIdentical
コイル電圧220-240ワシントンDCで220-240ワシントンDCで220-240ワシントンDCでIdentical, DC operation with no noise
Mechanical InterlockBuilt-in reliable mechanical interlockBuilt-in reliable mechanical interlockなしExclusive to VBC7 series, preventing simultaneous closing of forward and reverse contactors
Surge ProtectionBuilt-in suppression diodeBuilt-in suppression diodeBuilt-in suppression diodeIdentical
取付方法DIN rail / screw mountingDIN rail / screw mountingDIN rail / screw mountingIdentical
Mechanical Service Life10 100万操作10 100万操作10 100万操作Identical
Electrical Service LifeAC-3: 100,000 operationsAC-3: 100,000 operationsAC-3: 100,000 operationsIdentical
AC-1: 1 100万操作AC-1: 1 100万操作AC-1: 1 100万操作
保護等級IP20IP20IP20Identical, must be installed inside control cabinet
Reference Price約. 380-450約. 380-450約. 320-380BC7 is slightly cheaper; VBC7-30-01 and 30-10 are similarly priced
  1. Comparison of ABB VBC7-30-01 with Competitor Models (Core Parameters + 価格)
パラメータ項目ABB VBC7-30-01-05Schneider LC1D18FDSiemens 3RT2016-1BB41+3RT2016-1BB41選択の提案
(220-240ワシントンDCで)(Reversing, 220ワシントンDCで)(Reversing Combination, 220ワシントンDCで)
Brand SeriesABB VBC7 SeriesSchneider LC1D SeriesSiemens 3RT2 Series
タイプIntegrated reversing contactorIntegrated reversing contactorDual-contactor combinationABB/Schneider integrated design saves more space
(with mechanical interlock)(with mechanical interlock)(external mechanical interlock required)
主な連絡先3いいえ (3-ポールは通常オープンです)3いいえ (3-ポールは通常オープンです)3NO+3NO (dual contactors)Identical
補助接点1ノースカロライナ州1NO+1NC1NO+1NC (per contactor)Schneider/Siemens have more abundant auxiliary contacts
定格電流16あ (AC-3) / 20あ (AC-1)18あ (AC-3) / 25あ (AC-1)9あ (AC-3) / 12あ (AC-1)Schneider has higher rated current, suitable for 7.5kW motor
適用モーター出力5.5kW (400V AC-3)7.5kW (400V AC-3)4kW (400V AC-3)Schneider supports higher power
コイル電圧220-240ワシントンDCで220ワシントンDCで220ワシントンDCでIdentical, DC operation with no noise
Mechanical InterlockBuilt-in, reliable and durableBuilt-in, long mechanical service lifeExternal required, increased costABB/Schneider are more convenient to use
Surge ProtectionBuilt-in suppression diodeBuilt-in varistorBuilt-in varistorIdentical protection function
取付方法DIN rail / screw mountingDIN rail / screw mountingDIN rail / screw mountingIdentical
Mechanical Service Life10 100万操作10 100万操作10 100万操作Identical
Electrical Service LifeAC-3: 100,000 operationsAC-3: 100,000 operationsAC-3: 100,000 operationsIdentical
AC-1: 1 100万操作AC-1: 1 100万操作AC-1: 1 100万操作
保護等級IP20IP20IP20Identical, must be installed inside control cabinet
Width Dimension45mm55mm45mm*2 (dual contactors)ABB has the smallest volume
Reference Price約. 380-450約. 420-480約. 450-520 (dual contactors)ABB offers the best cost performance
利点Integrated design, quiet operation, smallest volumeHigh rated current, abundant auxiliary contactsSiemens ecosystem compatibility, strong diagnostic functionsSelect according to load power and space constraints

Ⅲ. Price and Selection Replacement Summary

  1. Same Series Replacement Recommendations
Original ModelReplacement ModelReplacement Reason注意事項
VBC7-30-01-05VBC7-30-10-05Different auxiliary contact type (1NC→1NO)Confirm auxiliary contact requirements in the control circuit
VBC7-30-01-05BC7-30-01-05Lower price for non-reversing applicationsNot suitable for forward/reverse control, no mechanical interlock
VBC7-30-01-05VBC7-30-01-01Different coil voltage (220V DC→24V DC)Must match the system control power supply voltage
  1. Cross-Brand Replacement Recommendations
Original ModelOptimal ReplacementAlternative Replacement置き換えのメリット
VBC7-30-01-05Schneider LC1D18FDSiemens 3RT2016 CombinationHigher rated current and applicable power
VBC7-30-01-05ABB VBC7-30-10-05Schneider LC1D12FDBetter compatibility with the same brand, no need to adjust installation dimensions
  1. 選定のポイント
  2. ロードマッチング: Select the corresponding rated current for standard loads; for heavy-duty applications, it is recommended to choose one size larger (例えば, VBC7→Schneider LC1D25FD).
  3. 制御電圧: Ensure the coil voltage matches the system DC power supply (220-240ワシントンDCで).
  4. 補助接点: Select 1NC/1NO or versions with more contacts according to the control circuit requirements.
  5. Installation Space: Integrated reversing contactors (ABB VBC7/Schneider LC1D) save about 40% space compared to dual-contactor combinations.
  6. Cost Control: Same-brand replacement has the lowest cost; cross-brand replacement needs to consider installation adaptability and system compatibility.