Technical File of Chint CJX2-6511 + NR2-93

Chint CJX2-6511 + NR2-93 is a standard electromagnetic starter combination, consisting of a CJX2-6511 ACコンタクタ and an NR2-93 thermal overload relay. It is mainly used for remote control, overload and phase failure protection of AC motors, and is widely applied in industrial automation and electrical control systems.

  1. モデルの解釈
Componentモデル意味
コンタクタCJX2-6511CJX2: Series code (based on Schneider LC1-D technology)
65: Rated current of main contacts is 65A
11: 補助接点構成 (1 通常は開いています + 1 通常は閉まっている)
サーマルリレーNR2-93NR2: Series code
93: Frame size is 93A (adjustable current range: 23-93あ)
/Z: With manual/automatic reset selection (standard configuration)
  1. コア技術パラメータ
  2. CJX2-6511 AC Contactor
パラメータ項目Specification Value備考
Rated Operational Voltage690Vと50/60Hz
Rated Operational Current65あUnder AC-3 utilization category and 380V condition
定格絶縁電圧690V
定格インパルス耐電圧6kV
Control Coil Voltage24V/36V/110V/220V/380V ACオプション, 220V/380V are common choices
Main Contact Configuration3いいえ (3 通常開)For making and breaking the main circuit
Auxiliary Contact Configuration1いいえ + 1ノースカロライナ州For interlocking of control circuits
機械的寿命 10 100万操作
電気的寿命 1 100万操作Under AC-3 utilization category
取付方法Screw mounting / 35mm standard DIN railCompatible with DIN rail
周囲温度-5℃ ~ +40℃24-hour average temperature ≤ +35℃
  1. NR2-93 Thermal Overload Relay
パラメータ項目Specification Value備考
Rated Operational Voltage690Vと50/60Hz
フレームサイズ93あ
Adjustable Current Range23-32あ, 30-40あ, 37-50あMultiple specifications available, matched with 65A contactor
48-65あ, 55-70あ, 63-80あ
80-93あ
Trip Class10あOverload protection characteristic (tripping time is 2-10 seconds at 10 定格電流の倍)
保護機能過負荷保護 + phase failure protectionThree-phase bimetallic strip structure
Reset MethodManual/automatic selectableStandard configuration is /Z type
取付方法Plug-in mounting with CJX2 contactorCan be mounted independently
Ambient Temperature CompensationYesEnsures protection accuracy under different ambient temperatures

Ⅲ. 機能的な特徴

  1. Features of CJX2-6511 Contactor

High-performance Contacts: Silver alloy contacts with excellent conductivity, strong arc erosion resistance and long service life.

Low-noise Design: Optimized electromagnetic system to reduce noise during pull-in and release.

Modular Structure: Expandable auxiliary contacts for flexible installation.

Safe and Reliable: Complies with GB/T 14048.4 and IEC/EN 60947-4-1 standards, with short-circuit protection coordination capability.

幅広い電圧適応性: Control coil is compatible with multiple voltage levels to meet the requirements of different control circuits.

  1. Features of NR2-93 Thermal Overload Relay

Comprehensive Protection: Provides both overload and phase failure protection to prevent motor burnout due to phase loss operation.

Temperature Compensation: Maintains stable protection characteristics when ambient temperature changes.

Action Indication: Clear trip status indication for easy fault troubleshooting.

Flexible Reset: Manual/automatic reset selection to adapt to different control requirements.

Plug-in Mounting: Perfectly matched with CJX2 contactor for quick installation and space saving.

  1. Advantages of the Combined System

Integrated Control and Protection: The contactor is responsible for circuit on/off and motor starting, while the thermal overload relay provides overload/phase failure protection, forming a complete control and protection unit.

Standardized Design: Complies with international standards and can be seamlessly integrated with other electrical components.

Easy Maintenance: Modular structure allows easy component replacement and reduces maintenance costs.

  1. 適用範囲
  2. モーター制御: Suitable for frequent starting, stopping, forward and reverse rotation control of three-phase AC motors with power below 30kW (380V).
  3. Industrial Equipment: General machinery such as fans, ウォーターポンプ, コンプレッサー, conveyors and machine tools.
  4. Building Electrical Engineering: Central air conditioning systems, fire pumps and elevator control systems.
  5. Other Applications: Long-distance controlled power transmission and distribution systems, and electrical circuits requiring overload protection.
  6. 選択の推奨事項
  7. Basic Selection Principles

Contactor Selection: The rated current of main contacts shall be ≥ 1.2-1.5 times the rated current of the motor (inductive load).

Thermal Relay Selection: The adjustable current range shall cover the rated current of the motor (usually set to 0.95-1.05 times the rated current of the motor).

コイル電圧: Selected according to the power supply of the control circuit, 220V or 380V AC are commonly used.

  1. Motor Power Matching Table (380V)
モーター出力定格電流Recommended Thermal Relay Specificationアプリケーションシナリオ
18.5kW37あNR2-93/Z 37-50AGeneral load
22kW44あNR2-93/Z 37-50AGeneral load
30kW60あNR2-93/Z 48-65AHeavy load, frequent starting
37kW74あNR2-93/Z 63-80ADerating required (65A contactor is close to the limit)
  1. 設置および使用上の注意事項

Mounting Direction: The contactor and thermal overload relay can be installed horizontally or vertically, with an inclination angle not exceeding 5°.

配線仕様: The terminals of the main circuit shall be tightened to avoid heating; the cross-sectional area of the control circuit wire shall be ≥ 1.5mm².

環境要件: Avoid installation in humid, dusty or corrosive gas environments; altitude ≤ 2000m.

保護調整: Must be used with circuit breakers to provide short-circuit protection.

  1. トラブルシューティング
故障現象考えられる原因ソリューション
コンタクタが引き込まれない1. Low coil voltage/phase loss1. Check the power supply voltage to ensure it is within 10% of the rated value
2. Burned-out coil2. Measure the coil resistance and replace the coil if abnormal
3. 機械的な妨害3. Check the iron core and mechanism to remove foreign objects
4. Open circuit in control circuit4. Check the wiring of the control circuit and repair the open circuit
Loud noise after contactor pulls in1. Oil stain/dust on iron core end face1. Clean the iron core end face
2. Broken short-circuit ring2. Replace the iron core or contactor
3. Voltage fluctuation3. Stabilize the power supply voltage
接点の過熱/アブレーション1. 配線の緩み1. Tighten the wiring terminals
2. Severe contact wear2. Replace the contacts or contactor
3. Overload3. Check the load and replace with a contactor of larger capacity if necessary
4. High operating frequency4. Reduce the operating frequency or select a contactor suitable for AC-4 utilization category
Frequent tripping of thermal overload relay1. Excessively small adjustable current1. Adjust the adjustable current to the rated current of the motor
2. Motor overload2. Check the motor load and eliminate faults
3. Phase loss operation3. Check the wiring of the main circuit and repair the phase loss
4. 周囲温度が高い4. Improve ventilation conditions and reduce the ambient temperature
Thermal overload relay fails to trip1. Excessively large adjustable current1. Adjust the adjustable current
2. Damaged heating element2. Replace the thermal overload relay
3. Jammed trip mechanism3. Check and repair the trip mechanism

Ⅶ. Substitution and Compatibility

ComponentChint ModelCompatible/Alternative Model備考
コンタクタCJX2-6511Schneider LC1-D6511Compatible in mounting dimensions and electrical parameters
Delixi CDM1-6511
ABB A16-30-11
サーマルリレーNR2-93Schneider LRD3363Similar protection characteristics; attention shall be paid to matching of mounting methods
Delixi JR28-93
ABB TA25DU

VIII. まとめ

Chint CJX2-6511 + NR2-93 is a cost-effective and highly reliable motor control and protection solution, especially suitable for frequent starting and protection applications of small and medium-sized motors. Its modular design, standardized interface and comprehensive protection functions make it an ideal choice in the field of industrial automation. 選択中, it is necessary to choose the appropriate adjustable current specification of the thermal overload relay and the coil voltage of the contactor according to the motor power, rated current and control requirements.

Service Life Details of Chint CJX2-6511 + NR2-93

The service life of the Chint CJX2-6511 + NR2-93 combination shall be comprehensively evaluated from three dimensions: mechanical life (no-load operation times), electrical life (on-load operation times) and actual service life, which is also affected by various factors such as operating conditions and maintenance level.

  1. Officially Nominal Life Parameters
  2. CJX2-6511 AC Contactor
Life TypeStandard ValueTest Condition
機械的寿命 10 100万操作Operation under no-load and rated coil voltage
電気的寿命 600,000 operations (AC-3利用カテゴリー)Controlling three-phase asynchronous motor under 380V and rated operating current of 65A
電気的寿命 100,000 operations (AC-4 utilization category)Frequent starting/reversing/braking conditions with larger current
  1. NR2-93 Thermal Overload Relay
Life TypeStandard ValueTest Condition
機械的寿命 1 100万操作Operation under no-load and rated control voltage
電気的寿命 100,000 operationsOperation of control circuit under rated working conditions
Heating Element LifeLong-term stable (について 10 年)Normal use without frequent overload tripping
  1. Key Factors Affecting Service Life
  2. Factors Affecting Contactor Life
  1. 要素Influence MechanismInfluence Degree
    動作周波数Frequent operation accelerates mechanical wear and contact ablation高い (if the frequency is doubled, the life may be halved)
    負荷の種類The life of AC-4 load (frequent starting/reversing) is 60-80% lower than that of AC-3 load高い
    Voltage FluctuationOvervoltage causes coil overheating, and undervoltage causes contact bouncingMedium-High
    環境条件温度 > 40, humidity, dust and corrosive gas accelerate aging中くらい
    取付方法Non-vertical installation (inclination > 5°) affects heat dissipation and mechanical action低い
    Maintenance LevelRegular cleaning and terminal tightening can extend the service life中くらい

    Factors Affecting Thermal Overload Relay Life

要素Influence MechanismInfluence Degree
Overload FrequencyFrequent overload tripping causes fatigue of bimetallic strips高い
Adjustable CurrentExcessively small adjustable current leads to unnecessary tripping中くらい
周囲温度High temperature affects protection accuracy and component life中くらい
制御回路電圧Overvoltage causes ablation of control contacts低い

Ⅲ. Life Estimation in Practical Application

  1. Calculation of Actual Contactor Life (例)

Assumed working conditions: AC-3利用カテゴリー, 100 operations per day, 300 working days per year

Theoretical electrical life: 600,000 operations

Annual operation times: 100 operations/day × 300 days = 30,000 operations/year

Expected service life: 600,000 ÷ 30,000 = 20 年 (ideal working conditions)

If it is AC-4 utilization category with 200 operations per day:

Theoretical electrical life: 100,000 operations

Annual operation times: 200 × 300 = 60,000 operations/year

Expected service life: 100,000 ÷ 60,000 = about 1.7 年 (severe working conditions)

  1. Estimation of Actual Thermal Overload Relay Life

Control Contact Life: With 50 operations per day, the theoretical 100,000 operations can last for about 5.5 年.

Heating Element Life: Under normal use (less than 5 overload trips per month), it can work stably for 8-10 年.

Overall Life: Usually determined by the life of the contactor; the thermal overload relay can be replaced as a wearing part.

  1. Practical Suggestions for Extending Service Life
  2. Selection Optimization

The rated current of the contactor shall be ≥ 1.2-1.5 times the rated current of the motor.

For frequent starting/reversing conditions, select AC-4 dedicated contactors or use them with derating.

  1. Installation and Usage Specifications

Install vertically with good ventilation; control the ambient temperature within -5℃ ~ +40℃.

Keep the control coil voltage stable within ±10% of the rated value.

Set the adjustable current of the thermal overload relay to 0.95-1.05 times the rated current of the motor.

  1. Maintenance Measures

Regularly clean the contacts and iron core to remove dust and oil stains.

Check the wiring terminals to prevent loosening and heating.

After 3-5 years of operation of the contactor, the contacts and coil can be replaced.

When the thermal overload relay trips frequently, check the motor load and main circuit.

  1. まとめ

Under standard working conditions (AC-3, 100 operations per day), the electrical life of the contactor in the Chint CJX2-6511 + NR2-93 combination is about 20 年, and the mechanical life far exceeds the actual service demand; the overall life of the thermal overload relay is about 10 年. The actual service life mainly depends on the operating frequency, load type and maintenance level, and may be shortened to 1-2 years under severe working conditions. Through reasonable selection, standardized use and regular maintenance, the service life of the equipment can be effectively extended and the replacement cost can be reduced.