Chint NM1-800H/3300-800A is a 3-pole, 800あ ノーヒューズサーキットブレーカー (MCCB) of the NM1 series, featuring H-grade breaking capacity and thermomagnetic tripping. It is designed for overload and short-circuit protection of power distribution lines, and suitable for industrial and large commercial power distribution trunk lines.
| Code | Meaning |
| NM1 | Chint NM1 series molded case circuit breaker |
| 800 | Frame current 800A |
| H | High breaking capacity grade (Grade H, typically 50kA at 400V AC) |
| 3300 | 3 極, combined tripper (thermomagnetic tripping), no accessories |
| 800あ | Rated current 800A |
Core Parameters
| パラメータ | Value |
| Rated operating voltage | AC 690V, 50Hz |
| Rated insulation voltage | 800V |
| 定格電流 | 800あ |
| 遮断容量 | Grade H: 50の (400Vと) |
| Pole number | 3P |
| Tripper type | Thermomagnetic (overload long-time delay + short-circuit instantaneous protection) |
| Mounting method | Fixed type, vertical/horizontal mounting available |
| Wiring method | Front wiring (rear wiring and plug-in type optional) |
| Operation method | Direct handle operation |
| Executive standard | GB 14048.2, IEC 60947-2, CCC certification |
アプリケーションシナリオ
Overload and short-circuit protection for industrial power distribution trunks and power circuits in large workshops.
Protection for power distribution main trunks in commercial buildings (shopping malls, office buildings).
Protection for large motor circuits with infrequent starting.
Installation and Operation Key Points
- Installation shall comply with specifications; both vertical and horizontal mounting are acceptable, with secure fastening and good heat dissipation ensured.
- Check the specification of wiring terminals before wiring to match cables/bus bars for 800A current.
- Regularly inspect the action accuracy of the tripper to avoid the impact of ambient temperature on protection performance.
Cross-brand Replacement Reference
シュナイダー: NSX 800N/3P 800A (Verify breaking capacity and tripping curve).
ABB: Tmax T6N 800/3P 800A (Pay attention to mounting dimensions and accessory compatibility).
The core difference between Chint NM1-800H/3300-800A and NM1-800H/3200-800A lies in the tripper type and protection function; other basic parameters (frame current, breaking capacity, pole number, 等) are completely consistent.
- Core Difference: Meaning of “3300” そして “3200” in the Model
| Model Part | Digital Meaning | Protection Function |
| 3300 | 1st digit 3 = 3 極; 2nd digit 3 = combined tripper (thermomagnetic tripping); last two digits 00 = no accessories | Overload long-time delay protection + short-circuit instantaneous protection |
| 3200 | 1st digit 3 = 3 極; 2nd digit 2 = magnetic tripper (magnetic tripping only); last two digits 00 = no accessories | Short-circuit instantaneous protection only, no overload protection |
This is the fundamental difference between the two circuit breakers, which directly determines their application scenarios and protection capabilities.
- Complete Parameter Comparison Table
| パラメータ | NM1-800H/3300-800A | NM1-800H/3200-800A | Remarks |
| Tripper type | Thermomagnetic combined tripping | Magnetic tripping | Core difference |
| Overload protection | Available (long-time delay) | Unavailable | の 3300 model achieves overload delay protection through the thermal bending of bimetallic strips |
| Short-circuit protection | Available (instantaneous) | Available (instantaneous) | Both realize short-circuit instantaneous tripping through electromagnetic coils |
| Frame current | 800あ | 800あ | Consistent |
| 定格電流 | 800あ | 800あ | Consistent |
| 遮断容量 | Grade H (50kA@400V AC) | Grade H (50kA@400V AC) | Consistent |
| Pole number | 3P | 3P | Consistent |
| 定格電圧 | AC 690V, 50Hz | AC 690V, 50Hz | Consistent |
| Rated insulation voltage | 800V | 800V | Consistent |
| Mounting method | Fixed type (vertical/horizontal) | Fixed type (vertical/horizontal) | Consistent |
| Wiring method | Front wiring (rear wiring, plug-in type optional) | Front wiring (rear wiring, plug-in type optional) | Consistent |
| Executive standard | GB 14048.2, IEC 60947-2 | GB 14048.2, IEC 60947-2 | Consistent |
Ⅲ. Application Scenario Differences
| モデル | 該当するシナリオ | Inapplicable Scenarios |
| 3300 | • Industrial/commercial power distribution trunks (requiring both overload and short-circuit protection) | • Special occasions requiring only short-circuit protection |
| • Large motor circuits (infrequent starting) | • Dedicated circuits for fire-fighting equipment (3300 model with shunt trip is usually required for fire-fighting equipment) | |
| • General lighting and power hybrid distribution systems | ||
| 3200 | • Used as an isolating switch (needing short-circuit protection but no overload protection) | • Used alone as power distribution line protection (lack of overload protection will cause line overheating and damage) |
| • Occasions matched with other overload protection devices (例えば, thermal overload relays) | • Direct protection for motors (unable to prevent motor burnout due to overload) | |
| • Special short-circuit protection for specific industrial equipment |
- Selection Suggestions
- Prioritize the 3300 model: Most power distribution scenarios require both overload and short-circuit protection; の 3300 model provides more comprehensive protection to avoid line overheating, equipment damage and other problems caused by overload.
- Select the 3200 model only under specific conditions: When the system is already equipped with other overload protection devices (例えば, thermal overload relays, overload alarms), の 3200 model can be used as a dedicated short-circuit protection circuit breaker to reduce costs.
- 注記: の 3200 model cannot be used alone for power distribution lines requiring overload protection due to the lack of overload protection, otherwise potential safety hazards may be caused.