NV = Earth Leakage Circuit Breaker (ELCB); 250 = 250AF frame size; SV = Standard breaking capacity (Sクラス); 3P = 3-pole; In=250A; AC-type electronic residual current circuit breaker
✅ Core Technical Parameters
フレームサイズ: 250の, rated current 250A
極: 3P (3-ポール, 3-相3線式)
定格使用電圧Ue: AC100~440V (compatible with AC380/400/415V)
Insulation voltage Ui: 440V; impulse withstand voltage Uimp: 6kV
遮断容量 (AC400V): Icu=Ics=36kA
Earth leakage sensitivity: 3 adjustable levels: 100/200/500ミリアンペア (select Instantaneous / Time-delayed type when ordering)
トリップユニット: 熱磁気トリップ (過負荷 + 短絡保護) + electronic residual current protection
規格: IEC60947-2, GB/T14048.2, CE認証済み
寸法: W105mm × H165mm × D92mm; standard front wiring
頻度: 50/60Hz
📌 Model Code Breakdown
NV: Earth Leakage Circuit Breaker (ELCB); NF = non-leakage standard MCCB
250: 250フレームサイズ
SV: S-class Standard breaking capacity; other variants: 履歴書 (economic low breaking), HV (高い遮断容量, 50の)
3P: 3-ポール; 4P version available
サフィックス: J = Instantaneous trip; D = Time-delayed trip (for selective protection against upstream tripping)
🧩 Optional Accessories (Interchangeable within the series)
Auxiliary switch (斧), Alarm switch (アル), シャントトリップ (SHT), 不足電圧トリップ (UVT), 拡張回転ハンドル, Rear terminal blocks, Terminal safety covers
📋 Model Selection & 交換オプション
- Upgraded model within the same series: NV250-SEV (new WS-V generation, electronic adjustable overload trip, CCC認証済み, mainstream stock model for domestic projects)
- High breaking capacity same-frame variant: NV250-HV (Icu=50kA @ AC400V)
- 注記: NV250-SV is an older imported model; NV250-SEV is the domestic mainstream stock model. Direct replacement requires verification of leakage current range, mounting dimensions and accessory interfaces.
- 国内代替リファレンス: Chint NM1LE-250S, Delixi CDM1LE-250 (similar breaking capacity and leakage logic, but cabinet cutout and accessories are not interchangeable)
⚠️ Application & トラブルシューティングのヒント
アプリケーションシナリオ: Main incoming feeders in 3-phase power cabinets, ファン, water pumps and production lines, with integrated overload, short-circuit and earth fault protection.
3P version only detects 3-phase leakage; single-phase 220V loads with neutral wire are not allowed. Select 4P if single-phase loads exist.
Common fault: Immediate tripping after closing. First distinguish between earth leakage trip (leakage indicator pops out) and overload/short-circuit trip. Adjust leakage setting to 500mA to avoid tripping caused by normal equipment residual current.
Maintenance test: Press the built-in leakage test button regularly to verify the residual current function.
📎 Complete Ordering Example
NV250-SV 3P 250A 100/200/500mA J (瞬間式)
比較表: NV250-SV / NV250-SEV / NV250-HV (250AF frame, 3P 250A, AC-type ELCB)
All belong to WS-V series; 取付寸法, cabinet cutouts and accessory interfaces are fully interchangeable for direct in-situ replacement.
Core differences: トリップユニット, breaking capacity and market positioning.
| アイテム | NV250‑SV | NV250‑SEV | NV250‑HV |
| 位置決め | Older standard breaking model, 熱磁気トリップ | New domestic mainstream model, standard breaking, electronic adjustable overload trip | High breaking model, 熱磁気トリップ |
| Icu/Ics @ AC400V | 36の / 36の | 36の / 36の | 50の / 50の |
Full Model List of 三菱 WS-V Series MCCB
- NF (Standard MCCB without earth leakage) & NV (ELCB with earth leakage) — Small & 中型フレーム (32~250AF)
(1) 32AFフレーム
NF (MCCB): NF32-SV (only S-class available)
NV (ELCB): NV32-SV
(2) 63AFフレーム
NF: NF63-CV (経済的な), NF63-SV (標準), NF63-HV (ハイブレイク)
NV: NV63-CV, NV63-SV, NV63-HV
(3) 125AFフレーム (Most widely used)
- Thermal-magnetic fixed trip: NF125-CV, NF125-SV, NF125-HV
- Electronic adjustable trip: NF125-SEV, NF125-HEV
- Current-limiting type: NF125-UV, NF125-RV
NV Earth Leakage Breakers: NV125-CV, NV125-SV, NV125-HV, NV125-SEV, NV125-HEV
(4) 250AFフレーム (Your current model frame)
NF Standard MCCB (No leakage protection)
熱磁気: NF250-CV, NF250-SV, NF250-HV
Electronic adjustable: NF250-SEV, NF250-HEV
電流制限: NF250-RV, NF250-UV
NV Earth Leakage Circuit Breakers (ELCB, including NV250-SV)
NV250-CV (経済版)
NV250-SV (standard general model, your selected type)
NV250-HV (高い遮断容量, 50の)
NV250-SEV (electronic adjustable overload)
NV250-HEV (電子旅行 + 高い遮断容量)
Leakage current settings: 100/200/500mA 3-level adjustable; J=Instantaneous, D=Time-delayed.
- Large Current Frames (400~4000AF, Traditional WS Series)
- 400の: NF400-CW / SW / HW; NV400-CW / SW / HW
- 630の: NF630-CW / SW / HW; NV630-CW / SW / HW
- 800~4000AF: NF800~NF4000, NV800~NV4000 (only thermal-magnetic trip; suffix = CW/SW/HW, no SV suffix)
Ⅲ. Universal Accessory Cross Reference (32/63/125/250の)
| フレームサイズ | Auxiliary Switch AX | Alarm Switch AL | Shunt Trip SHT | Undervoltage Trip UVT | Locking Cover |
| 32の | 斧-05SV | アル-05SV | SHT-05SV | UVT-05SV | LC-05SV |
| 63の | 斧-05SV | アル-05SV | SHT-05SV | UVT-05SV | LC-05SV |
| 125の | AX-1SV | AL-1SV | SHT-1SV | UVT-1SV | LC-1SV |
| 250の | 斧-05SV | アル-05SV | SHT-05SV | UVT-05SV | LC-2SV |
結論: All accessories for NV250-SV are fully compatible with NF250-CV/SV/HV/SEV/HEV and can be retrofitted on site without factory modification.
- UL Export Models (サフィックス U)
NF125-SVU / HVU; NF250-CVU / SVU / HVU
NV125-SVU / HVU; NV250-CVU / SVU / HVU
- Full Ordering Format
- 標準タイプ: NV250-SV 3P 250A J 100/200/500mA (Instantaneous trip)
- Selective protection type: NV250-SV 3P 250A D (Time-delayed leakage trip)
- Full set with accessories: NV250-SV 3P 250A + AX+AL+SHT(AC220V)+UVT(AC380V)
- Old-to-New Model Replacement (WS → WS-V Series)
Old model NF250-SGW → New model NF250-SV
Old model NV250-SW → New model NV250-SV
寸法, cutouts and accessories are 1:1 interchangeable with no cabinet modification required
コンタクタ,サーキットブレーカー,センサー,エンコーダ,PLC,コンバータ