PHNIX PC4001 PHNIX PC4001 is a main controller / control board designed for equipment including air-to-water heat pumps, central air conditioners, industrial water chillers, and printing machines. It is a dedicated embedded main control board proprietary to PHNIX, commonly used in commercial heat pumps and industrial refrigeration units. Basic Information Brand: PHNIX Model: PC4001 Type: ...

  • 製品詳細

PHNIX PC4001

PHNIX PC4001 is a main controller / control board designed for equipment including air-to-water heat pumps, central air conditioners, industrial water chillers, and printing machines. It is a dedicated embedded main control board proprietary to PHNIX, commonly used in commercial heat pumps and industrial refrigeration units.

  1. 基本情報

ブランド: PHNIX

モデル: PC4001

タイプ: Main controller (control board) for heat pump / refrigeration units

Applicable Equipment:

PHNIX commercial air-to-water heat pumps (hot water / heating / ultra-low temperature Polaris series)

Industrial water chillers / refrigeration units

Printing machines, central air conditioners, pool heat pumps

Nature: Dedicated main control board with pre-programmed firmware, not a general-purpose PLC.

  1. Main Functions (Heat Pump / Refrigeration Control)
  2. Multi-mode Control

Heating / Cooling / Hot Water / Constant Temperature Dehumidification

  1. Temperature Control

Closed-loop control of supply and return water temperature

Monitoring of ambient temperature, discharge temperature, and coil temperature

  1. 保護機能

High pressure, low pressure, 過負荷, 位相損失, phase sequence, anti-freeze, high discharge temperature

Sensor fault, flow switch, and compressor protection

  1. Compressor Management

Sequencing, time delay, and balanced start/stop for 1-3 コンプレッサー

  1. External Device Control

Four-way valve, electronic expansion valve, ファン, water pump, electric heater

  1. コミュニケーション & Display

Supports wired controller (モデル 95005 シリーズ)

Some versions support Modbus-RTU

  1. Typical Hardware Specifications

Power Supply: AC 220V ±15% / 380V

Inputs:

NTC 10KΩ temperature sensors (multiple)

High pressure switch, low pressure switch, flow switch, phase sequence protector

Outputs (リレー / Thyristor):

1-3 compressor outputs

Four-way valve, ファン, water pump, electric heater, アラーム

Display: Onboard LED run/fault indicators

Controller Interface: Dedicated 4/5-pin connector (for Model 95005, 等)

寸法: Standard PCB board (約. 150×120mm)

取り付け: Screw-mounted inside the unit cabinet

  1. Common Replacement / Compatible Models

PC4001: Basic universal version

430084: Common PHNIX heat pump mainboard (same-platform replacement)

20000-430084: Extended part number for ordering

PC4002 / PC4003: Upgraded versions (more compressors / enhanced protection)

  1. 一般的な故障コード

E1: High pressure protection

E2: Low pressure protection

E3: Supply water temperature sensor fault

E4: Return water temperature sensor fault

E5: 過負荷 / 過電流

E6: Phase sequence error / 位相損失

E7: Anti-freeze protection

E8: Excessively high discharge temperature

  1. Difference from Carlo Gavazzi PC4001

Carlo Gavazzi PC4001: Phase sequence / phase loss protection relay (electrical protection)

PHNIX PC4001: Main control board for complete heat pump system (system control)

The two are completely different and not interchangeable.

  1. Ordering & メンテナンス

Original Ordering: Through PHNIX distributors (mostly using extended part number: 20000-430084)

メンテナンス: Requires original factory firmware; board replacement is generally the only solution.

PHNIX PC4001 Mainboard: Complete Installation & Commissioning Manual

The PC4001 is a dedicated main control board for PHNIX commercial heat pumps / water chillers (not a general-purpose relay). Below is the factory-level full procedure for installation, wiring, power-on, パラメータ設定, and troubleshooting (applicable to ultra-low temperature heat pumps, 給湯器, chillers, and printing machine units).

  1. インストール前の準備

1.1 Model Confirmation & 互換性

Mainboard: PC4001 / 20000-430084 (extended part number)

応用: PHNIX 3-25HP commercial heat pumps / water chillers (single / dual compressor)

Wired controller: Matching Model 95005 wired controller (4/5-core cable)

Power Supply: Three-phase AC 380V / Single-phase AC 220V (depending on unit)

1.2 ツール & Accessories

プラスドライバー, ワイヤーストリッパー, multimeter, 電圧テスター

Crimp terminals, ケーブルタイ, 絶縁テープ

NTC 10KΩ temperature sensors (supply water / return water / discharge / ambient / コイル)

Phase sequence protector (PC4001 has built-in phase loss / phase sequence protection)

1.3 安全上の注意事項

Install with power disconnected: Turn off main power and attach lockout tag

Anti-static: Touch grounded metal to discharge static; do not operate with wet hands

Separate strong and weak current: Route power / compressor cables separately from signal wires

  1. Mechanical Installation (Mainboard Mounting)
  2. Mounting Location: Inside the unit’s electrical cabinet, away from compressors, ファン, and high-temperature areas
  3. Fixation: Secure the PCB with 4 M3 screws (do not overtighten to avoid cracking the PCB)
  4. Orientation: Mount vertically for heat dissipation; keep away from water accumulation / condensation
  5. クリアランス: Leave ≥3cm ventilation space around the board
  6. Standard Wiring (PC4001 Terminal Definitions)

3.1 Power Input (三相380V)

L1, L2, L3: Three-phase power input (correct phase sequence)

N: Neutral wire

PE: Protective earth (must be connected for shock and interference protection)

3.2 Compressor Outputs (1-2 単位)

COMP1: Compressor 1 (live wire)

COMP2: Compressor 2 (live wire)

COM: Common neutral

OVL: 過負荷保護 (series-connected normally closed thermal relay)

3.3 External Device Control

FV: Four-way valve (heating / cooling switching)

FAN: Condensing fan

PUMP: Water pump / flow switch

EH: Electric heater (オプション)

ALARM: Fault alarm output (dry contact)

3.4 Temperature Sensors (NTC 10KΩ)

T1: Supply water temperature (必須)

T2: Return water temperature (必須)

T3: Discharge temperature (必須)

T4: 周囲温度

T5: Coil temperature

3.5 Protection Switches (Normally Closed Inputs)

HP: High pressure switch (必須)

LP: Low pressure switch (必須)

FLOW: Flow switch (必須)

PH: Phase sequence / 位相損失 (built-in, can be connected externally in series)

3.6 Wired Controller Interface

CN5 / CN6: 4-core cable (VCC, GND, DATA, CLK)

Cable length: ≤15 meters, shielded cable, kept away from high-voltage lines

3.7 Wiring Guidelines

All terminals use crimp terminals + tinning to prevent loosening

Route strong and weak current in separate ducts; shield of signal cables grounded at one end

Compressor wires ≥2.5mm², signal wires 0.75mm²

Secure wiring with cable ties to avoid abrasion by fans or compressors

  1. Pre-power Inspection (Critical)
  2. Multimeter Checks:

L1-L2-L3: Balanced three-phase voltage (380V±5%)

Insulation: Compressor / fan insulation to ground ≥ 2MΩ

  1. Phase Sequence Check:

Use phase sequence meter to confirm L1-L2-L3 is positive phase sequence

Incorrect phase sequence triggers E6 on PC4001

  1. Sensor Check:

All NTC sensors measure approx. 10KΩ at room temperature

No short circuit or open circuit in sensor cables

  1. Protection Switches:

High pressure / low pressure / flow switches are normally closed and conducting

No bypassed protections (do NOT short HP / LP / FLOW)

  1. Power-on Commissioning (Wired Controller Operation)

5.1 First Power-on

Turn on main power → Mainboard LED lights up, wired controller shows boot screen

Self-test: 30 秒, checking sensors, inputs/outputs, and protections

5.2 Unit Parameter Setting (Required)

To enter parameters: Long press [SET] on wired controller for 5 seconds → Password [6666]

P00: Unit type selection

0: Heat pump water heater

1: Heat & cool heat pump

2: Industrial water chiller

P01: Number of compressors (1/2)

P02: Rated supply water temperature (hot water 55℃ / chiller 7℃)

P03: Temperature differential (2-3℃)

P04: Anti-freeze temperature (5℃)

P05: High discharge temperature protection (110-120℃)

P06: Fan control (0: constant run / 1: thermostatic control)

P07: Water pump control (0: unit interlock / 1: constant run)

5.3 較正 & Testing

  1. Temperature Calibration:

Compare multimeter readings with controller display → Calibrate in P20-P24

  1. Manual Test (Service Mode):

Long press [MODE + わかりました] のために 5 seconds → Manual output mode

Test sequentially: COMP1, COMP2, FV, FAN, PUMP, ALARM

Verify normal pull-in, no short circuit, no abnormal odor

5.4 Phase Sequence & Protection Test

Disconnect any phase → Immediate E6 (位相損失)

Reverse phase sequence → E6 (phase sequence error)

Open high pressure switch → E1 (high pressure)

Disconnect supply water sensor → E3 (sensor fault)

  1. Operational Commissioning
  2. Mode Selection: Hot Water / Cooling / Heating
  3. Temperature Setting:

Hot water: 50-55℃

Chilled water: 7-12℃

Heating: 45-55℃

  1. Monitoring:

Compressor starts after 3-minute delay (prevents frequent cycling)

Discharge temperature 60-90℃ (≤110℃)

Pressure levels:

Cooling: High pressure 12-18bar, low pressure 3-5bar

Heating: High pressure 18-25bar, low pressure 1.5-3bar

  1. Protection Operation:

Over-temperature / over-pressure → immediate shutdown with corresponding fault code

Fault lockout: Reset by power cycle or controller [Reset]

  1. 一般的な故障コード & ソリューション

E1: High pressure protection → Check dirty condenser, ファン, high pressure switch

E2: Low pressure protection → Check insufficient refrigerant, 漏れ, low pressure switch

E3: Supply water sensor fault → Check T1 wiring, damaged sensor

E4: Return water sensor fault → Check T2

E5: 過負荷 / overcurrent → Check compressor, thermal relay, 電圧

E6: Phase sequence / phase loss → Correct phase sequence, check three-phase input

E7: Anti-freeze protection → Check water temperature, pump, anti-freeze settings

E8: High discharge temperature → Check refrigerant, heat dissipation, discharge sensor

  1. Key Difference from Carlo Gavazzi PC4001

PHNIX PC4001: Complete heat pump main control board (コントロール + 保護)

Carlo Gavazzi PC4001: Phase sequence relay (only phase loss / phase sequence protection)

Not interchangeable

  1. Delivery List

PC4001 mainboard

マニュアル / parameter sheet

Wired controller (95005)

Sensors (T1/T2/T3)

Terminal kit

PHNIX PC4001 Complete Parameter Setting Manual (Using 95005 Controller)

The PC4001 is matched with the Model 95005 wired controller; all parameters are set via the controller.

Core steps: Long press SET 5s → Password 6666 → Select P parameter → Modify → Save

  1. Entering Parameter Settings (Essential Steps)

1.1 Enter Menu

Controller on normal standby screen

Long press [SET] key for 5 秒

Display shows P00, enter password: 6666

Press [わかりました] to enter parameter list

1.2 Button Functions

[SET]: Confirm, enter, up / +

[C/F]: Down / -, switch

[MODE]: Exit, back

[わかりました]: Save, lock

 

1.3 Parameter Editing Flow

  1. Press [SET / C/F] to select parameter (P00-P30)
  2. Press [SET + C/F] together → value flashes
  3. Press [SET / C/F] to adjust value
  4. Press [SET + C/F] together again → save (stops flashing)
  5. Long press [MODE] のために 3 seconds → exit menu
  6. Core Basic Parameters (P00-P09, Required)

P00 Unit Type (Most Important)

0: Heat pump water heater (default)

1: Heat & cool heat pump

2: Industrial water chiller

P01 Number of Compressors

1: 1 compressor

2: 2 コンプレッサー

P02 Rated Set Temperature

Hot water: 50-55℃

Heating: 45-55℃

Chilled water: 7-12℃

P03 Temperature Differential (On/Off Offset)

推奨: 2-3℃

例: Set 55℃, stop at 57℃, start at 54℃

P04 Anti-freeze Temperature

Default: 5℃

Water temp <5℃ → auto start pump / low-temp heating

P05 High Discharge Temperature Protection

Default: 110℃

推奨: 105-115℃ (immediate shutdown if exceeded)

P06 Fan Control Mode

0: Constant run (always on in cooling / heating)

1: Thermostatic control (stops at set temp, restarts low)

P07 Pump Control Mode

0: Unit interlock (pump runs when compressor runs)

1: Constant run (runs continuously when powered)

P08 Compressor Time Delay Protection

Default: 3 分

Range: 0-5 分 (prevents frequent starting)

P09 Current Protection (過負荷)

Set to compressor rated current × 1.1-1.2

Overcurrent → E5 overload protection

  1. Temperature Calibration Parameters (P20-P24)

P20 Supply Water Temp (T1) 較正

Actual temperatureDisplayed temperature = Calibration value

例: Actual 50℃, display 52℃ → set -2

P21 Return Water Temp (T2) 較正

P22 Discharge Temp (T3) 較正

P23 Ambient Temp (T4) 較正

P24 Coil Temp (T5) 較正

Range: -10~+10℃

Must save and exit after calibration

  1. 保護 & Advanced Parameters (P25-P30)

P25 High Pressure Protection Value

Cooling: 20-22 バー

Heating: 25-28 バー

P26 Low Pressure Protection Value

Cooling: 1.5-2 バー

Heating: 1.0-1.5 バー

P27 Defrost Temperature / Time

Defrost start: -3~-5℃

Max defrost duration: 10 分

P28 Electric Heating Enable Temperature

例: ≤40℃ allows electric heater activation

P29 Modbus Address (オプション)

Default: 1

Set to 1, 2, 3… for multi-unit networking

P30 Restore Factory Defaults

0: Do not restore

1: Restore defaults (use with caution)

  1. Manual Test Mode (For Service)

Enter Manual Test

Normal screen → Long press [MODE + わかりました] のために 5 秒

Display shows TEST

Manual Output Test

Press [SET / C/F] to select output:

  1. COMP1: Compressor 1
  2. COMP2: Compressor 2
  3. FV: Four-way valve
  4. FAN: ファン
  5. PUMP: Water pump
  6. ALARM: アラーム

Press [わかりました] to switch on/off

Long press [MODE] to exit test

  1. 一般的な障害 & Parameter Adjustments

E1 High Pressure: Increase P25 by 1-2 bar or clean condenser

E2 Low Pressure: Decrease P26 by 0.5 bar or recharge refrigerant

E3/E4 Sensor Fault: Calibrate P20/P21 or replace NTC 10K

E6 Phase Sequence: Swap any two of L1/L2/L3

Frequent Cycling: Increase P03 differential to 3-5℃

E8 High Discharge Temp: Set P05 to 110℃ or check cooling

  1. Quick Parameter Setting Table (Direct Input)
ParamWater HeaterHeat & CoolChiller
P00012
P011-21-21-2
P0253℃50℃7℃
P033℃3℃2℃
P045℃5℃4℃
P05110℃110℃105℃
P06101
P07001
P083min3min3min
  1. 注意事項

Parameters must be saved after editing (value stops flashing)

Do NOT short protection terminals (HP/LP/FLOW)

Use precision multimeter for temperature calibration

Lock parameters after commissioning: Change password to 8888 to prevent accidental changes

前へ:

次:

返信を残す

伝言を残す