微信: +86-13184948252 ワッツアップ: 0086-13811255435 電子メール: kent@bestcontactor.com

について 接触 |

Schneider LC1D245M5C Contactor - コンタクタ,サーキットブレーカー,ソーラーインバーター,電気メーター,太陽電池

接触器/

Schneider LC1D245M5C Contactor

Model SegmentMeaning
LC1Schneider Standard AC Contactor Series
DTeSys D Platform (Domestic High-current Series)
245Rated Operating Current 245A (at AC-3 400V)
MCoil Voltage Code, representing AC 220V
5Coil Frequency Code, representing 50Hz (Code 7 indicates universal compatibility with 50/60Hz)
CDomestic Version Identifier

  • 製品詳細

Model Interpretation

Model SegmentMeaning
LC1Schneider Standard AC Contactor Series
DTeSys D Platform (Domestic High-current Series)
245Rated Operating Current 245A (at AC-3 400V)
MCoil Voltage Code, representing AC 220V
5Coil Frequency Code, representing 50Hz (Code 7 indicates universal compatibility with 50/60Hz)
CDomestic Version Identifier
  1. Core Technical Parameters ⚙️
  2. Basic Specifications

極数: 3P (3-pole, 3NO normally open)

Utilization Category: AC-1 (resistive load), AC-3 (direct-on-line starting of squirrel-cage motors)

Rated Operating Voltage: Up to 660V AC

Rated Insulation Voltage: 1000V AC

Rated Impulse Withstand Voltage: 8kV

Rated Operating Current (Ie): 245あ (AC-3, 400V, cosφ=0.85)

  1. Coil Parameters

Coil Voltage: 220V AC 50Hz

Coil Power Consumption: Approximately 140VA for pull-in, 25VA for holding

Control Circuit Voltage Range: 85%-110% of rated voltage (for reliable pull-in)

Release Voltage: ≤75% of rated voltage

  1. Electrical and Mechanical Service Life

Mechanical Service Life: Up to 20 million operations

Electrical Service Life: Approximately 1 million operations at AC-3 400V, 2 million operations at AC-1

Rated Short-time Withstand Current (Icw): 210あ (1s), 105あ (10s), 30あ (10min)

  1. Installation and Dimensions

Mounting Method: Standard 35mm DIN rail mounting or screw fixing

Mounting Depth: Approximately 150mm

Width: Approximately 108mm (245A specification)

重さ: Approximately 4.5kg

Ⅲ. Performance Features

  1. High-efficiency Arc Extinguishing: Dual-break electric arc extinguishing + longitudinal slot arc extinguishing design ensures reliable breaking
  2. Modular Design: Flexible installation of auxiliary contact modules (LADN series), pneumatic time-delay heads, mechanical interlocks and other accessories
  3. Reliable Connection: Adopts EverLink™ patented terminal technology to prevent conductor creep-induced loosening
  4. Wide Temperature Adaptability: Operating temperature range from -25℃ to +55℃, storage temperature range from -40℃ to +70℃
  5. Complete Certifications: CCC, CE, UL, CSA and other international certifications
  6. アプリケーションシナリオ
  7. Motor Control: Direct starting and operation control of squirrel-cage motors with rated power of 110kW (AC-3 400V)
  8. Power System: Making and breaking circuits with AC 50Hz/60Hz and rated voltage up to 660V
  9. Industrial Equipment: Used for controlling heavy-duty loads such as fans, water pumps and compressors
  10. Combination with Thermal Overload Relays: Can be combined with thermal overload relays (例えば, LRD series) to form magnetic starters for overload protection
  11. Selection and Replacement

代替モデル: LC1D245M7C (50/60Hz universal coil), LC1D245Q5C (380V coil)

Matching Accessories:

Auxiliary Contacts: LADN04 (4いいえ), LADN22 (2NO+2NC), 等.

Thermal Overload Relays: LRD3363C (230-320あ), LRD3359C (170-230あ)

Mechanical Interlocks: LADS2 (for reversible contactors)

  1. Installation and Maintenance Points
  2. Inspect product integrity before installation and verify that the model and parameters meet design requirements
  3. Use copper lugs for main circuit terminals during wiring to ensure firm connection
  4. Install fuses or circuit breakers for control circuit protection (6A recommended)
  5. Regularly inspect contact ablation; replace the main contacts when wear exceeds 1mm
  6. Keep the contactor clean to prevent dust and oil contamination from affecting its operating performance

Ⅶ. まとめ

Schneider LC1D245M5C is a 245A 3-pole AC contactor in the TeSys D series, suitable for 220V 50Hz control circuits. It is mainly used for controlling three-phase squirrel-cage motors below 110kW or other heavy-duty loads. Its long mechanical and electrical service life, modular design and reliable performance make it an ideal choice in the field of industrial automation.