シュナイダー LC1E1801 コンタクタ

型式コード説明: LC1E = TeSys E series contactor; 18 = rated 18A at 400V under AC-3 duty; 01 = built-in 1 常閉接点 (1ノースカロライナ州) ⚠️ The LC1E series has been discontinued (production stopped in July 2020). The standard replacement model is LC1N1801, fully compatible in mounting, terminal layout and performance. Key Specifications Main ...

  • 製品詳細

型式コード説明: LC1E = TeSys E series 接触器; 18 = rated 18A at 400V under AC-3 duty; 01 = built-in 1 常閉接点 (1ノースカロライナ州)

⚠️ The LC1E series has been discontinued (production stopped in July 2020). The standard replacement model is LC1N1801, fully compatible in mounting, terminal layout and performance.

主な仕様

主な連絡先: 3P, 3いいえ

AC-3 (motor duty): 18A @ 400V; AC-1 (抵抗負荷): 25あ

モーター定格: 7.5kW @ 380/400V; 4kW @ 220V; 9kW @ 440V

絶縁電圧Ui: 690V; インパルス耐電圧 Uimp: 6kV

補助接点: 1ノースカロライナ州 (通常閉)

取り付け: DINレール / base plate screw mounting

全体の寸法: W45mm × H74mm × D80mm, net weight ≈0.3kg

保護クラス: IP20; 動作温度: -5~+55℃; No derating up to 3000m altitude

機械的寿命: 10 100万操作; AC-3 electrical life: 1.2 100万操作; 最大動作周波数: 1800 サイクル/時間

Coil suffix definitions (complete model number)

LC1E1801B5: AC24V, 50Hz

LC1E1801F5: AC110V, 50Hz

LC1E1801M5: AC220V, 50Hz (most common in China)

LC1E1801Q5: AC380V, 50Hz

サフィックス 7 = 50/60Hz universal; サフィックス 6 = 60Hz only

コイル消費電力 (M5 220V example)

Inrush VA: 95バージニア州; Sealed holding VA: 8.5バージニア州; Coil heat dissipation: 2~3W

ピックアップ電圧: 0.85~1.1Uc; ドロップアウト電圧: 0.3~0.6Uc

締付トルク & wire gauge

Torque for main circuit and control circuit terminals: 1.2 N・m

単線: 1.5~6mm²; より線 (with ferrule): 1~4mm²

Matching selection reference

適合するサーマル過負荷リレー: LRD07 / LRN07 (current range suitable for 18A)

付属品: LA1EN auxiliary contact block, LA9D coil surge suppressor, mechanical interlock block

国内代替品: CJX2-1801 (similar outline, pay attention to mounting hole and marking differences)

トラブルシューティングガイド

  1. Coil energized but no pull-in: Check if coil voltage is within 0.85~1.1Uc; inspect broken coil wire and loose terminals
  2. Pulled in but main circuit no continuity: メイン接点の侵食, 接触溶接, 配線が緩んでいる
  3. Buzzing / チャタリング: 不足電圧, large harmonic distortion, dust accumulated on core faces
  4. Failed to drop out after power-off: Welded main contacts, core stuck by oil and dirt

Detailed Installation Procedure for シュナイダー LC1E1801 Contactor

⚠️ Safety precondition: Operated by qualified electricians; cut off all power supply and verify zero voltage before installation. LC1E1801: 3P main contacts with built-in 1NC auxiliary contact. 端子マーキング: Main circuit L1/L2/L3 (line side, incoming), T1/T2/T3 (負荷側, outgoing); Coil A1, A2; 補助接点: 95, 96 (1ノースカロライナ州)

  1. インストール前の準備
  2. コイル電圧を確認する: LC1E1801M5=AC220V, Q5=AC380V, F5=AC110V. Coil rated voltage must match control circuit voltage to avoid coil burnout.
  3. 目視検査: No shell cracks, intact terminals, armature moves freely without jamming when pressed manually.
  4. ツール: 2 プラスドライバー, ワイヤーストリッパー, マルチメータ, トルクレンチ; 35mm standard DIN rail or mounting base plate.
  5. Wire specification

Main circuit solid wire: 1.5~6mm²; フェルール付撚線: 1~4mm²

制御回路 (A1/A2, 補助接点): 0.75~1.5mm²

締付トルク: 1.2 N・m (avoid over-tightening to prevent thread stripping, or loose connection causing overheating)

  1. Environmental check: Cabinet temperature -5℃~+55℃, keep away from dust, 水分と油分. Mount vertically upright. Do NOT install upside down or horizontally.
  2. 固定する (2 methods: DINレール / base plate screw mounting)

方法 1: 35mm DINレール取付 (好ましい)

  1. The contactor has upper hooks and a spring locking clip at the bottom.
  2. Hook the upper notch onto the top edge of the DIN rail first.
  3. Press the bottom of the contactor down until you hear a click, the bottom clip locks onto the rail.
  4. Shake lightly to confirm firm fixation. 除去: Use a flat screwdriver to pry down the bottom clip and pull out the contactor.

方法 2: Screw mounting on insulated base plate (no rail)

  1. Mark and drill holes on the insulated plate according to the rear mounting holes (for M4 screws).
  2. Insert screws diagonally, pre-tighten, then torque evenly in diagonal sequence; do not force one side to avoid casing deformation.
  3. Accessory Fitting (オプション: LA1EN auxiliary block, mechanical interlock etc.)
  4. Top auxiliary contact block: Align with the slots on top of contactor, push vertically down until latched.
  5. Thermal relay LRD/LRN: Clip directly underneath the contactor, align positioning slots; the linkage will engage automatically.
  6. Surge suppressor LA9D: Clip beside coil terminals A1/A2, absorbs back EMF to protect PLC output points.
  7. 配線順序 (Main circuit → Auxiliary contacts → Coil control circuit)

Standard routing: Line side on top, load side on bottom. L1/L2/L3 on top for three-phase supply; T1/T2/T3 at bottom for load (モーター).

  1. 主回路配線

Strip insulation 5~6mm, avoid loose copper strands; ferrules are mandatory for stranded wire.

Keep phase sequence L1→T1, L2→T2, L3→T3 as per drawing.

Torque screws to 1.2N·m; only one conductor per terminal.

  1. Built-in auxiliary contact (95-96, ノースカロライナ州)

端子 95-96: Conductive when coil de-energized, open when contactor pulls in. Usually used in stop circuit or fault feedback for motor control.

If NO contact is required, add LA1EN auxiliary block.

  1. Coil A1, A2 (制御回路)

A1 and A2 have no polarity for AC. For AC220V: one to live, one to neutral; for AC380V: connect to two different phases.

Wire in series with start/stop pushbuttons, thermal relay NC contact or PLC outputs.

Route control wires separately from power cables to reduce interference.

Terminal summary:

L1/L2/L3 (Supply In), T1/T2/T3 (Load Out), A1 A2 (コイル), 95-96 (Built-in 1NC)

  1. 電源投入前検査
  2. 目視チェック: All terminals tightened, no exposed copper, no short circuit risk, no loose strands touching adjacent terminals.
  3. Continuity test with multimeter:

De-energized state: No continuity between L-T; 95-96 auxiliary contact is conductive.

Manually press armature to simulate pull-in: L-T becomes conductive, 95-96 開く.

  1. Double-check coil voltage; separate power supply for main circuit and control circuit.
  2. 電源投入時のコミッショニング
  3. Energize control circuit only, keep main power off: Press start button, contactor should pull-in smoothly without chattering or buzzing; release stop button for reliable drop-out.

チャタリング: 供給電圧が低い, loose wiring or dirty core surfaces.

  1. After control circuit test passes, energize main circuit and run on load.
  2. Temperature check after 10min running: No obvious overheating at terminals (temperature rise indicates poor connection).
  3. インストールに関する注意事項 & 禁止事項
  4. Keep minimum clearance ≥10mm between contactor and fuse / MCB for heat dissipation.
  5. Minimum spacing ≥5mm between multiple contactors; increase spacing for high ambient temperature.
  6. Do not plug or remove auxiliary blocks when energized.
  7. Do not trap wire insulation inside terminal clamps; copper must be fully clamped.
  8. LC1E discontinued, spare replacement: LC1N1801, same mounting size and terminal definition.
  9. Common Installation Faults

No pull-in after energized: Wrong A1/A2 voltage, broken control wire or open button circuit

Buzzing when pulled in: 不足電圧, dust or rust on magnetic core faces

Cannot drop out after power cut: Welded main contacts or core jammed by oil

Schneider Easy TeSys E (LC1E / EasyPact TVS) Series Full List

重要な注意事項: LC1E series fully discontinued in July 2020. 直接交換: LC1N series, identical mounting dimensions and terminal layout.

Model rule: LC1E + current code + auxiliary contact code (10=1いいえ; 01= 1NC) + coil suffix

Coil suffix description:

B5=AC24V 50Hz; F5=AC110V 50Hz; M5=AC220V 50Hz; Q5=AC380V 50Hz

B7/F7/M7/Q7=50/60Hz universal; BD=DC24V; 6=60Hz only

  1. 3P LC1E Contactors (AC-3 @400V)
ベースモデルAC-3電流Motor Rating @400VBuilt-in Auxiliary Contact
LC1E06106あ2.2kW1いいえ
LC1E06016あ2.2kW1ノースカロライナ州
LC1E09109あ4kW1いいえ
LC1E09019あ4kW1ノースカロライナ州
LC1E121012あ5.5kW1いいえ
LC1E120112あ5.5kW1ノースカロライナ州
LC1E181018あ7.5kW1いいえ
LC1E180118あ7.5kW1ノースカロライナ州 (your referenced model)
LC1E251025あ11kW1いいえ
LC1E250125あ11kW1ノースカロライナ州
LC1E321032あ15kW1いいえ
LC1E320132あ15kW1ノースカロライナ州
LC1E381038あ18.5kW1いいえ
LC1E380138あ18.5kW1ノースカロライナ州
LC1E401140あ18.5kW1NO+1NC
LC1E501150あ22kW1NO+1NC
LC1E651165あ30kW1NO+1NC
LC1E801180あ37kW1NO+1NC
LC1E951195あ45kW1NO+1NC
LC1E120120あ55kW内蔵なし, add auxiliary block separately
LC1E160160あ75kW内蔵なし, add auxiliary block separately
LC1E200200あ90kW内蔵なし, add auxiliary block separately
LC1E300300あ160kW内蔵なし, add auxiliary block separately

完成モデルの例: LC1E1801M7 = 18A, 1ノースカロライナ州, AC220V 50/60Hz universal

  1. Matching LRE Thermal Overload Relays (plug-on fit for LC1E)

LRE01N~LRE35N (for 06~38A); LRE322N~LRE365N (for 40~300A)

LRE01N: 0.1~0.16A

LRE02N: 0.16~0.25A

LRE03N: 0.25~0.4A

LRE04N: 0.4~0.63A

LRE05N: 0.63~1A

LRE06N: 1~1.6A

LRE07N: 1.6~2.5A

LRE08N: 2.5~4A

LRE09N: 4~6A

LRE10N: 6~10A

LRE12N: 10~16A

LRE14N: 16~24A

LRE16N: 24~36A

LRE21N: 28~36A

LRE22N: 36~48A

LRE322N: 55~70A

LRE323N: 63~80A

LRE353N: 80~104A

LRE355N: 104~135A

LRE365N: 130~165A

  1. E-series Accessories
  2. LA1EN: Top-mounted auxiliary contact block (1いいえ / 1ノースカロライナ州, stackable)
  3. LAEM1: メカニカルインターロックモジュール (for two contactor interlocking)
  4. LA9D: コイルサージキラー (RCネットワーク / バリスタ, PLC output protection)
  5. LAEB1N / LAEB3N: Thermal relay independent base (when not mounted under contactor)
  6. LA1EBN: Timed auxiliary contact block (オンディレイ / オフディレー)
  7. 2P / 4P LC1E (single phase, 点灯 & 抵抗負荷, AC-1デューティ)

LC1E0920: 2Q9A

LC1E2520: 2P25A

LC1E0940: 4Q9A

LC1E2540: 4P25A

LC1E4040: 4P 40A

4P versions commonly used for HVAC, lighting and heating resistive loads

  1. Cross Reference Table
Old LC1E ModelDirect Replacement LC1N
LC1E0601/0610LC1N0601 / LC1N0610
LC1E0901/0910LC1N0901 / LC1N0910
LC1E1201/1210LC1N1201 / LC1N1210
LC1E1801/1810LC1N1801 / LC1N1810
LC1E2501/2510LC1N2501 / LC1N2510
LC1E3201/3210LC1N3201 / LC1N3210
LC1E3801/3810LC1N3801 / LC1N3810
LC1E40~95LC1N40~95