状態: Discontinued by original manufacturer, Class 10E, S6 frame, electronic motor protection relay
基本仕様
注文番号: 3RB2056-1FC2
電流設定範囲: 50 … 200 あ
フレームサイズ: S6 (compatible with S6 contactors such as 3RT1056)
旅行クラス: Class 10E (修理済み, 調整不可)
Matched motor power at 400V 50Hz: 30~90kW
主回路接続: バスバー接続
補助回路: ネジ端子, auxiliary contacts 1NO + 1ノースカロライナ州
リセットモード: マニュアル / automatic reset selectable
取り付け: Direct snap-on to S6 contactor or standalone mounting
保護クラス: IP20
定格絶縁電圧: 1000Vと, インパルス耐電圧8kV
周波数範囲: 50/60Hz
動作温度: -25℃~+60℃
保護機能
電子式, different from bimetallic thermal relays:
Inverse-time overload protection
位相損失 / 位相不平衡保護
Motor stall protection
Built-in test button for loop testing
モデルの区別 (Easily Confused Models in the Same Series)
3RB2056-1FC2: Class10E, 製造中止
3RB2056-2FC2 / 2FX2: Class20E, heavy-duty start version, 最も一般的な代替品
Replacement Selection Suggestions
- 同じ仕様で直接交換可能: 3RB2056-2FC2 (Class20E); if Class10 is strictly required, prioritize the new generation 3RB3056 series electronic 過負荷リレー
- Matching contactor: シーメンス 3RT1056 (S6)
- 国内代替品: Domestic electronic thermal relay with 50-200A, S6 footprint, 1NO+1NC, Class10
重要なメモ
3RB2056-1FC2 is an older imported 3RB2 model, discontinued by Siemens. Stock units are only available from inventory. New projects are generally recommended to adopt the new 3RB30 series.
3RB2056-1FC2 (S6 / 50-200あ / Class10E) 配線 & 試運転マニュアル
備考: Electronic type requiring auxiliary power supply A1/A2; main circuit adopts busbar connection (S6, matched with 3RT1056 contactor), not through-core type; 連絡先: 95-96 (NC ノーマルクローズ), 97-98 (NO ノーマルオープン), 1NO+1NC
- 端子の定義
A1, A2: Auxiliary power supply terminals (AC/DC 24V or 110~240V, depending on sub-version). The 3RB20 draws power here. The electronic relay must be powered up for phase loss/unbalance protection to work.
95, 96: 常閉接点 (ノースカロライナ州) → Standard usage: wired in series into the contactor coil control circuit to cut off and stop the motor on overload trip
97, 98: 常開接点 (いいえ) → For fault alarm, PLC fault input or fault indicator light
主回路: Upper busbar connects to contactor output, lower busbar connects to motor (L1/L2/L3 straight through. The thermal relay does not break the main circuit, only the control circuit)
フロントパネル: Current adjustment knob (50-200あ), M/A DIP switch (マニュアル / auto reset), TEST test button, RESET reset button
- 標準配線図 (Direct-On-Line Start Circuit)
1) 主回路
3-phase power supply → Circuit breaker → 3RT1056 (S6 contactor) → 3RB2056-1FC2 busbar input → 3RB busbar output → Motor
2) 補助回路
- A1/A2: Connected to control power supply (to power the electronic board of thermal relay)
- Contactor coil circuit: Power supply → Stop button → Start button (セルフロック) → 95-96 (ノースカロライナ州) → Contactor coil → Power supply neutral
- Fault signal: 97-98 parallel to fault indicator or PLC DI point
重要: 95-96 is the protection series contact, opens on trip; 97-98 closes synchronously to output fault signal
3) スタンドアロン取り付け (Not clipped onto contactor)
Main circuit remains busbar connection, auxiliary terminals unchanged, fixed separately on backplate. A1/A2 must be powered.
注記: 3RB20 has no A3/A4 remote reset terminals (remote reset is available on 3RB21 only). Only local panel reset or automatic reset is supported.
- M / A Reset DIP Switch
M = Manual Reset (Recommended for safety circuits) : After overload / phase loss trip, the RESET button on panel must be pressed to reset; no automatic restart
A = Auto Reset : Automatically resets after approx. 3 minutes delay after tripping, suitable for low-risk fans with unattended operation; A mode is strictly prohibited for equipment with entanglement hazard
- Complete Commissioning Procedure (Before Power-on → No-load → On-load)
ステップ 1: Pre-power Check (電源オフ)
- Check rated current on motor nameplate, set the current knob to motor rated current (つまり)
例: Motor rated 88A → Align knob at 88A; do not set directly to 200A
Range 50-200A, Class10E fixed and non-adjustable
- Set M/A DIP switch per process requirement (M is default)
- Check tightening torque of busbar bolts, no loose 3-phase busbar connections; secure auxiliary terminal screws
- Continuity test with multimeter: 95-96 conducting normally; 97-98 open normally
ステップ 2: Power on Auxiliary Supply and Test Functions (No High Voltage on Main Circuit!)
- Supply power only to A1/A2, no 380V on main circuit
- プレス [テスト] ボタン:
95-96 開く, 97-98 closes → Contact action normal
Release TEST and press RESET to restore normal state
TEST only simulates contact action, does not simulate real overload current, it is a loop verification
- リセットテスト: For M mode, RESET button must be pressed to restore after test; for A mode wait for auto reset (M mode is used during commissioning generally)
ステップ 3: Energize Main Circuit and No-load Test Run
- Close main circuit, start motor for no-load operation
- Measure 3-phase no-load current with clamp meter and record; confirm no severe unbalance
- If 3-phase current deviation>20%, check motor, wiring and power supply first. The electronic relay will trip for phase loss/unbalance protection directly
ステップ 4: On-load Operation and Current Verification (致命的)
- After motor runs stably at rated load, measure 3-phase operating current with clamp meter
- If steady operating current is 70A, set the knob to 70A;
- Pay attention not to run below the lower limit of the range if starting inrush current is high and rated current is near 50A lower limit;
Definition of Class10E: Trips within 10s at 7.2 定格電流の倍, suitable for standard motors; not suitable for heavy-duty long-start applications (use 3RB2056-2FC2 Class20E for heavy duty)
ステップ 5: Fault Simulation and Acceptance
- Cut off one phase (power off before operation), energize and verify: thermal relay triggers phase loss protection, 95-96 opens to stop motor
- 記録: setting current, リセットモード, trip logs
- Acceptance criteria: 過負荷, phase loss and phase unbalance trigger reliable tripping; self-locking circuit and fault signal output normal
- Quick Fault Troubleshooting
- 過負荷時にトリップしない: ① A1/A2 no power supply (no supply = no protection for electronic relay); ② setting current too high; ③ TEST button failure
- Trip immediately upon energizing: Severe 3-phase unbalance, モーター巻線の短絡, setting current too low
- Cannot auto reset after trip: DIP switch at M (普通); if switch at A and still no auto reset, device aging
- Normal no-load, trips frequently under load: モーターの過負荷, bearing jam, large supply voltage drop, setting current too low
- Important Safety Reminders
This is an electronic thermal relay. Protection fails if A1/A2 power is lost! This differs fundamentally from traditional bimetallic 3RU thermal relays
S6 busbar requires strict tightening torque. Poor contact causes heating and false tripping
Automatic reset mode A is forbidden for safety-critical equipment (コンベア, ミキサー)
- Matching Replacement Reference
Same frame Class10: New generation 3RB3056
Same frame Class20: 3RB2056-2FC2 (heavy-duty start)
3RB2056-1FC2 (S6 / 50-200あ / Class10E) 故障 & ソリューション
Pre-reminder: Electronic relay loses all protection without A1/A2 supply, different from traditional bimetallic 3RU. No fault indicator LEDs. Troubleshooting relies on TEST button, multimeter and clamp meter.
故障 1: No trip when motor is overloaded (Protection failure)
症状: Motor overheats obviously, 95-96 contacts of thermal relay do not act and motor does not stop
原因 1: A1/A2 auxiliary supply lost, wrong voltage or loose terminals (Most frequent)
救済策: Measure A1/A2 voltage; verify supply specification; tighten auxiliary terminals. Continuous power supply is required for current detection
原因 2: Current knob set far higher than motor rated current
救済策: Reset to motor rated current per nameplate, verify with clamp meter under operation
原因 3: Loose main busbar bolts, poor contact and abnormal internal sampling
救済策: 電源を切る, tighten 3-phase busbar to S6 specified torque; check busbar for oxidation and discoloration from heat
原因 4: Internal sampling board damaged or component aging (High risk for discontinued stock units)
救済策: Run TEST test. If 95-96 does not switch when TEST pressed → relay damaged, 直接交換する
故障 2: Normal no-load, frequent tripping under load (誤トリップ)
症状: Starts fine without load, trips shortly after loading, 95-96 開く
原因 1: 設定電流が低すぎる; Class10E trips fast, not fit for heavy-duty long-start motors
救済策: モーターの定格電流を確認する; use 3RB2056-2FC2 (Class20E) for heavy starting applications
原因 2: 3-phase current unbalance, 位相損失, burnt contactor contacts
救済策: Measure 3-phase currents with clamp meter; trip triggered if deviation>20%; check upstream contactor and power supply
原因 3: Loose busbar generates heat and sampling drift causes false overload judgement
救済策: Stop equipment, check busbar temperature and oxidation, 締め直す
原因 4: Ambient temperature over 60℃, poor cabinet ventilation
救済策: 冷却を改善する; reserve current margin for high-temperature environments
故障 3: Immediate trip when energizing / 起動 (Trip on switch-on)
症状: Thermal relay trips as soon as main circuit is energized before motor rotates
原因 1: モーター巻線の短絡, insulation failure, mechanical seizure or stall
救済策: Disconnect motor, test insulation with megger; check bearing by hand rotation
原因 2: Interference on A1/A2 supply, large control voltage fluctuation
救済策: Add filter on control supply; separate supply from variable frequency drives and large contactors
原因 3: DIP switch at A auto reset, fault still present and re-trips immediately after closing
救済策: Switch to M manual reset, eliminate root fault before re-energizing, avoid repeated trial switching
故障 4: トリップ後リセットできない (RESET button ineffective)
症状: After protection triggers, 95-96 cannot restore conduction even after pressing RESET
原因 1: Root fault persists (継続的な過負荷, 位相損失, 発作) so protection latches
救済策: Cut main circuit, eliminate load fault then reset
原因 2: DIP switch at M manual reset but A1/A2 supply drops
救済策: Reset only with stable A1/A2 supply; reset not possible when power is lost
原因 3: Internal mechanical jam, contact welding or electronic board latch-up
救済策: Power off and rest for 5 minutes and retry; if still fails TEST test, ユニットを交換する
補足: 3RB20 has no remote reset terminals. Remote reset is available only on 3RB21. Do not add external remote reset wiring.
故障 5: Auto reset mode A fails to reset automatically
症状: Set to auto reset, no recovery after long waiting post trip
原因 1: A1/A2 auxiliary supply interrupted, auto-reset timer stops when power is lost
救済策: Keep A1/A2 continuously powered
原因 2: Fault remains active (persistent overload, 位相損失), protection stays latched and will not reset
救済策: Root fault must be cleared first
原因 3: Unit aging, auto-reset timing circuit failure
救済策: Change to M manual reset; replace if auto reset is mandatory
故障 6: TEST button no response (Contacts do not switch on TEST press)
症状: Only A1/A2 powered, 95-96 remains closed and 97-98 stays open when TEST pressed
原因 1: A1/A2 no power supply or mismatched voltage
救済策: Measure auxiliary supply voltage
原因 2: TEST button mechanically jammed or internal electronic board damaged
救済策: Power off and clean; replace relay if still invalid
TEST only verifies auxiliary contact loop, does not simulate real overload current. Passing TEST only confirms contact loop works, not current sampling.
故障 7: No fault signal output from 97-98 after trip (PLC no fault feedback)
症状: Motor stops after trip but NO fault signal output
原因 1: Loose wiring or broken wire on 97-98 端子
救済策: Measure continuity of 97-98 under tripped state
原因 2: Insufficient contact rating, voltage drop when driving low-power PLC DI
救済策: Confirm contact load rating; add intermediate relay if required
原因 3: Internal auxiliary contact burnt and damaged
救済策: Run TEST test; replace relay if 97-98 does not close
故障 8: Random intermittent tripping during operation
症状: Current reading normal, trips irregularly
原因 1: Intermittent loose connection on busbar or auxiliary terminals (振動, thermal expansion)
救済策: Retighten all terminals and check cabinet vibration
原因 2: Control supply fluctuation and harmonic interference (common with VFD circuits)
救済策: Add isolation on control loop; this model is not recommended directly on VFD output, dedicated motor protection relay preferred
原因 3: Unit aging, sampling circuit drift (Common for old discontinued stock)
救済策: リレーを交換する, prefer 3RB30 new generation
故障 9: Relay latches to trip immediately after auxiliary power on, motor not energized
症状: 380V main circuit not powered, 95-96 opens right after A1/A2 supply is switched on
原因: Internal electronic board failure, damaged sampling circuit
救済策: Replace overload relay
Standard Field Troubleshooting Flow
- Confirm A1/A2 auxiliary power supply normal (First check for electronic relay)
- Trigger TEST button to verify contact operation
- Measure 3-phase operating current with clamp meter and cross-check setting value
- Inspect 3-phase voltage, contactor contacts, motor insulation and busbar tightness
- Confirm M/A reset mode matches process requirements
- If all above checks pass and fault persists → Relay internal damage
Critical Pitfall Notes
- Not recommended for direct use on VFD output side; harmonics cause false detection
- Auto reset mode A must not be used long-term on safety equipment (コンベア, ミキサー)
- このモデルは生産終了です; inventory spares suffer higher electronic board aging risk than newer 3RB30 series
- S6 busbar loose torque causes continuous heating and sampling drift false tripping
SIRIUS 3RB2 Electronic Overload Relay Series Overview
Series includes: 3RB20 (標準バージョン, no remote reset), 3RB21 (Enhanced version with remote reset terminals); All discontinued by OEM, only spare stock available. Electronic type requiring A1/A2 auxiliary supply; 保護: 過負荷, 位相損失, 位相アンバランス, ストール; Standard contacts 1NO+1NC; Main circuit busbar connection; Frame sizes S6 / S10 / S12; Current range 50~820A
モデルコードの定義 (3RB2 □ □□ □□□)
3RB20: 基本バージョン, no remote reset (3RB2056-1FC2 belongs here)
3RB21: 強化版, with remote reset terminals A3/A4
5th-6th digits: 56=S6 (50-200あ); 66=S10/S12 (55-630あ)
プレフィックス 1 = Class10E; 接頭語 2 = Class20E (heavy-duty start)
サフィックス:
FC2: ネジ端子, direct snap-on to contactor
FF2: スタンドアロン取付, ネジ端子
FW2: スプリング端子, snap-on
FX2: スプリング端子 + standalone mounting
GC2 / GF2 / MC2 / MF2: S10/S12 specifications
- 3RB20 Series List (No Remote Reset)
| 注文番号. | 電流範囲 | フレーム | 旅行クラス | Matching Contactor | 備考 |
| 3RB2056-1FC2 | 50–200A | S6 | Class10E | 3RT1056 | Snap-on, ネジ端子, main subject, 製造中止 |
| 3RB2056-1FF2 | 50–200A | S6 | Class10E | 3RT1056 | スタンドアロン, ネジ端子 |
| 3RB2056-1FW2 | 50–200A | S6 | Class10E | 3RT1056 | Snap-on, スプリング端子 |
| 3RB2056-1FX2 | 50–200A | S6 | Class10E | 3RT1056 | スタンドアロン, スプリング端子 |
| 3RB2056-2FC2 | 50–200A | S6 | Class20E | 3RT1056 | Heavy-duty snap-on, ネジ端子, popular replacement |
| 3RB2056-2FF2 | 50–200A | S6 | Class20E | 3RT1056 | Heavy-duty standalone, ネジ端子 |
| 3RB2056-2FW2 | 50–200A | S6 | Class20E | 3RT1056 | Heavy-duty snap-on, スプリング端子 |
| 3RB2056-2FX2 | 50–200A | S6 | Class20E | 3RT1056 | Heavy-duty standalone, スプリング端子 |
| 3RB2066-1GC2 | 55–250A | S10 | Class10E | 3RT1065 | Snap-on, ネジ端子 |
| 3RB2066-1GF2 | 55–250A | S10 | Class10E | 3RT1065 | スタンドアロン, ネジ端子 |
| 3RB2066-1MC2 | 160–630A | S12 | Class10E | 3RT1066 | Snap-on, ネジ端子 |
| 3RB2066-1MF2 | 160–630A | S12 | Class10E | 3RT1066 | スタンドアロン, ネジ端子 |
| 3RB2066-2GC2 | 55–250A | S10 | Class20E | 3RT1065 | Heavy-duty snap-on, ネジ端子 |
| 3RB2066-2GF2 | 55–250A | S10 | Class20E | 3RT1065 | Heavy-duty standalone, ネジ端子 |
| 3RB2066-2MC2 | 160–630A | S12 | Class20E | 3RT1066 | Heavy-duty snap-on, ネジ端子 |
| 3RB2066-2MF2 | 160–630A | S12 | Class20E | 3RT1066 | Heavy-duty standalone, ネジ端子 |
| 3RB2011 + 3UF18 | 630–820A | S14 | Class10E | 3TF68/3TF69 | CT combination solution |
- 3RB21 Series List (With Remote Reset A3/A4)
Suitable for PLC remote reset; protection functions and current ranges same as 3RB20
| 3RB2156-1FC2 | 50-200あ | S6 | Class10E | Remote reset, snap-on, ネジ端子 |
| 3RB2156-1FF2 | 50-200あ | S6 | Class10E | Remote reset, スタンドアロン, ネジ端子 |
| 3RB2156-2FC2 | 50-200あ | S6 | Class20E | 耐久性の高い + リモートリセット |
| 3RB2166-1GC2 | 55-250あ | S10 | Class10E | S10 remote reset |
| 3RB2166-1MC2 | 160-630あ | S12 | Class10E | S12 remote reset |
| 3RB2166-2GC2 | 55-250あ | S10 | Class20E | S10 heavy duty + リモートリセット |
| 3RB2166-2MC2 | 160-630あ | S12 | Class20E | S12 heavy duty + リモートリセット |
| 3RB2111 + 3UF18 | 630-820あ | S14 | Class10E | CT combination, リモートリセット |
- Common Series Parameters
- Auxiliary supply: A1/A2, AC/DC 24V or AC110~240V (depends on sub-version). Protection fails when supply is lost
- 補助接点: 95-96 (ノースカロライナ州), 97-98 (いいえ), 1NO+1NC, 5評価
- リセット: M/A DIP switch (マニュアル / auto reset); 3RB21 adds A3/A4 remote reset
- 保護クラス: IP20; Insulation voltage 1000V AC, インパルス耐電圧8kV; Operating temperature -25~+60℃
- 主回路: バスバー接続, not through-core CT type
- 応用: Standard 3-phase asynchronous motors; Not recommended directly on VFD output; harmonics cause false tripping
- New Generation Replacement Series (新しいプロジェクトに推奨)
S6 50-200A replacement: 3RB3056 (新世代, より良い安定性, active supply)
S10/S12 high-current: 3RB3066 for equivalent replacement
- クイックセレクションガイド
No remote reset required → 3RB20
PLC remote reset required → 3RB21
標準ファン, パンプス, smooth start → Class10E (接頭語 1)
ベルトコンベア, 破砕機, heavy-duty long start → Class20E (接頭語 2)
Snap-on mounting with contactor → FC2 / GC2 / MC2
Separate backplate mounting → FF2 / GF2 / MF2