Siemens 3RB2056-1FC2 Electronic Overload Relay

状態: Discontinued by original manufacturer, Class 10E, S6 frame, electronic motor protection relay Basic Specifications Order No.: 3RB2056-1FC2 Current setting range: 50 … 200 A Frame size: S6 (compatible with S6 contactors such as 3RT1056) 旅行クラス: Class 10E (修理済み, 調整不可) Matched motor power at 400V 50Hz: 30~90 kW Main circuit connection: Busbar connection Auxiliary ...

  • 製品詳細

状態: Discontinued by original manufacturer, Class 10E, S6 frame, electronic motor protection relay

基本仕様

注文番号: 3RB2056-1FC2

電流設定範囲: 50 … 200 あ

フレームサイズ: S6 (compatible with S6 contactors such as 3RT1056)

旅行クラス: Class 10E (修理済み, 調整不可)

Matched motor power at 400V 50Hz: 30~90kW

主回路接続: バスバー接続

補助回路: ネジ端子, auxiliary contacts 1NO + 1ノースカロライナ州

リセットモード: マニュアル / automatic reset selectable

取り付け: Direct snap-on to S6 contactor or standalone mounting

保護クラス: IP20

定格絶縁電圧: 1000Vと, インパルス耐電圧8kV

周波数範囲: 50/60Hz

動作温度: -25℃~+60℃

保護機能

電子式, different from bimetallic thermal relays:

Inverse-time overload protection

位相損失 / 位相不平衡保護

Motor stall protection

Built-in test button for loop testing

モデルの区別 (Easily Confused Models in the Same Series)

3RB2056-1FC2: Class10E, 製造中止

3RB2056-2FC2 / 2FX2: Class20E, heavy-duty start version, 最も一般的な代替品

Replacement Selection Suggestions

  1. 同じ仕様で直接交換可能: 3RB2056-2FC2 (Class20E); if Class10 is strictly required, prioritize the new generation 3RB3056 series electronic 過負荷リレー
  2. Matching contactor: シーメンス 3RT1056 (S6)
  3. 国内代替品: Domestic electronic thermal relay with 50-200A, S6 footprint, 1NO+1NC, Class10

重要なメモ

3RB2056-1FC2 is an older imported 3RB2 model, discontinued by Siemens. Stock units are only available from inventory. New projects are generally recommended to adopt the new 3RB30 series.

3RB2056-1FC2 (S6 / 50-200あ / Class10E) 配線 & 試運転マニュアル

備考: Electronic type requiring auxiliary power supply A1/A2; main circuit adopts busbar connection (S6, matched with 3RT1056 contactor), not through-core type; 連絡先: 95-96 (NC ノーマルクローズ), 97-98 (NO ノーマルオープン), 1NO+1NC

  1. 端子の定義

A1, A2: Auxiliary power supply terminals (AC/DC 24V or 110~240V, depending on sub-version). The 3RB20 draws power here. The electronic relay must be powered up for phase loss/unbalance protection to work.

95, 96: 常閉接点 (ノースカロライナ州) → Standard usage: wired in series into the contactor coil control circuit to cut off and stop the motor on overload trip

97, 98: 常開接点 (いいえ) → For fault alarm, PLC fault input or fault indicator light

主回路: Upper busbar connects to contactor output, lower busbar connects to motor (L1/L2/L3 straight through. The thermal relay does not break the main circuit, only the control circuit)

フロントパネル: Current adjustment knob (50-200あ), M/A DIP switch (マニュアル / auto reset), TEST test button, RESET reset button

  1. 標準配線図 (Direct-On-Line Start Circuit)

1) 主回路

3-phase power supply → Circuit breaker → 3RT1056 (S6 contactor) → 3RB2056-1FC2 busbar input → 3RB busbar output → Motor

2) 補助回路

  1. A1/A2: Connected to control power supply (to power the electronic board of thermal relay)
  2. Contactor coil circuit: Power supply → Stop button → Start button (セルフロック) → 95-96 (ノースカロライナ州) → Contactor coil → Power supply neutral
  3. Fault signal: 97-98 parallel to fault indicator or PLC DI point

重要: 95-96 is the protection series contact, opens on trip; 97-98 closes synchronously to output fault signal

3) スタンドアロン取り付け (Not clipped onto contactor)

Main circuit remains busbar connection, auxiliary terminals unchanged, fixed separately on backplate. A1/A2 must be powered.

注記: 3RB20 has no A3/A4 remote reset terminals (remote reset is available on 3RB21 only). Only local panel reset or automatic reset is supported.

  1. M / A Reset DIP Switch

M = Manual Reset (Recommended for safety circuits) : After overload / phase loss trip, the RESET button on panel must be pressed to reset; no automatic restart

A = Auto Reset : Automatically resets after approx. 3 minutes delay after tripping, suitable for low-risk fans with unattended operation; A mode is strictly prohibited for equipment with entanglement hazard

  1. Complete Commissioning Procedure (Before Power-on → No-load → On-load)

ステップ 1: Pre-power Check (電源オフ)

  1. Check rated current on motor nameplate, set the current knob to motor rated current (つまり)

例: Motor rated 88A → Align knob at 88A; do not set directly to 200A

Range 50-200A, Class10E fixed and non-adjustable

  1. Set M/A DIP switch per process requirement (M is default)
  2. Check tightening torque of busbar bolts, no loose 3-phase busbar connections; secure auxiliary terminal screws
  3. Continuity test with multimeter: 95-96 conducting normally; 97-98 open normally

ステップ 2: Power on Auxiliary Supply and Test Functions (No High Voltage on Main Circuit!)

  1. Supply power only to A1/A2, no 380V on main circuit
  2. プレス [テスト] ボタン:

95-96 開く, 97-98 closes → Contact action normal

Release TEST and press RESET to restore normal state

TEST only simulates contact action, does not simulate real overload current, it is a loop verification

  1. リセットテスト: For M mode, RESET button must be pressed to restore after test; for A mode wait for auto reset (M mode is used during commissioning generally)

ステップ 3: Energize Main Circuit and No-load Test Run

  1. Close main circuit, start motor for no-load operation
  2. Measure 3-phase no-load current with clamp meter and record; confirm no severe unbalance
  3. If 3-phase current deviation>20%, check motor, wiring and power supply first. The electronic relay will trip for phase loss/unbalance protection directly

ステップ 4: On-load Operation and Current Verification (致命的)

  1. After motor runs stably at rated load, measure 3-phase operating current with clamp meter
  2. If steady operating current is 70A, set the knob to 70A;
  3. Pay attention not to run below the lower limit of the range if starting inrush current is high and rated current is near 50A lower limit;

Definition of Class10E: Trips within 10s at 7.2 定格電流の倍, suitable for standard motors; not suitable for heavy-duty long-start applications (use 3RB2056-2FC2 Class20E for heavy duty)

ステップ 5: Fault Simulation and Acceptance

  1. Cut off one phase (power off before operation), energize and verify: thermal relay triggers phase loss protection, 95-96 opens to stop motor
  2. 記録: setting current, リセットモード, trip logs
  3. Acceptance criteria: 過負荷, phase loss and phase unbalance trigger reliable tripping; self-locking circuit and fault signal output normal
  4. Quick Fault Troubleshooting
  5. 過負荷時にトリップしない: ① A1/A2 no power supply (no supply = no protection for electronic relay); ② setting current too high; ③ TEST button failure
  6. Trip immediately upon energizing: Severe 3-phase unbalance, モーター巻線の短絡, setting current too low
  7. Cannot auto reset after trip: DIP switch at M (普通); if switch at A and still no auto reset, device aging
  8. Normal no-load, trips frequently under load: モーターの過負荷, bearing jam, large supply voltage drop, setting current too low
  9. Important Safety Reminders

This is an electronic thermal relay. Protection fails if A1/A2 power is lost! This differs fundamentally from traditional bimetallic 3RU thermal relays

S6 busbar requires strict tightening torque. Poor contact causes heating and false tripping

Automatic reset mode A is forbidden for safety-critical equipment (コンベア, ミキサー)

  1. Matching Replacement Reference

Same frame Class10: New generation 3RB3056

Same frame Class20: 3RB2056-2FC2 (heavy-duty start)

3RB2056-1FC2 (S6 / 50-200あ / Class10E) 故障 & ソリューション

Pre-reminder: Electronic relay loses all protection without A1/A2 supply, different from traditional bimetallic 3RU. No fault indicator LEDs. Troubleshooting relies on TEST button, multimeter and clamp meter.

故障 1: No trip when motor is overloaded (Protection failure)

症状: Motor overheats obviously, 95-96 contacts of thermal relay do not act and motor does not stop

原因 1: A1/A2 auxiliary supply lost, wrong voltage or loose terminals (Most frequent)

救済策: Measure A1/A2 voltage; verify supply specification; tighten auxiliary terminals. Continuous power supply is required for current detection

原因 2: Current knob set far higher than motor rated current

救済策: Reset to motor rated current per nameplate, verify with clamp meter under operation

原因 3: Loose main busbar bolts, poor contact and abnormal internal sampling

救済策: 電源を切る, tighten 3-phase busbar to S6 specified torque; check busbar for oxidation and discoloration from heat

原因 4: Internal sampling board damaged or component aging (High risk for discontinued stock units)

救済策: Run TEST test. If 95-96 does not switch when TEST pressed → relay damaged, 直接交換する

故障 2: Normal no-load, frequent tripping under load (誤トリップ)

症状: Starts fine without load, trips shortly after loading, 95-96 開く

原因 1: 設定電流が低すぎる; Class10E trips fast, not fit for heavy-duty long-start motors

救済策: モーターの定格電流を確認する; use 3RB2056-2FC2 (Class20E) for heavy starting applications

原因 2: 3-phase current unbalance, 位相損失, burnt contactor contacts

救済策: Measure 3-phase currents with clamp meter; trip triggered if deviation>20%; check upstream contactor and power supply

原因 3: Loose busbar generates heat and sampling drift causes false overload judgement

救済策: Stop equipment, check busbar temperature and oxidation, 締め直す

原因 4: Ambient temperature over 60℃, poor cabinet ventilation

救済策: 冷却を改善する; reserve current margin for high-temperature environments

故障 3: Immediate trip when energizing / 起動 (Trip on switch-on)

症状: Thermal relay trips as soon as main circuit is energized before motor rotates

原因 1: モーター巻線の短絡, insulation failure, mechanical seizure or stall

救済策: Disconnect motor, test insulation with megger; check bearing by hand rotation

原因 2: Interference on A1/A2 supply, large control voltage fluctuation

救済策: Add filter on control supply; separate supply from variable frequency drives and large contactors

原因 3: DIP switch at A auto reset, fault still present and re-trips immediately after closing

救済策: Switch to M manual reset, eliminate root fault before re-energizing, avoid repeated trial switching

故障 4: トリップ後リセットできない (RESET button ineffective)

症状: After protection triggers, 95-96 cannot restore conduction even after pressing RESET

原因 1: Root fault persists (継続的な過負荷, 位相損失, 発作) so protection latches

救済策: Cut main circuit, eliminate load fault then reset

原因 2: DIP switch at M manual reset but A1/A2 supply drops

救済策: Reset only with stable A1/A2 supply; reset not possible when power is lost

原因 3: Internal mechanical jam, contact welding or electronic board latch-up

救済策: Power off and rest for 5 minutes and retry; if still fails TEST test, ユニットを交換する

補足: 3RB20 has no remote reset terminals. Remote reset is available only on 3RB21. Do not add external remote reset wiring.

故障 5: Auto reset mode A fails to reset automatically

症状: Set to auto reset, no recovery after long waiting post trip

原因 1: A1/A2 auxiliary supply interrupted, auto-reset timer stops when power is lost

救済策: Keep A1/A2 continuously powered

原因 2: Fault remains active (persistent overload, 位相損失), protection stays latched and will not reset

救済策: Root fault must be cleared first

原因 3: Unit aging, auto-reset timing circuit failure

救済策: Change to M manual reset; replace if auto reset is mandatory

故障 6: TEST button no response (Contacts do not switch on TEST press)

症状: Only A1/A2 powered, 95-96 remains closed and 97-98 stays open when TEST pressed

原因 1: A1/A2 no power supply or mismatched voltage

救済策: Measure auxiliary supply voltage

原因 2: TEST button mechanically jammed or internal electronic board damaged

救済策: Power off and clean; replace relay if still invalid

TEST only verifies auxiliary contact loop, does not simulate real overload current. Passing TEST only confirms contact loop works, not current sampling.

故障 7: No fault signal output from 97-98 after trip (PLC no fault feedback)

症状: Motor stops after trip but NO fault signal output

原因 1: Loose wiring or broken wire on 97-98 端子

救済策: Measure continuity of 97-98 under tripped state

原因 2: Insufficient contact rating, voltage drop when driving low-power PLC DI

救済策: Confirm contact load rating; add intermediate relay if required

原因 3: Internal auxiliary contact burnt and damaged

救済策: Run TEST test; replace relay if 97-98 does not close

故障 8: Random intermittent tripping during operation

症状: Current reading normal, trips irregularly

原因 1: Intermittent loose connection on busbar or auxiliary terminals (振動, thermal expansion)

救済策: Retighten all terminals and check cabinet vibration

原因 2: Control supply fluctuation and harmonic interference (common with VFD circuits)

救済策: Add isolation on control loop; this model is not recommended directly on VFD output, dedicated motor protection relay preferred

原因 3: Unit aging, sampling circuit drift (Common for old discontinued stock)

救済策: リレーを交換する, prefer 3RB30 new generation

故障 9: Relay latches to trip immediately after auxiliary power on, motor not energized

症状: 380V main circuit not powered, 95-96 opens right after A1/A2 supply is switched on

原因: Internal electronic board failure, damaged sampling circuit

救済策: Replace overload relay

Standard Field Troubleshooting Flow

  1. Confirm A1/A2 auxiliary power supply normal (First check for electronic relay)
  2. Trigger TEST button to verify contact operation
  3. Measure 3-phase operating current with clamp meter and cross-check setting value
  4. Inspect 3-phase voltage, contactor contacts, motor insulation and busbar tightness
  5. Confirm M/A reset mode matches process requirements
  6. If all above checks pass and fault persists → Relay internal damage

Critical Pitfall Notes

  1. Not recommended for direct use on VFD output side; harmonics cause false detection
  2. Auto reset mode A must not be used long-term on safety equipment (コンベア, ミキサー)
  3. このモデルは生産終了です; inventory spares suffer higher electronic board aging risk than newer 3RB30 series
  4. S6 busbar loose torque causes continuous heating and sampling drift false tripping

SIRIUS 3RB2 Electronic Overload Relay Series Overview

Series includes: 3RB20 (標準バージョン, no remote reset), 3RB21 (Enhanced version with remote reset terminals); All discontinued by OEM, only spare stock available. Electronic type requiring A1/A2 auxiliary supply; 保護: 過負荷, 位相損失, 位相アンバランス, ストール; Standard contacts 1NO+1NC; Main circuit busbar connection; Frame sizes S6 / S10 / S12; Current range 50~820A

モデルコードの定義 (3RB2 □ □□ □□□)

3RB20: 基本バージョン, no remote reset (3RB2056-1FC2 belongs here)

3RB21: 強化版, with remote reset terminals A3/A4

5th-6th digits: 56=S6 (50-200あ); 66=S10/S12 (55-630あ)

プレフィックス 1 = Class10E; 接頭語 2 = Class20E (heavy-duty start)

サフィックス:

FC2: ネジ端子, direct snap-on to contactor

FF2: スタンドアロン取付, ネジ端子

FW2: スプリング端子, snap-on

FX2: スプリング端子 + standalone mounting

GC2 / GF2 / MC2 / MF2: S10/S12 specifications

  1. 3RB20 Series List (No Remote Reset)
注文番号.電流範囲フレーム旅行クラスMatching Contactor備考
3RB2056-1FC250–200AS6Class10E3RT1056Snap-on, ネジ端子, main subject, 製造中止
3RB2056-1FF250–200AS6Class10E3RT1056スタンドアロン, ネジ端子
3RB2056-1FW250–200AS6Class10E3RT1056Snap-on, スプリング端子
3RB2056-1FX250–200AS6Class10E3RT1056スタンドアロン, スプリング端子
3RB2056-2FC250–200AS6Class20E3RT1056Heavy-duty snap-on, ネジ端子, popular replacement
3RB2056-2FF250–200AS6Class20E3RT1056Heavy-duty standalone, ネジ端子
3RB2056-2FW250–200AS6Class20E3RT1056Heavy-duty snap-on, スプリング端子
3RB2056-2FX250–200AS6Class20E3RT1056Heavy-duty standalone, スプリング端子
3RB2066-1GC255–250AS10Class10E3RT1065Snap-on, ネジ端子
3RB2066-1GF255–250AS10Class10E3RT1065スタンドアロン, ネジ端子
3RB2066-1MC2160–630AS12Class10E3RT1066Snap-on, ネジ端子
3RB2066-1MF2160–630AS12Class10E3RT1066スタンドアロン, ネジ端子
3RB2066-2GC255–250AS10Class20E3RT1065Heavy-duty snap-on, ネジ端子
3RB2066-2GF255–250AS10Class20E3RT1065Heavy-duty standalone, ネジ端子
3RB2066-2MC2160–630AS12Class20E3RT1066Heavy-duty snap-on, ネジ端子
3RB2066-2MF2160–630AS12Class20E3RT1066Heavy-duty standalone, ネジ端子
3RB2011 + 3UF18630–820AS14Class10E3TF68/3TF69CT combination solution
  1. 3RB21 Series List (With Remote Reset A3/A4)

Suitable for PLC remote reset; protection functions and current ranges same as 3RB20

| 3RB2156-1FC2 | 50-200あ | S6 | Class10E | Remote reset, snap-on, ネジ端子 |

| 3RB2156-1FF2 | 50-200あ | S6 | Class10E | Remote reset, スタンドアロン, ネジ端子 |

| 3RB2156-2FC2 | 50-200あ | S6 | Class20E | 耐久性の高い + リモートリセット |

| 3RB2166-1GC2 | 55-250あ | S10 | Class10E | S10 remote reset |

| 3RB2166-1MC2 | 160-630あ | S12 | Class10E | S12 remote reset |

| 3RB2166-2GC2 | 55-250あ | S10 | Class20E | S10 heavy duty + リモートリセット |

| 3RB2166-2MC2 | 160-630あ | S12 | Class20E | S12 heavy duty + リモートリセット |

| 3RB2111 + 3UF18 | 630-820あ | S14 | Class10E | CT combination, リモートリセット |

 

  1. Common Series Parameters
  2. Auxiliary supply: A1/A2, AC/DC 24V or AC110~240V (depends on sub-version). Protection fails when supply is lost
  3. 補助接点: 95-96 (ノースカロライナ州), 97-98 (いいえ), 1NO+1NC, 5評価
  4. リセット: M/A DIP switch (マニュアル / auto reset); 3RB21 adds A3/A4 remote reset
  5. 保護クラス: IP20; Insulation voltage 1000V AC, インパルス耐電圧8kV; Operating temperature -25~+60℃
  6. 主回路: バスバー接続, not through-core CT type
  7. 応用: Standard 3-phase asynchronous motors; Not recommended directly on VFD output; harmonics cause false tripping
  8. New Generation Replacement Series (新しいプロジェクトに推奨)

S6 50-200A replacement: 3RB3056 (新世代, より良い安定性, active supply)

S10/S12 high-current: 3RB3066 for equivalent replacement

  1. クイックセレクションガイド

No remote reset required → 3RB20

PLC remote reset required → 3RB21

標準ファン, パンプス, smooth start → Class10E (接頭語 1)

ベルトコンベア, 破砕機, heavy-duty long start → Class20E (接頭語 2)

Snap-on mounting with contactor → FC2 / GC2 / MC2

Separate backplate mounting → FF2 / GF2 / MF2