シュナイダー A9DA2616 (Acti9 iDD40T 1P+N C16 30mA AC) 残留電流作動型サーキットブレーカー with Overcurrent Protection (RCBO)
- モデルの解釈
A9DA2616 = Acti9 Series iDD40T Product Type 1P+N Pole Configuration C-type Tripping Curve 16A Rated Current 30mA Residual Current AC-type Residual Current Detection
- コア技術パラメータ (Compliant with IEC 61009-1/GB 16917.1)
| パラメータ | 仕様 |
| 製品タイプ | Residual Current Operated Circuit Breaker with Overcurrent Protection (RCBO, integrating three protections: 過負荷, 短絡, および残留電流) |
| ポール構成 | 1P+N (1 ポール + 中性, phase line breaks, neutral line remains conducting permanently) |
| 定格電流 (で) | 16あ |
| トリッピングカーブ | C-type (instantaneous tripping at 5~10 In), suitable for lighting, socket, and general motor loads |
| 定格残留動作電流 (IΔn) | 30ミリアンペア (personal safety protection level) |
| Residual Current Type | AC-type (detects sinusoidal AC leakage current, suitable for conventional environments) |
| 定格電圧 (うえ) | 230Vと (1P+N), 50/60Hz |
| Short-circuit Breaking Capacity (アイコン) | 6の (400V) / 4500あ (230V) |
| Rated Residual Operating Time (at IΔn) | ≤0.3s |
| 機械的寿命 | 10,000 オペレーション |
| 電気的寿命 | 5,000 オペレーション |
| 取付方法 | 35mm DINレール (18幅mm) |
| Wiring Specification | Solid wire: 1~25 mm²; Flexible wire: 1~16 mm² (with cable lugs) |
| Terminal Torque | 2.0 N・m |
| 動作温度 | -25℃~+70℃ |
| 保護クラス | IP20 (for use inside distribution boxes) |
| 定格インパルス耐電圧 (ウンプ) | 4kV |
- 機能 & アプリケーション
コア機能
過負荷保護: Realizes inverse-time protection via the thermal bending of bimetallic strips.
Short-circuit Protection: Achieves instantaneous protection through electromagnetic release.
残留電流保護: Rapidly trips within ≤0.3s when detected residual current exceeds 30mA, preventing electric shock accidents.
典型的なアプリケーションシナリオ
- Branch circuit protection for residential/commercial buildings (例えば, lighting and socket circuits)
- Electrical safety protection for crowded places such as offices and shops
- Power supply protection for small household appliances and office equipment
- Replacement for traditional MCB + RCCB combinations, 配電ボックスのスペースを節約する
Selection Tips
AC-type is suitable for pure AC load environments, such as traditional lighting and resistive loads.
For loads containing DC components (例えば, switching power supplies, LED lighting), A-type or B-type residual current circuit breakers are recommended.
30mA is the standard value for personal safety protection and shall not be used for equipment protection (300mA is usually selected for equipment protection).
- インストール & メンテナンスのポイント
- 配線仕様: Top-in bottom-out (bidirectional wiring with bottom-in top-out supported). Connect phase line to L pole and neutral line to N pole; reverse connection is strictly prohibited.
- Residual Current Test: インストール後, テストボタンを押してください (T button) to confirm the normal operation of the residual current protection function.
- 定期点検: Press the test button once a quarter to verify the effectiveness of the residual current protection function.
- Fault Handling:
Overload/Short-circuit Tripping: Troubleshoot load or line faults before closing the breaker directly.
Residual Current Tripping: First disconnect all loads, check for leakage points one by one, and close the breaker only after repairs; forced closing with faults is strictly prohibited.
- Spacing Requirement: Maintain a gap of ≥3mm from adjacent components to ensure heat dissipation and wiring space.
- Corresponding Chint Product & Replacement Comparison
Chint Equivalent Model: NXBLE-63 1P+N C16 30mA AC
| パラメータのカテゴリ | シュナイダー A9DA2616 | Chint NXBLE-63 1P+N C16 30mA | 交換互換性 |
| コアの保護 | 過負荷 + 短絡 + Residual Current (RCBO) | 過負荷 + 短絡 + Residual Current (RCBO) | ✅ Fully Matched |
| Pole Configuration/Tripping Curve/In | 1P+N/C-type/16A | 1P+N/C-type/16A | ✅ Fully Matched |
| IΔn/IΔ Type | 30mA/AC | 30mA/AC | ✅ Fully Matched |
| 遮断容量 | 6の | 6の | ✅ Fully Matched |
| 設置寸法 | 18mm (幅) × 91mm (身長) × 65mm (深さ) | 18mm (幅) × 91mm (身長) × 65mm (深さ) | ✅ Identical Dimensions |
| Wiring Specification | Solid wire: 1~25 mm² | Solid wire: 10~16 mm² | ⚠️ Schneider Terminals Have Larger Capacity |
| 動作温度 | -25℃~+70℃ | -30℃~+70℃ | ✅ Chint Has Better Low-temperature Adaptability |
| Additional Functions | VisiTrip Fault Indication | Red-Green Window Indication (Red for Closed, Green for Open) | ⚠️ Different Indication Methods |
| 保証期間 | 24 月 | 18 月 | ⚠️ Warranty Difference |
Key Replacement Precautions
- ✅ Installation Compatibility: Both are mounted on 35mm DIN rails with 18mm width, enabling direct interchange.
- ✅ Protection Characteristics: C-type curve, 16定格電流, and 30mA residual current protection are fully consistent; no load adjustment is required.
- ⚠️ Wiring Adaptation: Schneider terminals support larger wire diameters; keep the original wire diameter during replacement to avoid loose connections.
- ⚠️ Function Identification: The VisiTrip indication window of Schneider shows red after tripping; it is necessary to train operators to recognize the new marks.
- まとめ & 選択の推奨事項
Schneider A9DA2616 is a 1P+N 16A RCBO in the Acti9 series iDD40T product line. It integrates triple protection functions and is suitable for personal safety protection in conventional environments.
選択の推奨事項:
For international brand reputation and reliable performance: Choose Schneider A9DA2616, which provides more comprehensive fault indication and bidirectional wiring functions.
For cost-effectiveness: Choose Chint NXBLE-63 1P+N C16 30mA, which features more favorable pricing and performance meeting national standards.
For special environments (例えば, low temperature < -25℃): Prioritize Chint products for their better low-temperature adaptability.