(MN Type 125VDC Undervoltage Release)
Schneider LV429413 is an MN series undervoltage release specially designed for molded case circuit breakers of the Compact NSX, PowerPact Multistandard, and EasyPact CVS series. It has a rated voltage of 125VDC and uses screwless spring terminals. It is used for emergency stop or remote tripping control. When the control voltage drops below 35% 定格値の, it automatically trips the circuit breaker to ensure system safety.
- Model Code Interpretation
| コードセグメント | 意味 |
| LV | Prefix for Schneider low-voltage power distribution products |
| 4294 | Product category identifier for undervoltage releases |
| 13 | Specific specification code corresponding to 125VDC rating, MN type, screwless terminals |
| ミネソタ州 | Product type code: 不足電圧解除; MX denotes Shunt Trip |
コア機能: 125VDC operating voltage, suitable for 100-630A molded case circuit breakers, non-delay type, tripping threshold at 35% 定格電圧の.
- コア技術パラメータ
| アイテム | 仕様 |
| 製品タイプ | MN Type Undervoltage Release |
| Rated Control Voltage | 125VDC (not for AC systems) |
| Tripping Threshold | ≤ 35% 定格電圧の (約. 43.75VDC) |
| Reset Voltage | ≥ 85% 定格電圧の (約. 106.25VDC) |
| 端子の種類 | Screwless Spring Terminal |
| Compatible Breaker Series | Compact NSX 100–630A, PowerPact Multistandard, EasyPact CVS |
| Mounting Location | Accessory slot on front of circuit breaker |
| Wire Capacity | 1.5–2.5mm² cable |
| Ingress Protection | IP20 (when installed) |
| 動作温度 | -25℃~+70℃ |
| 重さ | 約. 50g |
| 認証 | IEC 60947-2, UL 489, CSA C22.2 No. 5 |
- Application Environment
- System Types
Industrial automation control systems, data center UPS systems
DC power supply systems, emergency stop circuits
Remote monitoring and tripping applications
- Operating Conditions
Control voltage fluctuation: 85%-110% of rated value for stable operation
EMC performance: IEC準拠 61000-4
Compatible frame sizes: 100あ, 160あ, 250あ, 400あ, 630あ (NSX series)
- インストール要件
Must be installed in dedicated front accessory slot with reliable mechanical interlock
Control circuit to be protected by 1A fuse to prevent coil damage from short circuit
Observe polarity: “+” for positive, “-” for negative
- Cross-Reference & 代替モデル
| Replacement Type | モデル | ブランド | 説明 |
| 直接交換 | LV429414 | シュナイダー | 220VAC version for AC control circuits |
| Equivalent Function | S29413 | シュナイダー (Square D) | 125VDC undervoltage release for PowerPact series |
| Cross鈥態rand Alternative | ABB TA250-125DC | ABB | 125VDC undervoltage release for Tmax MCCBs |
| Domestic Alternative | CHINT NXB-MN/125DC | チント | For NXB series MCCBs |
- 公式注文情報
| アイテム | 詳細 |
| Official Model | LV429413 (global part number) |
| 製品名 | Undervoltage Release MN, Compact NSX, 125VDC, Screwless Terminal |
| Order Note | Must match corresponding breaker model, 例えば, NSX100N, NSX250F |
| Packing | Individual package including release body, manual, mounting screws |
| EAN Code | 3606480019029 |
| MOQ | 1 piece |
- Engineering Implementation
- 互換性チェック
Confirm breaker model: only for Compact NSX (100-630あ), PowerPact Multistandard, EasyPact CVS
Verify control voltage: strictly 125VDC, not for AC or other DC voltages
Ensure front slot available for MN/MX accessories
- インストール手順
- Disconnect main and control power to the breaker
- Remove front accessory cover
- Insert undervoltage release into slot and engage mechanical interlock
- Secure with supplied screws
- Wire 125VDC with correct polarity
- Refit cover and perform functional test
- Commissioning
Trip test: reduce voltage below 43VDC; breaker must trip automatically
Reset test: restore voltage above 106VDC; breaker should close normally
Interlock check: breaker cannot be manually closed when release is activated until voltage recovers
- Complete Model List (MN Series Undervoltage Releases)
| モデル | 定格電圧 | 端子の種類 | Compatible Series | 備考 |
| LV429400 | 24VAC/DC | Screw Terminal | NSX/CVS | 標準 |
| LV429401 | 48VAC/DC | Screw Terminal | NSX/CVS | 標準 |
| LV429402 | 110VAC/DC | Screw Terminal | NSX/CVS | 標準 |
| LV429403 | 220VAC/DC | Screw Terminal | NSX/CVS | 標準 |
| LV429410 | 24VDC | Screwless Terminal | NSX/CVS | Spring Terminal |
| LV429411 | 48VDC | Screwless Terminal | NSX/CVS | Spring Terminal |
| LV429412 | 110VDC | Screwless Terminal | NSX/CVS | Spring Terminal |
| LV429413 | 125VDC | Screwless Terminal | NSX/CVS | Spring Terminal |
| LV429414 | 220VAC | Screwless Terminal | NSX/CVS | Spring Terminal |
| LV429415 | 230VAC | Screwless Terminal | NSX/CVS | Spring Terminal |
- Risks & Warnings
- 電圧マッチング: This model is only for 125VDC control circuits. Applying AC or incorrect DC voltage will burn the coil and damage the unit.
- Polarity: DC polarity must be observed; reversed connection causes failure or circuit damage.
- Overcurrent Protection: Install 1A fast-acting fuse in control circuit to protect coil.
- 機械的インターロック: Ensure reliable engagement; さもないと, false tripping or failure to trip may occur.
- Ambient Limits: Do not use above +70°C or below -25°C to avoid performance degradation.
- メンテナンス: Regularly check control voltage stability (85%-110% of rated) to prevent excessive mechanical wear from frequent undervoltage tripping.
コンタクタ,サーキットブレーカー,ソーラーインバーター,電気メーター,太陽電池