(Varispeed P7 Inverter Specialized for Fans & パンプス)
- モデルコードの内訳
CIMR-P7U4160 (Full name on nameplate: CIMR-P7U41600 PDF)
CIMR: Universal prefix for Yaskawa インバータ
P7: P7 series, energy-saving V/F inverter dedicated to fans and pumps
U: 400V three-phase high-voltage model (380~480V)
4160: Power rating code, corresponding to 250HP / 160kW class
- Core Electrical Rated Specifications
2.1 Main Circuit Power Ratings
| アイテム | 価値 |
| Input Specification | 3-phase AC 380~480V, 50/60Hz |
| 定格入力電流 | 334 あ |
| Rated Output Capacity | 230 kVA |
| 定格出力電流 | 304 あ (ND Normal Duty) |
| Matching Motor Power | 250HP / 160kW 3-phase induction motor |
| Max Output Voltage | 3-段階 0 ~ input voltage (最大. 480V) |
| 最大出力周波数 | 120 Hz |
| キャリア周波数 | Adjustable from 2kHz to 10kHz |
| Accel/Decel Time Range | 0.0~6000s, two independent accel/decel groups |
2.2 Allowable Power Supply Fluctuation
電圧: +10% / -15%
頻度: ±5%
2.3 制御性能
Speed Adjustment Range: 40:1 (V/F制御)
Speed Control Accuracy: ±2%~±3%
制御モード: Standard V/F, Energy-saving Square V/F (for fans & パンプス), Multi-point V/F curve
- 機械式 & Environmental Specifications
- Enclosure Rating: NEMA1 wall-mounted closed cabinet
- 全体の重量: 約. 170kg
- 動作周囲温度: 0℃~+40℃ (40℃以上ではディレーティングが必要)
- 湿度: ≤80%RH, 結露なし
- 高度: No derating below 1000m; derate 1% per additional 100m above 1000m
- 冷却方法: Built-in high-power cooling fan (individually replaceable)
- Braking Mode: Built-in DC dynamic braking; external braking unit/resistor required for high-power regenerative energy
- Hardware Interface Configuration
4.1 主回路端子 (R/S/T Input; U/V/W Motor Terminals; +/ブレーキユニット; PE Earth)
R, S, T: 3-phase 380~480V power input
U, V, W: Connection to 3-phase induction motor
+, -: External braking resistor / regenerative unit connection
PE: 保護アース (common ground for cabinet and main circuit)
4.2 Standard Control Circuit Configuration
デジタル入力: 8 チャンネル, switchable between NPN and PNP
Digital Relay Outputs: 2 常開接点 (fault signal, run status signal)
アナログ入力: 2 チャンネル (0~10V / 4~20mA frequency reference)
Analog Outputs: 2 チャンネル (monitor frequency, 現在, 電圧)
コミュニケーション: 標準 Modbus-RTU; optional Profibus & DeviceNet communication cards
Digital Operator: 5-line 16-character LCD, supports parameter upload, download and copy
- 典型的なアプリケーションシナリオ
The P7 series is designed specifically for square-torque loads. The high-power CIMR-P7U4160 model applies to:
- Large cooling water circulation pumps, municipal water supply booster pumps
- Factory centrifugal fans, ボイラー誘引通風機, main dust removal fans
- Central air-conditioning chiller units, large cooling tower water pumps
- マイニング & metallurgy dust exhaust fans, wastewater treatment aeration pumps
利点: Built-in energy-saving square torque curve, sleep function, multi-pump rotation switching, constant pressure PID control
- Discontinued Replacement Solution (P7 series fully discontinued)
Direct Drop-in Upgrade: Yaskawa P1000 Series
Equivalent replacement model: CIMR-PU4A0415ABA
- Fully matched power rating: 304A output, compatible with 160kW motors
- Full function coverage: Retains all fan & pump dedicated functions of P7 (マルチポンプ制御, PID, スリープモード)
- Highly compatible communication protocols, terminal logic and parameter sets, low renovation workload
- Merits: Higher energy efficiency, 内蔵EMCフィルター, enhanced fault diagnosis, abundant spare parts
Alternative General Heavy-Duty Option: A1000 Series
(Vector type, selected for heavy-duty or closed-loop control demands)
- 一般的な故障コード & Troubleshooting Matrix (Universal for P7 Series)
| 故障コード | 障害の説明 | 根本的な原因 | 是正措置 |
| OC/OC1/OC2/OC3 | Overcurrent during Accel / Decel / 一定速度 | Motor short circuit, cable earth fault, mechanical stall, overly short accel/decel time | Test motor insulation; extend accel/decel time; inspect mechanical jamming |
| GF | Output Ground Fault | Damaged insulation on U/V/W cables, motor winding breakdown to earth | Disconnect motor cables section by section and test insulation separately |
| UV | DC Bus Undervoltage | Mains phase loss, excessive voltage drop, poor contact of contactor | Measure three-phase voltage of R/S/T; fasten main circuit terminals |
| OV | DC Bus Overvoltage | Excessively fast deceleration, no braking resistor, high mains voltage | Lengthen deceleration time; install external braking unit |
| OL1 | モーターの過負荷 | Excessive load, long-time low-speed operation, incorrect motor current parameter | Verify rated motor current parameter E2-01; 負荷を減らす |
| OL2 | Inverter Overload | Sustained 150% 定格電流 1 分 | 負荷を軽減する, upgrade inverter size, lower carrier frequency |
| SPI | 入力位相損失 | Broken wire on one R/S/T phase, ヒューズが切れた | Inspect input circuit breaker, terminals and three-phase voltage balance |
| SPO | Output Phase Loss | Disconnection of one U/V/W phase, burnt single-phase motor contact | Tighten motor terminals; test cable continuity |
| OH1/OH2 | Overheat (ヒートシンク) | Dust-clogged air duct, damaged cooling fan, ambient temperature over 40℃ | Clean air filter; replace cooling fan; 通気性を改善する |
| LF | Output Three-Phase Imbalance | Damaged motor winding, loose wiring terminals | Measure three-phase output current; fasten all terminals |
- Strict Wiring & Installation Prohibitions
- Main power cables and control signal wires must be routed in separate cable trays with a minimum spacing of 30cm; long parallel laying is forbidden.
- Shielded motor cables are recommended; shield shall be grounded only at the control cabinet end.
- Main circuit copper busbars of high-power models shall be tinned and tightened with specified torque to avoid overheating and arcing.
- For multi-pump linked systems, AC contactors shall not be installed on the inverter output side for frequent switching.
- For sites with heavy dust and moisture, clean air duct filters regularly to prevent overheat alarms.
- If long motor cables (>50メートル) 必要です, an output du/dt filter must be installed to suppress peak voltage and protect motor insulation.
- Key Basic Commissioning Parameters (Standard for Fan & Pump Applications)
- E1-06 Base Frequency: Rated 50/60Hz as marked on motor nameplate
- E1-13 Square V/F (Fan Energy Saving): に設定します 2 to enable square torque curve
- b5 PID Pressure Closed-Loop: Set target pressure and P/I/D gains
- b5-17 Sleep Function: Low-frequency energy-saving sleep, auto-stop during idle periods
- C1-01~C1-04 Accel & Decel Time: ≥15s recommended for pumps, ≥30s for fans to avoid overcurrent
- E2-01 Motor Rated Current: Enter value per motor nameplate, baseline for overload protection
Complete Model List of Yaskawa Varispeed P7 Series (CIMR-P7U□4□□□) 400Vシリーズ
注意事項
- Series Naming Rule: `CIMR-P7U4XXX0`. The full code printed on the nameplate ends with digit 0, which is omitted as the short model number for selection (例えば, CIMR-P7U4160).
- U = Dedicated 3-phase 380~480V model for fans and pumps; ND Normal Duty (square-torque loads for fans & パンプス).
- Power correspondence unit: kW / HP / 定格出力電流 (あ).
- The entire series adopts V/F control, built-in square torque curve and PID multi-pump control. This series has been fully discontinued, with replacement models CIMR-PU4A□□□□ (P1000 series).
- 低い & Medium Power Range (7.5kW ~ 132kW)
| Full Model No. | Matching Motor Power | 定格出力電流 (あ) |
| CIMR-P7U40070 | 7.5kW / 10HP | 18 |
| CIMR-P7U40110 | 11kW / 15HP | 24 |
| CIMR-P7U40150 | 15kW / 20HP | 30 |
| CIMR-P7U40180 | 18.5kW / 25HP | 37 |
| CIMR-P7U40220 | 22kW / 30HP | 43 |
| CIMR-P7U40300 | 30kW / 40HP | 57 |
| CIMR-P7U40370 | 37kW / 50HP | 69 |
| CIMR-P7U40450 | 45kW / 60HP | 83 |
| CIMR-P7U40550 | 55kW / 75HP | 106 |
| CIMR-P7U40750 | 75kW / 100HP | 130 |
| CIMR-P7U40900 | 90kW / 125HP | 160 |
| CIMR-P7U41100 | 110kW / 150HP | 192 |
| CIMR-P7U41320 | 132kW / 175HP | 232 |
- High Power Range (160kW ~ 400kW, including CIMR-P7U4160 you inquired)
| Full Model No. | Matching Motor Power | 定格出力電流 (あ) |
| CIMR-P7U41600 | 160kW / 250HP | 304 |
| CIMR-P7U42000 | 200kW / 300HP | 370 |
| CIMR-P7U42200 | 220kW / 330HP | 415 |
| CIMR-P7U42500 | 250kW / 375HP | 460 |
| CIMR-P7U43150 | 315kW / 450HP | 580 |
| CIMR-P7U43750 | 375kW / 500HP | 690 |
| CIMR-P7U44000 | 400kW / 540HP | 730 |
Supplementary Key Remarks
- 200V single/3-phase P7 models (P7E / P72 series) are excluded from the above table. This list only covers mainstream industrial 400V 3-phase fan & pump models P7U.
- Model Abbreviation Rule: The trailing digit 0 is often omitted in engineering drawings and procurement documents. 例えば, CIMR-P7U41600 is abbreviated as CIMR-P7U4160.
- Cabinet Classification: Models ≤132kW adopt standard wall-mounted cabinets; models ≥160kW (4160 and above) are large floor-standing cabinets equipped with independent high-power cooling fans.
- Distinction of output versions at the same power rating:
Standard built-in braking transistor; high-power models 4160 and above require an external braking unit + braking resistor to implement dynamic braking during deceleration.
- Discontinued Model Replacement Mapping (P7U4XXXX → P1000 PU4AXXXX)
CIMR-P7U41600 (160kW) → CIMR-PU4A0415ABA
CIMR-P7U42000 (200kW) → CIMR-PU4A0475ABA
CIMR-P7U42500 (250kW) → CIMR-PU4A0605ABA
コンタクタ,サーキットブレーカー,ソーラーインバーター,電気メーター,太陽電池