GEFRAN 40T-48-4-00-RR 가능-0-0-0-0 40T-48-4-00-RR로 교체-0-0-1?

GEFRAN 40T-48-4-00-RR 가능-0-0-0-0 40T-48-4-00-RR로 교체-0-0-1?

결론: Direct replacement is feasible. The hardware, wiring and core functions are fully compatible. The only difference lies in the software and compliance version indicated by the last digit, which will not affect normal operation. Below is the breakdown of model codes, differences and replacement guidelines.

  1. Digit-by-Digit Model Code Comparison (Only the last digit differs)

40T-48-4-00-RR-0-0-0-0 (부품 번호. F000187) vs 40T-48-4-00-RR-0-0-0-1 (부품 번호. F000188)

  1. 40티: 시리즈 (40T48 48×48 mm Indicator / Alarm Unit)
  2. 48: Panel dimension: 48×48 mm (1/16 에서)
  3. 4: 4-digit LED display
  4. 00: 전원공급장치: 100…240 V AC/DC
  5. RR: 산출 1 & 산출 2: Dual relays (5에이 / 250 뷔와)
  6. 0: 3rd output / 디지털 입력 / Transmitter output: 없음
  7. 0: 통신 인터페이스 / 4th output: 없음
  8. 0: Reserved bit
  9. Last digit: 0 = Legacy software / 기본 버전; 1 = Updated software / Compliance certified version (CE, UL, 등.)
  10. 주요 차이점

Identical hardware: Terminal layout, 장착 치수, power supply range, relay contact specifications and input types (Universal input: TC/RTD/Linear signal) are exactly the same. No wiring modification required.

Identical functions: Both support 3 alarm points, on-panel/software programming and parameter password protection. The only distinction is the firmware version and compliance certification. The version ending with 1 is the updated fully compatible firmware.

Part Numbers: Model ending with 0 = F000187; Model ending with 1 = F000188.

  1. 교체 권장사항 & 메모
  2. ✅ Direct replacement: Fully compatible in terms of installation, wiring and terminal definition. No rewiring needed.
  3. ⚠️ Mandatory operation: Reconfigure parameters (입력 유형, measuring range, alarm threshold, differential gap, 등.) after replacement. The new firmware is fully compatible with legacy parameter logic.
  4. Special scenario: If the original equipment requires traceability of special compliance certifications (예를 들어. matching UL/CE documents), verify whether strict model consistency is required on site. For general functional use, no issues will occur.

Quick Reference for Replacement: GEFRAN 40T-48-4-00-RR-0-0-0-0 / 40T-48-4-00-RR-0-0-1

  1. Full Model Code Explanation (Only the last digit differs)
코드 세그먼트콘텐츠설명Consistency Between Two Models
140티제품 시리즈: 40T Digital Alarm Controller완전히 동일함
248Panel Size: 48×48 mm (1/16 DIN Standard)완전히 동일함
34표시하다: 4-digit LED Digital Tube완전히 동일함
40전원공급장치: Wide voltage 100~240 V AC/DC완전히 동일함
5RR출력 구성: Two independent relay alarm outputs완전히 동일함
603rd output / 디지털 입력 / Transmitter output: 없음완전히 동일함
70통신 포트 / 4th output: 없음완전히 동일함
80Hardware reserved bit: Disabled reserved functions완전히 동일함
90 / 1Firmware & Compliance Version:Only difference
0 = Basic firmware
1 = Updated firmware (CE/UL 인증)

> 핵심 결론: 100% compatibility in hardware structure, electrical specifications, terminals and functional pins. Direct replacement is supported.

  1. 일반 기술 사양 (Identical for both models)
사양
장착 치수48×48 mm panel, standard DIN cutout
Operating Power100 ~ 240 V AC/DC, Power consumption < 3 버지니아
Measuring Input유니버셜 타입: 열전대 (K/J/S/T), Pt100 RTD, linear voltage/current analog signal
Display Accuracy±0.2% FS, Sampling rate: 10 초당 횟수
릴레이 출력 (RR)2-channel passive normally open contacts, 접점등급: 5에이 / 250 뷔와
작동 온도0 ~ +50 ℃
유입 방지전면 패널: IP65; Terminal side: IP20
유전 강도내전압 2000 V AC between input, output and power supply
  1. Terminal Pin Definition (Universal for on-site wiring, no rewiring)

Standard terminal block on the rear of the device, 총 8 터미널. Terminal layout and functions are fully identical for both models.

터미널 번호.기능Wiring Instruction비고
1Power L / +AC Live / DC Positive전원 입력
2Power N / –AC Neutral / DC Negative전원 입력
3Measuring Input +Sensor signal positiveConnect to thermocouple/RTD/analog output
4Measuring InputSensor signal negativeCommon end of signal loop
5Alarm Relay 1 연락 없음1st alarm outputCorresponds to the 1st alarm logic
6Alarm Relay 1 흔한Common terminal of Relay 1Passive contact, non-polar
7Alarm Relay 2 연락 없음2nd alarm outputCorresponds to the 2nd alarm logic
8Alarm Relay 2 흔한Common terminal of Relay 2Passive contact, non-polar

Supplement: This model has no transmitter output or communication port, and all terminals are fully utilized. Wire strictly in accordance with the above table.

  1. Panel Keys & Step-by-Step Parameter Configuration (Mandatory after replacement)

주요 설명

`SET`: Enter menu / Confirm parameter / Switch menu level

`▲/▼`: Adjust value / Switch options

`◀`: Shift digit / Return to previous menu

Complete Configuration Steps (General for field application)

단계 1: Enter Programming Mode

Press and hold `SET` for 3 seconds to enter parameter setting interface. For some units, enter the factory default password 0000 and press `SET` to confirm.

단계 2: Set Input Signal Type (Core setting)

  1. Locate parameter `In.Ty` (입력 유형)
  2. Use `▲/▼` to select the sensor type:

`K`: K-type Thermocouple

`Pt`: Pt100 RTD

`0-10`: 0-10V Analog Signal

`4-20`: 4-20mA Analog Signal

  1. Press `SET` to save and proceed to the next item.

단계 3: Set Measuring Range

  1. `Lo`: Set Lower range limit
  2. `Hi`: Set Upper range limit
  3. Adjust according to actual process range, then press `SET` to confirm.

단계 4: Configure Dual Alarm Relays (Corresponding to RR outputs)

  1. `AL1`: 1st alarm value (for Relay on Terminal 5/6)
  2. `dF1`: Differential gap of 1st alarm (to prevent frequent relay switching, 권장값: 0.5~2.0)
  3. `AL2`: 2nd alarm value (for Relay on Terminal 7/8)
  4. `dF2`: Differential gap of 2nd alarm
  5. Select alarm mode: High limit alarm / Low limit alarm as required.

단계 5: 매개변수 저장 & 출구

After all settings are completed, press `◀` repeatedly to return to the main interface. Parameters will be saved automatically.

To lock parameters against accidental modification: Locate `P.cod` and set a custom password.

  1. On-site Check List after Replacement (Check item by item to avoid faults)

Pre-power-on Inspection

  1. Mechanical mounting: Secure the instrument on the panel without looseness; cutout size complies with 48×48 mm.
  2. 배선 점검: Verify power, sensor and relay circuits per terminal table; ensure no loose connection, wrong wiring or short circuit.
  3. Power confirmation: On-site power supply is 100~240 V AC/DC within rated range.

Post-power-on Inspection

  1. Power-on test: 4-digit LED lights up normally, no black screen or flickering.
  2. Signal verification: Compare real-time reading with actual sensor value; ensure deviation is within allowable range.
  3. Alarm test: Simulate over-limit conditions manually; confirm two relays actuate/de-energize normally and external loads work properly.
  4. Parameter recheck: Keep range, alarm values and differential gap consistent with original settings.

Compliance Check (Execute as required)

General industrial sites / No certification traceability required: No extra operation needed.

장비 수출 / Strict model & certificate consistency required: The new model ending with 1 is the certified version with complete CE/UL documents for filing.

  1. 일반적인 결함 & Troubleshooting after Replacement
결함 현상가능한 원인솔루션
No display after power-on1. Reversed/loose power wiring단자를 다시 조이세요, measure input voltage and restore rated power supply
2. Supply voltage out of range
Fluctuating / Inaccurate readings1. Poor sensor connectionReconnect sensor cables and verify In.Ty parameter
2. Wrong input type selected
Normal reading but relay no action1. Incorrect alarm valueRecheck AL1/AL2 thresholds and switch alarm mode
2. Wrong alarm mode selected
Relay switches frequentlyExcessively small differential gapIncrease dF1/dF2 value
Parameters reset automaticallyFailed to exit menu completely / Stuck panel keysFully exit setting interface and clean foreign matters on keys
  1. 보충 노트
  2. Firmware compatibility: The updated firmware (ending with 1) is fully backward compatible with legacy parameter logic, with no function reduction or protocol mismatch.
  3. Spare parts procurement: Both models are interchangeable for reordering. The updated version ending with 1 is recommended for wider certification coverage.
  4. Long-term operation: The two models have identical service life and load capacity, and require no differentiated maintenance standards.