위챗: +86-13184948252 왓츠앱: 0086-13811255435 이메일: kent@bestcontactor.com

에 대한 연락하다 |

 INVT-CHF100A-055G-075P-4 Frequency Converter Selection Quick Reference Table - 접촉기,회로 차단기,태양광 인버터,전기 계량기,태양 전지

소식무역 뉴스

INVT-CHF100A-055G-075P-4 Frequency Converter Selection Quick Reference Table

INVT-CHF100A-055G-075P-4 Frequency Converter Selection Quick Reference Table

ModuleDetails
Basic InformationBrand: INVT
Series: CHF100A Vector General-Purpose Type
Model Definition: 055G = 55kW Standard Load / 075P = 75kW Heavy Load
Voltage Class: Three-phase 380-415V AC (50/60헤르츠)
Protection Rating: IP20 (Cabinet Installation)
Cooling Method: Forced Air Cooling
Core Electrical ParametersRated Input Voltage: 380-415뷔와 (Fluctuation ±15%)
Rated Output Power: 55kW (Standard) / 75kW (Heavy Load)
Rated Output Current: 105에이 (Standard) / 135에이 (Heavy Load)
Output Frequency Range: 0.00-600.00헤르츠 (Accuracy ±0.01Hz)
Control Mode: Sensorless Vector Control (SVC), V/F Control, Torque Control
Overload Capacity: 150% for 1min (Standard); 120% for 1min (Heavy Load)
Terminal Definitions▶ Main Circuit Terminals
R/L1, S/L2, T/L3: Three-phase Power Input
U, 다섯, 여: Frequency Converter Output (Connected to Motor)
PE: Grounding Terminal
▶ Control Circuit Terminals
DI1-DI9: Digital Input (Configurable for Multi-speed, Start/Stop, 등.)
DO1-DO6: Digital Output (잘못, Running Signal, 등.)
AI1/AI2: Analog Input (0-10V/4-20mA)
AO1/AO2: Analog Output
RS485: Communication Interface (모드버스 RTU)
Applicable Motor PowerStandard Load (Type G): Suitable for 55kW Three-phase Asynchronous Motor
Heavy Load (Type P): Suitable for 75kW Three-phase Asynchronous Motor
Starting Torque: 0.5헤르츠 / 150% Rated Torque (SVC Mode)
일반적인 애플리케이션 시나리오1. Fans & Pumps: Boiler Induced Draft Fans, Central Air Conditioning Water Pumps, Cooling Tower Fans
2. Industrial Machinery: Air Compressors, Injection Molding Machines, Printing & Packaging Equipment
3. Building Materials & Metallurgy: Belt Conveyors, Ball Mill Auxiliary Systems
4. Others: Mining Machinery, Sewage Treatment Equipment
Key Selection Tips1. 부하 매칭: Select Type G parameters for fans/pumps; select Type P parameters for compressors/extruders
2. Environmental Derating: For every 1℃ rise above 40℃, reduce rated current by 1%, maximum operating temperature 50℃
3. Recommended Accessories: Input Reactors (Harmonic Suppression), Braking Units (High-inertia Loads), Extended Operation Panels
4. Communication Expansion: Supports PROFIBUS-DP / DeviceNet Fieldbuses

이전:

다음:

답장을 남겨주세요

메시지를 남겨주세요