위챗: +86-13184948252 왓츠앱: 0086-13811255435 이메일: kent@bestcontactor.com

에 대한 연락하다 |

ABB Power Factor Controller 2GCA294985A0050 - 접촉기,회로 차단기,태양광 인버터,전기 계량기,태양 전지

전기 계량기/전기 같은/

ABB Power Factor Controller 2GCA294985A0050

The model 2GCA294985A0050 is not a display screen, but rather an ABB RVC-8 Power Factor Controller (also known as a Reactive Power Compensation Controller). It is used to automatically control the switching of capacitor banks, optimize the power factor of the power grid, and reduce energy consumption and electricity penalty charges due to poor power ...

  • 제품 세부정보

The model 2GCA294985A0050 is not a display screen, but rather an ABB RVC-8 Power Factor Controller (also known as a Reactive Power Compensation Controller). It is used to automatically control the switching of capacitor banks, optimize the power factor of the power grid, and reduce energy consumption and electricity penalty charges due to poor power factor.

  1. Core Product Information
상세사양
모델RVC-8 (2GCA294985A0050), Old Order No.: 10148029
제품 유형8-output Power Factor Controller
Voltage Range100V~440V, suitable for most low-voltage power grids
Input Current1A or 5A (RMS), requires connection to a Current Transformer (CT)
Frequency RangeAuto-adapts to 50/60Hz
Display TypeBlack and white LCD display with functional icons
Control ModeFully automatic control, supporting multiple switching strategies such as Integral, Cyclic, and Direct
작동 온도-25°C~+70°C (ambient); Triggers an alarm if internal temperature exceeds 85°C
Power ConsumptionMax 8VA
Output Circuits8 programmable relay outputs, each rated at 16A/250VAC
  1. Core Functional Features
  2. Comprehensive Parameter Monitoring:

Measures and displays key grid parameters including voltage, 현재의, power factor, THDV (Total Harmonic Voltage Distortion), and THDI (Total Harmonic Current Distortion).

  1. Flexible Control Strategies:

Fully programmable switching sequence supporting both共补 (Total Phase Compensation) and 分补 (Individual Phase Compensation).

Switching interval adjustable from 1 second to 999 초.

Target power factor adjustable from 0.7 (inductive) 에게 0.7 (capacitive).

Auto-adapts to grid phase sequence and CT terminal connection.

  1. 다중 보호 기능:

Over-voltage / Under-voltage protection.

Over-temperature protection (internal temperature > 85℃).

Excessive harmonic protection (THDV threshold超限).

Power-off memory function (maintains capacitor bank state for power off durations up to 40ms).

  1. User-friendly Interface:

Upgraded icon-based UI allows for quick commissioning without a manual. The compact design saves cabinet space.

  1. 응용 시나리오

Industrial Plants: Reactive power compensation for inductive loads such as inverters, 압축기, and motors.

Commercial Complexes: Reactive current compensation for devices like central air conditioners and elevators.

데이터 센터: Stabilize the power supply system and improve energy efficiency.

New Energy Power Stations: Optimize the reactive power output of photovoltaic inverters and wind turbine converters to improve grid connection efficiency.

공공시설: Power distribution systems for public buildings such as hospitals, schools, and subway stations.

  1. RVC Series Full Model Comparison
모델주문 번호.Number of Output CircuitsMain Features
RVC-32GCA294983A00503-circuitSuitable for small capacitor cabinets
RVC-62GCA294984A00506-circuitMedium-scale capacitor compensation system
RVC-82GCA294985A00508-circuitThis product; suitable for medium and large capacitor cabinets
RVC-102GCA294986A005010-circuitLarge-scale capacitor compensation system
RVC-122GCA294987A005012-circuitExtra-large scale capacitor compensation system
RVC-L-122TAZ460104R112012-circuitLong-life version, replacing the old RVC-12
RVT-L-182TAZ460103R018018-circuitDedicated to 3-phase individual compensation, 지원하다 18 output circuits
  1. Replacement Solutions
  2. ABB Original Factory Upgrade Replacements:

RVC-L Series: Long-life version, 예를 들어, RVC-L-12 (replaces RVC-12).

RVT Series: More advanced power factor controllers with support for more functions and communication protocols.

  1. Other Brand Replacements:

슈나이더: VPL06N/VPL12N series.

지멘스: 7KM series power factor controllers.

Domestic Replacements: Similar products from brands such as Chint and Delixi.

  1. Technical Documentation and Support
  2. 메모: The RVC-8 has been discontinued. It is recommended to prioritize upgrading to the RVC-L series or RVT series products for better performance and a longer service life.

Complete List of ABB Power Factor Controller Models and Comparison with Mainstream Brands

  1. Complete List of ABB Power Factor Controller Models
  2. RVC Series (Discontinued; recommended upgrade to the RVC-L series)
모델주문 번호. (New/Old)Number of OutputsCore Specifications응용 시나리오
RVC-32GCA294983A0050/101480273-circuit100-440뷔와, 1/5A CT, IP20Small capacitor cabinets, stable load systems
RVC-62GCA294984A0050/101480286-circuit100-440뷔와, 1/5A CT, IP20Medium compensation systems, 상업용 건물
RVC-82GCA294985A0050/101480298-circuit100-440뷔와, 1/5A CT, IP20Medium and large compensation systems, industrial plants
RVC-102GCA294986A0050/1014803010-circuit100-440뷔와, 1/5A CT, IP20Large compensation systems, data centers
RVC-122GCA294987A0050/1014803112-circuit100-440뷔와, 1/5A CT, IP20Extra-large compensation systems, new energy power stations

Core Features: Black and white LCD icon-based UI, supports Integral/Cyclic/Direct control, includes THDV/THDI monitoring, and features Over-voltage/Under-voltage/Harmonic/Over-temperature protection.

  1. RVC-L Series (RVC upgrade, long-life design)
모델주문 번호.Number of OutputsCore SpecificationsUpgrade Advantages
RVC-L-32TAZ460104R00303-circuit100-440뷔와, 1/5A CT, IP20Extended service life, optimized algorithms
RVC-L-62TAZ460104R00606-circuit100-440뷔와, 1/5A CT, IP20Extended service life, optimized algorithms
RVC-L-82TAZ460104R00808-circuit100-440뷔와, 1/5A CT, IP20Extended service life, optimized algorithms
RVC-L-102TAZ460104R010010-circuit100-440뷔와, 1/5A CT, IP20Extended service life, optimized algorithms
RVC-L-122TAZ460104R112012-circuit100-440뷔와, 1/5A CT, IP20Extended service life, optimized algorithms; most widely used

Core Features: Retains all RVC functionality with improved component quality, extended MTBF (Mean Time Between Failures), and greater stability and reliability.

  1. RVT Series (Advanced features, supporting individual phase compensation)
모델주문 번호.Number of OutputsCore Specifications핵심 기능
RVT-6100791826-circuit100-460뷔와, 1/5A CTIntegral/Cyclic/Direct control, individual/total phase compensation, harmonic monitoring
RVT-121007916112-circuit100-460뷔와, 1/5A CTIntegral/Cyclic/Direct control, individual/total phase compensation, harmonic monitoring
RVT-12-3PCustom12-circuit100-460뷔와, 1/5A CT3-phase independent measurement, energy calculation, support for all connection types

Core Features: More precise measurement, support for 3-phase unbalanced systems, independent measurement of each phase, suitable for complex load environments.

  1. RVT-L Series (Latest touchscreen series, most powerful features)
모델주문 번호.Number of OutputsControl Type핵심 장점
RVT-L-18 3P(N)2TAZ460103R018018-circuitContactor switching (passive)Touchscreen UI, 3-phase full parameter measurement, harmonic spectrum analysis
RVT-L-18 3P(T)Custom18-circuitThyristor switching (active DC12V)Dynamic compensation, fast response to impact loads
RVT-L-24 3P(N)Custom24-circuitContactor switching (passive)Maximum number of output circuits, suitable for extra-large systems
RVT-L-24 3P(T)Custom24-circuitThyristor switching (active DC12V)Dynamic compensation, maximum number of output circuits

Core Features: Color touchscreen, 18/24 output circuits, support for low/medium voltage applications, optional Modbus communication, suitable for high-end projects and smart grids.

  1. Comparison List of Mainstream Brand Power Factor Controllers (Categorized by Number of Output Circuits)
Number of Outputs씨줄슈나이더지멘스친트맛있는Main Feature Comparison
3-circuitRVC-L-3VPL03N7KM2111NWKL1-3JKL2B-3ABB/RVC-L: Harmonic monitoring; 슈나이더: 모듈형 디자인; 지멘스: Strong communication; 국내의: High cost-performance ratio
6-circuitRVC-L-6VPL06N7KM2112NWKL1-6JKL2B-6씨줄: Flexible switching strategies; 슈나이더: Plug-and-play; 지멘스: Strong diagnostic capabilities
8-circuitRVC-L-8VPL08N7KM2113ZT-830-8JKL5C-8씨줄: Integral/Cyclic/Direct 3 modes; 국내의: Significant cost advantage
12-circuitRVC-L-12VPL12N/NVPL12N7KM2114NWKL1-12JKL2C-12씨줄: Over-temperature protection; 슈나이더: 24V auxiliary power; 지멘스: Detailed fault records
18-circuitRVT-L-18NVPL18N/NVPL18T7KM2318ZT-830-18CustomABB/RVT-L: Touchscreen; 슈나이더: Contactor/Thyristor dual version; 지멘스: Advanced algorithms
24-circuitRVT-L-24NVPL24N/NVPL24T7KM2324CustomCustomABB/RVT-L: Harmonic spectrum; 슈나이더: Maximum number of circuits; 지멘스: Industrial network integration
  1. Comparison Table of Core Technical Characteristics by Brand
상표Representative Series핵심 장점Disadvantages응용 시나리오
씨줄RVC-L/RVT-LHigh measurement accuracy, comprehensive protection, strong harmonic analysis, 긴 서비스 수명Higher price, some models require customization산업 자동화, new energy, high-end commercial projects
슈나이더VPL/NVPL모듈형 디자인, plug-and-play, rich communication protocolsGeneral harmonic processing capabilityCommercial buildings, data centers, infrastructure
지멘스7KMPowerful diagnostic functions, excellent industrial network integration, advanced algorithmsComplex operation, steep learning curveHeavy industry, power systems, large factories
친트NWKL1/ZT-830High cost-performance ratio, simple operation, compatible with domestic power gridsFew high-end features, limited communication optionsSmall and medium enterprises, civil construction, renovation projects
맛있는JKL2B/JKL5C저렴한 가격, good reliability, comprehensive after-sales serviceLack of advanced algorithms, weak harmonic monitoringSmall factories, 상점, residential power distribution
  1. Selection Guidelines and Replacement Recommendations
  2. RVC Series Upgrade: Existing RVC users are recommended to directly upgrade to the corresponding RVC-L model to maintain compatibility of control logic and obtain a longer service life and more stable performance.
  3. Selection of Number of Circuits: Select the number of circuits based on 1.2 times the total reactive power of the system, and reserve 2-3 circuits for future load increases.
  4. Control Type Selection:

Stable Loads: Choose contactor switching (Type N) for low cost and long service life.

Impact Loads: Choose thyristor switching (Type T) for fast response and no inrush current.

  1. Harmonic Considerations: If the system THDV > 5%, it is recommended to select a model with harmonic protection functions (such as ABB RVT-L, Schneider NVPL), and use it in conjunction with reactors.
  2. Quick Reference Table of Technical Parameters (Universal for the entire series)
매개변수 카테고리Typical Value메모
작동 전압100-440뷔와 (RVC/RVC-L), 85-305뷔와 (RVT-L)Wide voltage range, compatible with global power grids
현재 입력1A or 5A CT (RMS)Requires connection to a Current Transformer
Frequency AdaptationAuto-adapts to 50/60HzNo manual setting required
Target Power FactorAdjustable from 0.7 (inductive) 에게 0.7 (capacitive)Meets requirements of different power grids
Switching IntervalAdjustable from 1 second to 999 초Independent of load changes
보호 기능Over-voltage/Under-voltage/Harmonic/Over-temperature/Power-off memoryComprehensive protection for capacitors and the power grid
설치 방법DIN rail installation (너비: standard 96mm)Saves cabinet space

이전:

답장을 남겨주세요

메시지를 남겨주세요