주문번호: 208281, Alias: XTCEXSBR11
포지셔닝: 측면 장착 보조자 contact module for high-power DILM/DILH series contactors (Moeller series)
✅ 모델 코드 설명
DILM820-X: Accessory for high-frame DILM power contactors
HI11: 1아니요 + 1NC (1 make, 1 break)
SI: Side Install (측면 장착; differentiated from SA & V variants)
✅ Key Contact Characteristics (비판적인)
Interlocked Mirror Contact, IEC를 준수 60947-5-1 Annex L and IEC 60947-4-1 Annex F
The NC contact is a mirror contact, designed for safety circuits, 연동, emergency stop feedback and PLC safety signal acquisition. It is NOT a late-break NC contact
연락처 구성: 1 평상시 열림 + 1 평상시 닫힘
종료: M3.5 screw terminals, 조임 토크: 1.2 Nm
기존열전류 Ith: 10 에이 (~에 60 ℃)
AC-15 control capacity:
230 다섯: 6 에이
400 다섯: 4 에이
500 다섯: 1.5 에이
정격절연전압 Ui: 690 다섯; 음: 6 kV; 과전압 카테고리 III, 오염도 3
전기 절연: Coil-to-auxiliary contacts and auxiliary-to-main contacts meet AC 440V isolation level
✅ Compatible Base Contactors (Only for this high-power frame)
DILM250 ~ DILM1000, DILH600 ~ DILH2600, DILDC300 ~ DILDC600 DC contactors
맥스. 1 module on each side (왼쪽 & 오른쪽), 최고 2 modules per contactor
✅ Dimensions & 무게
W15 mm × H77 mm × D77 mm, 순중량: 37 g
✅ Cross-Series Comparison (선택 가이드)
DILM820-XHI11-SI: Side mount, 나사 터미널, interlocked mirror contact (표준 모델, this part)
DILM820-XHI11V-SI: Side mount, vibration-resistant reinforced version
DILM820-XHI11-SA: Standard interlocked contact (non-mirror), not for safety EDM monitoring
✅ Certifications
CE, UL, CSA, CCC; compliant with railway standard EN 45545 and vibration standard IEC 61373. Suitable for cranes, 공기 압축기, 팬, high-power motor circuits, safety gate interlocks and inverter bypass feedback.
✅ Typical Applications
Safety interlock circuits, contactor status feedback to PLC, forward/reverse electrical interlocking, fault feedback, safety relay input signals.
This side-mounted IEC 60947-5-1 Annex L mirror contact module (1NO+1 mirror NC) is exclusively for DILM250~DILM1000 and DILH high-power contactors. It is mainly used in safety-related control circuits, high-power motor control and fault diagnosis feedback, and cannot be replaced by standard auxiliary contacts for safety validation.
- 안전 회로 (가장 일반적인, Mandatory for Safety Audits)
- EDM External Device Monitoring for Safety Relays
The mirror NC contact is wired into the EDM channel of the safety relay to monitor welding/sticking of the contactor main contacts. If the NC fails to reset after coil de-energization, the safety relay triggers a lockout. It meets ISO 13849 PLd/PLe and SIL2/3, which is the standard solution for 이튼 ESR, Pilz and Schneider XPS safety circuits.
- Safety Gate / Light Curtain Interlocking
The mirror NC verifies the true open state of the contactor after the safety gate is opened, preventing unexpected motor operation caused by welded main contacts.
- Emergency Stop State Verification
After E-stop cuts off the contactor coil, the mirror contact confirms the contactor is physically open, eliminating hidden risks from welded main contacts despite valid E-stop signals.
- High-Power Motor Control Circuits
- Hardware Electrical Interlock for Forward/Reverse Contactors (Preferred for Large Fans, Pumps and Hoists)
The mirror NC of each contactor is wired in series into the coil circuit of the opposing contactor, forming hardwired interlock to prevent simultaneous closure and phase-to-phase short circuit. For DILM high-power contactors, safety auditors will not approve ordinary auxiliary contacts for this interlock.
III. Performance Comparison Table
| 연락 유형 | Actuation Mechanism | Performance under Welded Main Contacts | 적용범위 |
| Standard NC Auxiliary Contact | Mechanically coupled only to the armature, no welding test certification | Follows armature position without standard validation | Indicator lights, ordinary PLC feedback; FORBIDDEN for EDM monitoring |
| DILM820-XHI11-SI Mirror NC | Rigid mechanical linkage + internal positive interlock, factory-tested for contact welding | NC remains open when main contacts are welded, maintaining safe contact gap | Safety relay EDM, safety interlocking, contact sticking diagnosis |
- 제한사항 (Derived from Mechanical Design)
- Only fits DILM250~DILM1000 / DILH high-power contactors; smaller frames do not match the mechanical stroke.
- Designed exclusively for control signals: Ith=10 A, AC-15 230V=6A; cannot carry main power loads.
- The mirror NC only detects welded closed main contacts. It cannot detect poor contact or increased contact resistance.
Full Model List for DILM820-XHI Series
오직 3 mass-produced variants: all side-mounted 1NO+1NC positive-interlock contacts; differences are mirror (SI) / 기준 (~에) and vibration-resistant (다섯) 버전.
- 모델 코딩 규칙
DILM820-XHI: Side auxiliary contact module for DILM/DILH high-power contactors (DILM250 ~ DILH2600)
11: 1아니요 + 1NC (1 make + 1 break)
에스: Side mounted
SI: Mirror Contact (IEC 60947-4-1 Annex F, approved for EDM welding monitoring)
~에: Standard positive interlock contact (IEC 60947-5-1 Annex L only; NOT allowed for safety relay EDM)
다섯: Vibration-resistant reinforced construction (철도, heavy vibrating equipment)
- Complete Product List
| 모델 | 주문 번호. | 연락처 구성 | 유형 | 핵심 애플리케이션 |
| DILM820-XHI11-SI | 208281 | 1아니요 + 1 mirror NC | Mirror contact (SI) | 안전 회로, EDM welding detection, forward/reverse hard interlock, PLC sticking alarm (your selected model)이튼 |
| DILM820-XHI11-SA | 208282 | 1아니요 + 1 standard NC | Standard positive interlock (~에) | Ordinary PLC feedback, pilot lights, basic electrical interlock; strictly prohibited for EDM safety monitoringfiles.kemp… |
| DILM820-XHI11V-SI | 208283 | 1아니요 + 1 mirror NC | Vibration-resistant mirror contact (V+SI) | 철도 차량, overhead cranes, mining machinery with heavy vibration; identical electrical performance to standard SI, with reinforced mechanical structurefiles.kemp… |
- Key Selection Distinction
(1) SI vs SA (가장 중요함)
SI: NC is a certified mirror contact. It stays open when main contacts are welded, satisfying ISO 13849 PLd / SIL2-3 and approved for safety relay EDM loops.
~에: Only mechanical positive interlock without welding test certification. Only for ordinary control; rejected by safety audits.
(2) V-SI Variant
Mechanically reinforced for higher shock & 진동 저항 (IEC 61373). Electrical specs are identical to standard SI. Used for hoisting, mining and railway rolling stock.
- Universal Installation Restrictions
설치: Only side-fit on DILM250~DILM1000 and all DILH series contactors.
수량: 맥스. 1 module per side, total maximum 2 modules per contactor.
평가: Ith=10 A, AC-15 230V=6A; strictly for control circuits only, no power loads.
- No Other Variants
No XHI22 (2아니요+2NC) version available.
No top-mount version; only side-mount (에스) 모델.
No spring-cage terminals; all models use M3.5 screw terminals.
- 브랜드 간 동등
Eaton DILM820-XHI11-SI ↔ Siemens 3RT1956-4G (mirror contact); Schneider LADN13C is only standard auxiliary contact and cannot replace the mirror type for safety EDM.
접촉기,회로 차단기,감지기,인코더,PLC,변환기