Comprehensive Analysis of Schneider C16F2TM160 회로 차단기
기본 매개변수
Product Type: ComPacT NSX160F Series Molded Case Circuit Breaker (MCCB)
Frame Current: 160에이 (Frame Rating)
Rated Voltage: 690뷔와 (Operating Voltage), 415뷔와 (Breaking Capacity Test Voltage)
Breaking Capacity: 18그만큼 (415뷔와, 50/60헤르츠) 메모: Different from the 36kA of 3-pole models
극 구성: 2P (2 Poles) 메모: Not 4 극
Trip Unit: TMD Thermal-Magnetic Type (Thermal Overload + Magnetic Short-Circuit Protection), Rated Current 160A
Applicable System: AC/DC (Universal for Alternating Current and Direct Current)
Detailed Model Coding
C16F2TM160:
C: ComPacT Series
16: Frame Current 160A
F: Breaking Capacity Class (F=18kA, corresponding to F=36kA for 3-pole models)
2: 극 구성 (2P)
TM: Trip Unit Type (TMD Thermal-Magnetic Type)
160: Rated Current 160A
Detailed Technical Parameters
| Parameter | 값 |
| 정격 절연 전압 | 800뷔와 |
| 전기적 수명 | 40,000 Operating Cycles (440뷔와) |
| 기계적 수명 | 100,000 Operating Cycles |
| Operating Temperature | -5℃ ~ +70℃ (Standard Type) |
| Protection Degree | IP20 (Front Side) |
| Mounting Method | Fixed Mounting |
| Compliant Standards | IEC 60947-2, IEC 60898-1 |
Core Features
1. Compact Design: Saves space in distribution cabinets and improves installation efficiency
2. Dual Protection: TMD thermal-magnetic trip unit provides overload and short-circuit protection
3. AC/DC Universality: Suitable for various power system environments
4. High Reliability: Robust structure with resistance to vibration and impact
5. Easy Maintenance: Front-panel operation for convenient inspection, repair and replacement
Characteristics of TMD Trip Unit
Thermal Protection: Bimetallic strip senses overload current, with inverse time-delay characteristic
Magnetic Protection: Electromagnetic coil detects short-circuit current, with instantaneous action
Fixed Protection Characteristics: Preset at the factory, no on-site adjustment required
No Communication Function: Only provides basic protection, without fault indication and remote monitoring capabilities
응용 시나리오
Commercial Buildings: Protection for single-phase 220V/240V power distribution systems such as lighting and air conditioning
Industrial Equipment: Power protection for single-phase motors and small production lines
Infrastructure: Single-phase power supply circuits in places like hospitals and schools
Residential Distribution Boxes: Branch protection for high-end residences (예를 들어, 에어컨, 온수기, 등.)
DC Systems: DC power protection for some industrial automation and communication equipment
Comparison with Other Models in the NSX160F Series
| 모델 | 극 구성 | Breaking Capacity (그만큼) | Trip Unit Type | 응용 시나리오 |
| C16F2TM160 | 2P | 18 | TMD | Single-phase system protection |
| C16F3TM160 | 3P | 36 | TMD | Three-phase system protection |
| C16F4TM160 | 4P | 36 | TMD | Three-phase four-wire system protection |
| C16F42D160 | 4P | 36 | Micrologic 2.2 | Systems requiring intelligent protection and communication functions |
지침
Discontinued and Obsolete: Together with the entire NSX160F Series, production was discontinued at the end of 2022, and service support was terminated at the end of 2023
Replacement Models: It is recommended to consider the latest upgraded products of Schneider’s NSX Series (예를 들어, NSX2 Series)
Purchasing Channels: Most products available on the market currently are stock items; please confirm the product status and quality assurance when purchasing
요약
Schneider C16F2TM160 is a 2-pole thermal-magnetic molded case circuit breaker with a breaking capacity of 18kA, specifically designed for single-phase or DC systems, and features a compact and reliable structure.
접촉기,회로 차단기,태양광 인버터,전기 계량기,태양 전지