Schneider Electric DC Molded Case Circuit Breakers - 접촉기,회로 차단기,태양광 인버터,전기 계량기,태양 전지

회로 차단기/

Schneider Electric DC Molded Case Circuit Breakers

SegmentCodeMeaning
Series IdentifierCComPacT Series
Frame Current63630A Frame Size
Breaking Capacity ClassSStandard Breaking Capacity (50그만큼)
Pole Number44-pole (3P3D/4P4D optional)
Trip UnitTMThermal-Magnetic Trip Unit
정격전류500500A Rated Current
DC IdentificationDDC-Specific

  • 제품 세부정보

A Comprehensive Analysis of Schneider Electric DC Molded Case Circuit Breakers (DC MCCB)

Schneider Electric DC molded case circuit breakers are specially designed for DC systems, providing current protection ranging from 16A to 4000A and covering voltage classes from 500Vdc to 1500Vdc. They are suitable for various DC application scenarios such as photovoltaic systems, data centers, rail transit, and energy storage systems. The core product series include three main lines: ComPacT NSX DC (including PV-specific DC PV/EP variants), EasyPact CVS DC and MasterPacT NW DC, which integrate high-reliability breaking capacity, flexible wiring options and intelligent protection capabilities.

  1. Overview of Core Product Series
Series정격전류Rated VoltageBreaking CapacityCore Features일반적인 응용 분야
NSX DC16-630에이750Vdc36-100그만큼Double rotary contacts, pole series/parallel connection, PV-specific designPV combiner boxes/inverters, data centers, energy storage systems
1000Vdc(PV)
1500Vdc(EP)
NSX DC PV100-630에이1000Vdc50-100그만큼Optimized for 1000Vdc, reverse polarity protection, isolation functionMain DC-side circuits of photovoltaic power plants
NSX DC EP100-630에이1500Vdc50그만큼High-voltage application for 1500Vdc, Icu=50kALarge-scale energy storage systems, high-voltage DC systems
CVS DC16-630에이500-1200Vdc25-85그만큼Double-break arc extinguishing, cost-effective and high-efficiencyIndustrial DC power distribution, charging piles, small-scale energy storage systems
MasterPacT NW DC1000-4000에이900Vdc85그만큼Micrologic intelligent trip unit, high-current ratingMain switches for DC power grids, large-scale industrial equipment
  1. Model Naming Convention Explanation (Taking NSX DC as an Example)

Taking the model C63S4TM500D as an example, the meaning of each segment is as follows:

SegmentCodeMeaning
Series IdentifierCComPacT Series
Frame Current63630A Frame Size
Breaking Capacity ClassSStandard Breaking Capacity (50그만큼)
Pole Number44-pole (3P3D/4P4D optional)
Trip UnitTMThermal-Magnetic Trip Unit
정격전류500500A Rated Current
DC IdentificationDDC-Specific

Other common codes:

F/H: Breaking capacity classes (F: 36그만큼, H: 70그만큼)

PV: Photovoltaic-Specific

EP: 1500Vdc High-Voltage Version

NA: Isolating Switch Type

III. Key Technical Parameters and Performance

  1. Rated Voltage and Breaking Capacity

Standard Type: 750Vdc, Icu = 36-100kA (depending on breaking capacity class)

PV Type: 1000Vdc, Icu = 50-100kA

High-Voltage Type: 1500Vdc, Icu = 50kA

High-Current Type: 900Vdc, Icu = 85kA (NW DC Series)

  1. Trip Unit Types

Thermal-Magnetic Trip (TM-DC): Overload long-time delay (adjustable from 0.7-1In) + short-circuit instantaneous protection, suitable for general-purpose power distribution.

Electronic Trip (Micrologic DC): Four-stage protection including long-time delay, short-time delay, instantaneous protection and earth fault protection, with precise adjustability, suitable for critical loads.

  1. Mounting and Wiring Methods

Mounting: Fixed/draw-out type, installed on 35mm DIN rail or front-panel mounting.

Wiring: Supports three DC-specific methods

Standard Wiring: Single-pole independent connection, suitable for ≤750Vdc.

Pole Series Connection: Enhances breaking capacity, suitable for high-voltage scenarios.

Pole Parallel Connection: Increases rated current, suitable for high-current scenarios.

Terminals: Compatible with copper/tinned copper cables of different wire gauges, with torque values varying by specification.

  1. Core Functions and Advantages
  2. DC Arc Extinguishing Technology

Double Rotary Contacts (NSX Series): Fast arc extinguishing, reduces arc energy, and improves breaking reliability.

Double-Break Arc Extinguishing (CVS Series): Enhances current-limiting capability and reduces thermal shock.

Dedicated Arc Chute: Adapted to the zero-crossing-free characteristic of DC current, improving arc extinguishing efficiency.

  1. Protection Features

과부하 보호: Inverse time characteristic, matched with the thermal curves of cables/equipment.

단락 보호: Instantaneous operation, with strong Icw short-time withstand capability.

절연 기능: Complies with EN/IEC 60947-2, ensuring maintenance safety.

PV-Specific Protection: Reverse polarity protection, adapted to the characteristics of photovoltaic arrays.

  1. Intelligent Features

Micrologic Trip Unit: Precise protection parameters, event logging, and communication functions (NW DC/high-end NSX models).

EcoStruxure Power Commission: Remote configuration, testing and maintenance.

Power Monitoring: Integrated measurement of parameters such as I/U/P/E/THD (high-end models).

  1. Application Scenarios and Selection Key Points
  2. 일반적인 애플리케이션 시나리오
Application FieldRecommended SeriesKey RequirementsSelection Key Points
Photovoltaic Power PlantsNSX DC PV/EP1000-1500Vdc, reverse polarity protection, isolationSelect rated current based on array capacity, considering 1.25 times overload margin
Data CentersNSX DC500-750Vdc, high reliability, communication capabilityChoose electronic trip units, equip with remote monitoring, and adopt redundant design
Energy Storage SystemsNSX DC EP/CVS DC800-1500Vdc, fast breakingSelect according to the series-parallel voltage of energy storage units, considering short-circuit current
Industrial DC SystemsCVS DC500-800Vdc, cost-effectiveSelect based on load current, ensure breaking capacity ≥ prospective short-circuit current
Rail TransitMasterPacT NW DC750Vdc, high currentChoose Micrologic trip units, adapted to frequent operation
  1. Core Selection Steps
  2. Determine System Parameters: 정격전압 (Ue), rated current (In), prospective short-circuit current (Isc).
  3. Select Product Series: Choose NSX/CVS/NW series according to voltage class and budget.
  4. Determine Breaking Capacity: Ensure Icu ≥ Isc, calculated based on the short-circuit current at the installation point.
  5. Select Trip Unit Type: Thermal-magnetic trip for general loads, electronic trip for critical loads.
  6. Pole Number and Wiring: 3P3D (three-phase DC) or 4P4D (including neutral wire), consider pole series connection for high-voltage scenarios.
  7. Accessory Configuration: 보조 접점, undervoltage release, 통신 모듈, 등.
  8. Installation and Operation Precautions
  9. 배선사양

DC systems must distinguish between positive and negative poles, reverse connection is strictly prohibited (except for PV-specific models).

Special insulation accessories must be used for pole series connection to ensure creepage distance.

Cable cross-section should be selected according to rated current and temperature rise requirements, with torque applied in accordance with manual specifications.

  1. Operation and Maintenance

Mechanical and electrical tests must be performed before initial use.

Regularly inspect the arc chute, contact wear and wiring tightness.

Wait for capacitor discharge after power-off of DC systems before conducting maintenance.

  1. 안전 경고

DC arcs are not easy to extinguish, switching isolating switches under load is strictly prohibited.

Insulated tools and protective equipment must be equipped for high-voltage DC systems.

Interchangeable use with AC circuit breakers is not allowed, even if parameters are similar.

Ⅶ. Series Comparison Overview

Comparison ItemNSX DCCVS DCMasterPacT NW DC
정격전류16-630에이16-630에이1000-4000에이
Maximum Voltage1500Vdc1200Vdc900Vdc
Breaking Capacity36-100그만큼25-85그만큼85그만큼
Price RangeMedium-High중간높은
Intelligence Level높은 (Micrologic optional)중간 (basic intelligence)Very High (full-function Micrologic)
적용 가능한 시나리오High-end PV/energy storage/data centersGeneral industrial applications/charging pilesLarge-scale DC power grids/main industrial switches

With four core advantages including full-series coverage, high-reliability arc extinguishing, flexible wiring and intelligent protection, Schneider Electric DC molded case circuit breakers have become the preferred solution for DC system protection. During selection, three key factors including voltage class, breaking capacity and trip unit type should be focused on, and the appropriate series should be selected according to application scenarios. It is recommended to refer to Schneider Electric’s official selection manual or consult technical support to ensure optimal protection effect and system compatibility.