Siemens 3TX4001-2A 보조 접점 블록

This legacy Siemens SIRIUS front-mounted auxiliary contact features 1 평상시 닫힘 (NC) 연락하다, compatible with 3TF3 / 3TF4 contactors. Original production discontinued on Oct 01, 2021 with no identical OEM replacement. Recommended drop-in alternative: domestic compatible 3TY7561-1AA00, or upgrade to 3RH2911-1AA01 for 3RT6 series contactors. Model Code Breakdown Code Segment Definition 3TX Base designation for ...

  • 제품 세부정보

This legacy Siemens SIRIUS front-mounted auxiliary contact features 1 평상시 닫힘 (NC) 연락하다, compatible with 3TF3 / 3TF4 contactors. Original production discontinued on Oct 01, 2021 with no identical OEM replacement. Recommended drop-in alternative: domestic compatible 3TY7561-1AA00, or upgrade to 3RH2911-1AA01 for 3RT6 series contactors.

  1. 모델 코드 분석
코드 세그먼트정의
3TXBase designation for Siemens SIRIUS snap-on front auxiliary contact blocks
4001Contact configuration code: 1NC (single normally closed); 4010 = 1NO (single normally open)
-2에이설치 & terminal specs: front snap-in installation, no contact status indicator window, captive screw clamp terminals (exclusively designed for 3TF3/3TF4 contactors)
상태Discontinued from Oct 01, 2021; OEM note: Product was deleted without replacement
  1. 핵심 전기 사양
비고
연락처 구성1NC, positively drivenDesigned for safety circuit compliance
기존 열 전류 (이)10 에이Rated continuous operating current
AC-15 Breaking Capacity5.6 에이 @ 230 VACBreaking capacity for control circuits
3.6 에이 @ 400 VAC
2.2 에이 @ 690 VAC
정격 절연 전압 (우이)690 다섯Maximum permissible operating voltage
임펄스 내전압6 kVElectrical isolation safety rating
기계적 내구성10 백만 개의 작업Far exceeds service life of base contactor
전기적 내구성1 백만 개의 작업 (AC-15 duty)Under rated cyclic load
TerminationCaptive clamping screwsFor solid conductors: 0.75~2.5 mm²
유입 방지IP20손가락 안전 & 방진
작동 온도-25℃ ~ +55℃저장: -55℃ ~ +80℃
규정 준수 표준IEC60947-5-1, GB14048.5CE & RoHS certified
  1. Full Same-housing Model List (3TX4 Series)
주문 코드Contact Layout장착 스타일Matching Contactor상태
3TX4001-2A1NCFront snap-on3TF30~3TF34 / 3TF40~3TF45단종
3TX4010-2A1아니요Front snap-on위와 동일단종
3TX3001-2A1NCSide-mountedLegacy 3TB contactors단종
3TX3010-2A1아니요Side-mounted위와 동일단종
3TX4002-2A2NCFront snap-onHigh-current 3TF range단종
3TX4012-2A1아니요+1NCFront snap-on위와 동일단종
  1. Full Compatible Contactor List (Exclusive for Front Snap Fit)

Only applicable to below 3TF series, incompatible with newer 3RT / 3RV ranges:

3TF30: 3TF3000~3TF3090 (9A~12A)

3TF31: 3TF3100~3TF3190 (12A~16A)

3TF32: 3TF3200~3TF3290 (16A~25A)

3TF33: 3TF3300~3TF3390 (25A~32A)

3TF34: 3TF3400~3TF3490 (32A~40A)

3TF40~45: 3TF4000~3TF4590 (40A~95A)

> 메모: One contactor can mount 1 front block + 2 side auxiliary blocks simultaneously, max expansion up to 6 보조 접점 (3NO +3NC).

  1. Replacement Selection Guide for Obsolete Item

5.1 Direct Drop-in Replacement (No Contactor Modification)

Replacement PN상표연락하다호환성장점
3TY7561-1AA00Siemens domestic alternative1NCIdentical snap dimension플러그 앤 플레이, 비용 효율적
3TX4001-2BLegacy Siemens1NCSame function with indicator lampObsolete stock only, 높은 비용
LC1-D Auxiliary Contact슈나이더 일렉트릭1NCRequires adapter bracketEstablished brand, 안정적인 성능

5.2 Full Unit Upgrade (3TF → 3RT6)

업그레이드 옵션New ContactorMatching Auxiliary Contact장점애플리케이션
표준 업그레이드3RT6026~3RT60363RH2911-1AA01 (1NC)긴 서비스 수명, 지능형 모니터링New construction & equipment retrofit
기능 확장3RT6040~3RT60563RH2911-1AA01 + 3RH2911-1BA01Multi-contact combinationComplex control circuits
  1. 응용 환경 & 산업용 케이스

✅ Approved Application Scenarios

  1. Motor Control Circuits: Fault feedback & star-delta interlock for 3TF contactors of fans & 물 펌프
  2. PLC Interface: NC contact feeds contactor open/closed status into PLC digital input modules
  3. Safety Interlock: 비상 정지 & access door protection; NC forced opening cuts control supply (EN 준수 60204-1)
  4. 상태 표시: Pilot lamp power switching; NC opens to turn off indicator when contactor energizes

❌ Forbidden Applications

  1. Direct main-circuit loading: Designed exclusively for control loops (코일, pilot lamps, PLC signals); never connect to power main circuit
  2. Harsh ambient: Avoid >60℃, 심한 먼지, corrosive chemical & non-enclosed cabinets (accelerates contact oxidation)
  3. High-frequency cycling: >10 사이클/분; use solid-state relays instead
  4. DC heavy-load circuits: AC-15 rating invalid for DC-13 duty; select dedicated DC auxiliary contacts

Industrial Application Cases

산업애플리케이션Contact Function
공조AC compressor contactorFault stop signal to building automation system
수처리Water pump motor controlOverload interlock with main contactor
일반 기계Conveyor controlEmergency stop cut-off for safe shutdown
배전Backup power transferContactor status monitoring to prevent faulty switching
  1. 일반적인 오류 문제 해결
잘못근본 원인Remedy
Open circuit / 접촉 불량1. Contact oxidation under humid condition1. Replace with compatible 3TY7561
2. 느슨한 배선2. 단자 나사를 다시 조이세요
Contactor pulls in but NC fails to open1. Loose & fallen snap clip1. Reinstall and lock into position
2. Mechanical blockage inside block2. Replace block; inspect deformed contactor shaft
Contact arcing & 탈진1. Exceeding AC-15 rated current1. Add intermediate relay for load expansion
2. High inductive surge from load2. Fit RC snubber circuit for surge suppression
Abnormal overheating1. High contact resistance at terminals1. Clean terminals & re-terminate
2. Excessive ambient temperature2. Improve ventilation or use high-temperature variant
  1. Quick Selection Mnemonic

4001 = NC, 4010 = 아니오; front snap exclusively for 3TF;<br>Obsolete → swap to 3TY; upgrade to 3RT with 3RH;<br>Only for control circuit, never main power, excellent for safety interlock!

  1. HS코드 & 항공 운송 규정 준수

HS코드: 85365000 (Electrical switching apparatus for circuit protection)

Air Transport Classification: 위험하지 않은 물품, purely mechanical contacts with no lithium battery/supercapacitor, compliant with IATA DGR

CE 인증: Complies with Low Voltage Directive 2014/35/EU; Certificate of Conformity available upon request

Application Scope of 3TX4001-2A (Front-mounted 1NC Auxiliary Contact)

제품특징: Snap-on external 1NC contact for 3TF3/3TF4 contactors, rated AC-15, dedicated for secondary control circuit only, NOT permitted in main power circuit.

  1. Standard Common Applications

1.1 Motor Start-Stop Control (팬, 워터 펌프, Air Compressors)

  1. Passive running status feedback

Contactor coil energizes → NC opens, sends closing/running feedback signal to PLC DI module; coil de-energizes → NC resets closed to transmit stop signal.

Typical usage: Chilled water pumps, cooling blowers, 순환 펌프, central air-conditioning units.

  1. Electrical interlock protection

Mutual NC interlock between two contactors (forward/reverse or star-delta) to avoid simultaneous closing and phase short-circuit.

예: Star-delta motor starter interlock between star & delta contactors.

1.2 공작 기계 & 자동화 장비 (Lathe, 컨베이어, Injection Molding Machine)

  1. Cabinet door interlock: NC of main contactor wired into safety loop; if contactor is welded closed, NC stays open to block equipment restart.
  2. Conveyor sequential interlock: Interlock between upstream & downstream conveyor contactors to prevent mechanical collision from misoperation.
  3. Fault alarm: Normally closed NC in series with fault indicator lamp; lamp lights at standby/shutdown and goes off when contactor pulls in.

1.3 HVAC Industry (Central AC, Fresh Air Unit, Smoke Exhaust Fan)

  1. BA system signal collection: Fan contactor NC feeds start/stop remote data to building management controller.
  2. Fire smoke exhaust interlock: NC links with fire damper; damper shutdown cuts fan control circuit.

1.4 수처리 장비 (Dosing Pump, Sewage Pump, Aeration Blower)

  1. Pump overload linkage: Thermal relay trip resets contactor, closed NC triggers audible-visual fault alarm.
  2. Duty/standby pump auto-switch: Main pump fault closes NC to activate backup pump automatically.

1.5 LV Power Distribution Panels

  1. Capacitor compensation cabinet: NC of switching contactor feeds capacitor switching status to reactive power regulator.
  2. ATS cabinet: Electrical interlock between normal & backup supply contactors to eliminate cross-source short-circuit risk.

1.6 게양 & Elevator Auxiliary Control

Brake contactor NC of overhead crane feeds brake open/closed feedback; also for cooling fan contactor status monitoring on elevators.

  1. Safety Circuit Exclusive Usage (Positively Driven Contact per Machinery Safety Standards)
  2. Emergency stop monitoring: Detects welded contactor fault; mechanically stuck contactor keeps NC open to lock control power off.
  3. Safety guard circuit: Equipment door opening de-energizes main contactor, closed NC locks startup circuit.
  4. Low-power Indicator & Small Relay Driving
  5. Standby pilot lamp: NC closed to light indicator at idle; NC opens to turn lamp off during equipment operation.
  6. Mini intermediate relay drive: NC switching controls relay coil to amplify load capacity.
  7. Prohibited Application List
  8. ❌ Never connect to 220V/380V main power loop; AC-15 rating only for control loads, cannot directly drive motor/heater high-power loads.
  9. ❌ Avoid >55℃, strong acid/alkali corrosion & unprotected open-air cabinets (accelerates contact oxidation & bad conduction).
  10. ❌ Unsuitable for heavy DC loads (no DC-13 rating; DC breaking easily causes arc burnout).
  11. ❌ Ban over 15 switching cycles per minute (fast mechanical wear; replace with solid-state relay).