Schneider A9Q41225

A9F18325-IC65N-3P-C25A 슈나이더 회로 차단기

A9F18325-IC65N-3P-C25A 슈나이더 회로 차단기

QuickVigi iC60 Residual Current Add-on Module

Overview of Key Specifications

A9Q41225 is a QuickVigi iC60 residual current add-on module (RCD add-on device) from Schneider Electric’s Acti9 range, specially designed for iC60 miniature circuit breakers (MCB), providing 2P 25A 30mA Type AC earth leakage protection.

사양
제품 유형QuickVigi iC60 Residual Current Add-on Module
극 수2피 (Two-wire system)
정격전류 (~ 안에)25에이
정격 잔류 작동 전류 (나)30엄마 (Personal safety level)
Residual Current TypeAC형 (Detects sinusoidal AC residual current)
치수1.5 모듈 (27mm 폭), 91mm height, 73.5mm depth
설치DIN 레일 장착
보호 정도IP20
작동 전압230/240뷔와
빈도50/60헤르츠
Trip IndicationLocal mechanical indicator (red)
Applicable StandardsIEC 61009-1

Product Features & 기능

  1. Plug-and-play design: Installs quickly onto iC60 MCBs without extra wiring
  2. Voltage-independent technology: Ensures reliable operation even with voltage fluctuations
  3. VisiTrip window: Red mechanical indicator shows fault trip status for fast troubleshooting
  4. Comprehensive protection: Prevents indirect electric shock and fire hazards caused by earth leakage
  5. Full compatibility with iC60 MCBs: Does not alter the original short-circuit and overload protection characteristics of the MCB when combined

Differences from Similar Models

모델제품 유형주요 차이점
A9Q41225QuickVigi iC60 Add-on Module1.5 모듈, QuickVigi series, market-specific version
A9V41225Vigi iC60 Standard Add-on Module3 모듈 (63mm 폭), standard Vigi series
A9R41225iID Standalone RCCBIndependent installation, no MCB required, built-in overload and short-circuit protection

응용

Suitable for residual current protection in final distribution systems, especially for:

Socket circuits in residential, commercial and small industrial buildings

Areas with high personal safety requirements (30mA sensitivity provides direct contact protection)

Installations needing space saving in distribution boards (1.5-module design saves 50% space vs. standard 3-module units)

Combination with iC60 miniature circuit breakers for a complete solution against overload, short-circuit and earth leakage

Key Installation & Operating Instructions

  1. Must be used together with Schneider iC60 series miniature circuit breakers
  2. Mounted on the right side of the iC60 MCB and fixed with dedicated clips
  3. Operating temperature range: -25°C ~ +40°C
  4. Pollution degree: 3
  5. Rated impulse withstand voltage (음): 6kV

A9Q41225 is a compact earth leakage protection solution launched by Schneider for specific markets. With its space-saving 1.5-module design, it delivers the same 2P 25A 30mA Type AC earth leakage protection as standard 3-module products, making it an ideal choice for space-efficient final distribution systems in residential and commercial buildings.