CHINT NM1LE800S-4300-800A MCCB - Contactor,circuit breaker,solar inverter,electric meter,solar batteries

circuit breaker/

CHINT NM1LE800S-4300-800A MCCB

This is a CHINT NM1LE series 800A moulded case earth leakage circuit breaker with triple protection: overload, short-circuit and earth leakage. It has S-class breaking capacity (36kA@400V), 4-pole fixed installation, and adjustable rated residual operating current (30–500mA). It is widely used for personal electric shock protection and earth fault protection in industrial power distribution, high-power ...

  • Product Details

This is a CHINT NM1LE series 800A moulded case earth leakage circuit breaker with triple protection: overload, short-circuit and earth leakage. It has S-class breaking capacity (36kA@400V), 4-pole fixed installation, and adjustable rated residual operating current (30–500mA). It is widely used for personal electric shock protection and earth fault protection in industrial power distribution, high-power motor circuits and building electrical systems.

  1. Full Model Code Breakdown
SectionMarkingDescriptionTechnical Note
1NM1LEProduct SeriesMCCB with earth leakage protection (LE = Leakage) based on CHINT NM1 series
2800Frame rated currentMaximum frame current: 800A
3SBreaking capacity classS-class standard breaking capacity, 36kA@400V, for general distribution
44300Pole number + trip type4 poles (3Ph+N), thermomagnetic trip (300 = no undervoltage release)
5800ARated current (In)Continuous operating current: 800A
  1. Key Technical Parameters
ItemValueRemarks
Product typeNM1LE series MCCB with earth leakage protectionClassic CHINT series with international advanced technology
Rated insulation voltage (Ui)800VMaximum continuous voltage for insulation parts
Rated operating voltage (Ue)400V AC (50Hz)Standard for three-phase four-wire systems
Rated impulse withstand voltage (Uimp)8kVWithstand capability against transient high voltage
Ultimate breaking capacity (Icu)36kA@400VS-class, suitable for general industrial & commercial use
Service breaking capacity (Ics)50% IcuReusable after fault operation (GB 14048.2 compliant)
Rated current (In)800AMaximum continuous current
Trip characteristicThermomagnetic (inverse time overload + instantaneous short-circuit)Overload: 0.8–1.0In adjustable; Instantaneous: 5–10In
Earth leakage parametersRated residual operating current (IΔn): 30/100/200/300/500mA optionalProvides both personal shock protection and earth fault protection
Residual non-operating current (IΔn0): 0.5IΔn
Operating time: ≤0.3s (≤30mA), ≤0.1s (>30mA)
Poles4P (3Ph+N)N pole for leakage detection only (not for short-circuit breaking except special versions)
Mounting typeFixedStandard rail or bolt mounting; withdrawable not supported
Connection typeFront connection (standard)Rear or plug-in connection optional
Degree of protectionIP30IEC 60529, protects against finger and solid foreign objects
Ambient temperature-5℃ to +40℃Derate required beyond this range
Dimensions (mm)H×W×D: 360×240×180Standard industrial size for panel installation
WeightApprox. 18kgIncludes leakage module; ~3kg heavier than standard NM1
  1. Typical Applications
  2. Industrial power distribution systems

Main or sub-switch for three-phase four-wire 800A high-current circuits

Control circuits for large motors (e.g., 400kW induction motors) with full protection

Factories, data centers, mines requiring personal safety protection

  1. Building electrical systems

Main switchboards and emergency power circuits in commercial and high-rise buildings

Public buildings such as hospitals and schools with high safety requirements

Power circuits for HVAC, pump rooms and large equipment to prevent electrical fires

  1. Special safety applications

Harsh environments: wet, dusty, corrosive locations (chemical, textile plants)

Locations requiring high-level fire protection: warehouses, power distribution rooms

Heavy-duty equipment with frequent starts: cranes, compressors, to detect insulation failure

  1. Replacement Models

4.1 CHINT Upgrades / Replacements

Replacement ModelMain DifferenceApplication
NM1LE800H-4300-800ABreaking capacity upgraded to H-class (50kA@400V)Systems with high short-circuit current near transformers
NM1LE800S-4308-800AWith motorized operatorRemote control, unattended automation systems
NXMLE800S-4300-800ANew Kunlun Series, smaller size, improved performanceSystem upgrades, new installations
NM1LE800S-4310-800AWith undervoltage releaseCritical circuits requiring undervoltage protection (e.g., fire power)

4.2 Cross‑Brand Equivalents

BrandModelKey Matching ParametersNotes
ABBT6N800 PR221DS-LSI+RCD 800 4PIn=800A, Icu=36kA, 4P, earth leakageElectronic trip + leakage module, higher precision
SchneiderNSX800F TM800D+Vigi 4PIn=800A, Icu=36kA, 4P, thermomagnetic + leakageIdentical breaking capacity, reliable Vigi module
Siemens3VA6880-6EL32-0AA0+3VA9180-0AA00In=800A, Icu=36kA, 3P+N, leakage add-on3VA series with leakage kit, similar performance
MitsubishiNF800-CW+leakage module 4PIn=800A, Icu=35kA, 4P, thermomagnetic + leakageJapanese brand, suitable for Japanese-equipped systems
  1. Selection & Application Notes
  2. Breaking capacity matching

Ensure short-circuit current ≤ 36kA@400V; otherwise use NM1LE800H (50kA).

S-class breaking capacity decreases at higher voltages; recheck for 690V systems.

  1. Earth leakage current selection

Personal protection / wet areas: IΔn = 30mA

Equipment & fire protection: IΔn = 100–300mA

Motor & high-power loads: IΔn = 300–500mA to avoid nuisance tripping during startup.

  1. Poles and N‑pole configuration

4-pole for three-phase four-wire systems only; N wire must be connected.

N pole only detects leakage; it does not break short-circuit current (except special versions).

For interruptible N pole, select a special model with “N-pole breaking”.

  1. Installation & wiring

Fixed mounting; allow ≥180mm depth for heat dissipation.

Use copper busbar/cable rated for 800A: ≥240mm² cable or 40×10mm busbar recommended.

Must be installed vertically, tilt ≤15°.

  1. Maintenance & replacement

Test leakage function monthly using the TEST button.

Inspect contacts after short-circuit operation; replace if necessary.

For upgrades, prefer CHINT NXMLE Kunlun Series (compatible dimensions, better performance).

Leakage module can be replaced separately.

CHINT NM1LE800S-4300-800A is a reliable 800A earth leakage MCCB with triple protection, standard breaking capacity and 4-pole design, ideal for industrial automation and building electrical systems. Selection should consider short-circuit level, leakage requirements and installation space. For better performance and safety, use higher-breaking versions or the new Kunlun series when applicable.

CHINT NM1LE800S-4300-800A – Key Selection Notes

  1. Breaking Capacity Check

This model: S-class = 36kA@400V

If short-circuit current >36kA (near transformer, main incomer), use NM1LE800H (50kA).

  1. Current Rating

Frame current 800A, rated current 800A

For continuous loads ≤800A only; do not overload.

  1. Poles & System Type

4300 = 4P (3Ph+N) + thermomagnetic trip

For three-phase four-wire (380V+N) systems only; N wire must be connected.

N pole does not break short-circuit current, only for leakage detection.

  1. Earth Leakage Selection

Available settings: 30/100/200/300/500mA

Personal safety / wet areas: 30mA

Equipment / fire protection: 100–300mA

Motors / high-power loads: 300–500mA (prevents startup nuisance tripping)

  1. Trip Characteristics

Thermomagnetic: overload + instantaneous short-circuit protection

Instantaneous range: 5–10In

Set higher for motors to avoid tripping during startup.

  1. Installation & Environment

Must be vertical, tilt ≤15°

Ambient: -5℃ to +40℃; derate at high temperature

IP20 open type; install in enclosure for dusty, wet or oily areas.

  1. Wiring & Heat Dissipation

Use 800A-rated conductors:

≥240mm² copper cable or 40×10mm copper busbar

Terminations must be tightly torqued to avoid overheating.

  1. Maintenance & Safety

Press TEST button monthly to verify leakage function.

Leakage module replaceable separately.

Not recommended for three-phase three-wire systems without neutral.

  1. Upgrade Recommendation

New CHINT NXMLE800S series: better performance, smaller size

Preferred for replacement or upgrade (dimensions nearly compatible).