Fuji Electric SC‑E4 (including SC‑E4/G DC type) 3‑pole electromagnetic contactor. This is a main model in the SC‑E series with an 80A frame, used for industrial motor control.
Key Rated Parameters
- Motor Power (AC‑3): 22kW at 200–240V; 40kW at 380–440V
- Rated Operational Current: 80A (AC‑3); 105A for resistive load (AC‑1)
- Operation Type: AC operation SC‑E4; DC coil SC‑E4/G (e.g. DC24V, DC110V)
- Mounting: 35mm DIN rail / screw fixing; dimensions 67×130×112 mm; weight approx. 1.4 kg
- Certifications: Compliant with IEC, UL, CSA; marked with CE; finger‑safe terminals for electric shock protection
Structure & Features
3‑pole main circuit, standard without auxiliary contacts (auxiliary modules such as SZ‑AS1T can be side‑mounted to expand 1a1b / 2a / 2b)
Direct‑connect main terminal design for easier wiring; safety structure to prevent exposed live parts
Coil options: AC110V, AC220V, AC380V, DC24V, DC110V; DC type (/G) suitable for unstable grids or DC control circuits
Compatible thermal overload relay: TK‑E3 series, for overload, locked‑rotor, and phase‑failure protection
Ambient temperature: -5℃ to +55℃ (non‑condensing); altitude ≤ 2000 m
Typical Applications & Selection Notes
- For direct starting, star‑delta starting, and soft‑starting of 40kW (380–440V) / 22kW (200–240V) three‑phase asynchronous motors
- Selection must confirm: coil voltage, number of auxiliary contacts, control circuit voltage, rated current, duty category (AC‑3/AC‑1), and whether surge suppressors are required
- Comparable competitive models: Schneider LC1‑D80, ABB A145‑30‑11, Siemens 3RT2036
Model Example & Replacement
Model designation: SC‑E4 AC220V (AC coil); SC‑E4/G DC24V (DC coil)
Replacement notes: Coil voltage, rated current, mounting dimensions, and auxiliary contact configuration must match; DC coils cannot directly replace AC coils
Installation & Maintenance Tips
- Install vertically; avoid dusty, oily, or corrosive environments
- Use crimped terminals for main circuit cables; follow torque specifications in the manual; control circuit wires ≤ 2.5 mm²
- Regularly inspect contact erosion, loose wiring, and abnormal odors from the coil; replace main contacts or the entire contactor if necessary
- Connect RC circuits or varistors in parallel to suppress coil surge and protect PLC output points
Cross‑Brand Model Cross‑Reference & Replacement Guide for Fuji SC‑E4
The following cross‑reference is based on the core parameters of the Fuji SC‑E4, categorized into international first‑tier brands, Japanese/Korean equivalent brands, and mainstream domestic brands.
Two types are distinguished:
Performance‑matched (fully matching parameters, universal function)
and
Direct interchangeable (compatible mounting dimensions and terminal positions, replaceable without cabinet modification).
- International First‑Tier Brands
| Brand | Equivalent Model (AC/DC) | AC‑3 Rated Current | Motor Power at 380V | Width | Replacement Notes |
| Schneider | AC: LC1D80 | 80A | 40kW | 70mm | Top performance match, full parameter match; AC‑3/AC‑1 ratings identical to SC‑E4; mounting holes compatible; Chinese version includes 1NO+1NC aux contacts; global availability. |
| Economy: LC1N80 | |||||
| DC: LP1D80 | |||||
| ABB | AC: A95‑30‑11 / AF80‑30‑00 | 80A | 40kW | 70mm | Performance‑matched; AF series supports wide AC/DC coils, strong voltage fluctuation resistance; excellent arc interruption; suitable for heavy‑duty applications. |
| DC: AF80‑30‑00 (wide voltage DC) | |||||
| Siemens | AC: 3RT2038 | 80A | 37kW/40kW | 62mm | Compact S2 frame; full 80A AC‑3 match; built‑in 1NO+1NC aux contacts; compatible with 3RU2 thermal relays; logic matches SC‑E4 + TK‑E3. |
| DC: 3RT2038 (DC coil suffix) | |||||
| Eaton Moeller | AC: DILM80 | 80A | 37kW/40kW | 69mm | Performance‑matched; mechanical and electrical life equivalent to Fuji; direct‑mount thermal relay compatible; ideal for export projects and European standard cabinets. |
| DC: DILM80 (DC coil suffix) |
- Japanese & Korean Equivalent Brands
| Brand | Equivalent Model (AC/DC) | AC‑3 Rated Current | Motor Power at 380V | Width | Replacement Notes |
| Mitsubishi | AC: S‑M80 / S‑T80 | 80A | 40kW | 67mm | Direct interchangeable; same width, mounting holes, and terminal pitch; fully compatible auxiliary and thermal relay mounting. |
| DC: SD‑T80 | |||||
| LS Electric (former LG) | AC: GMC‑85 / MC‑85a | 85A | 45kW | 82mm | Performance‑matched with extra current margin; heavy‑duty rated; includes 1NO+1NC aux contacts; widely available. |
| DC: GMD‑85 |
- Mainstream Domestic Brands (Cost‑Effective Replacement)
| Brand | Equivalent Model | AC‑3 Rated Current | Motor Power at 380V | Width | Replacement Notes |
| Chint | CJX2‑8011 / NC1‑8011 | 80A | 40kW | 70mm | Direct replacement; dimensions compatible with LC1D80 and SC‑E4; built‑in 1NO+1NC aux contacts; CCC/CE certified; cost‑effective. |
| Delixi | CJX2s‑8011 / CDC1‑8011 | 80A | 40kW | 70mm | Universal replacement; full parameter match; dual rail/screw mounting; silver alloy contacts; nationwide service. |
| TENGEN | CJX2‑8011 / TGC1‑8011 | 80A | 40kW | 70mm | Industrial‑grade replacement; improved surge & humidity resistance; suitable for harsh environments; meets tendering requirements. |
Key Notes for Cross‑Brand Replacement
- Coil specification must be 1:1 matched: AC coils (AC110V/220V/380V) and DC coils (DC24V/DC110V) cannot be interchanged. SC‑E4/G DC type can only be replaced by the same DC voltage model.
- Auxiliary contact logic matching: SC‑E4 has no built‑in auxiliary contacts. If the replacement model includes aux contacts, verify NO/NC logic in the PLC program to avoid malfunction.
- Thermal relay compatibility: Confirm rated current and mounting style after replacement; direct‑mount thermal relays must match the contactor frame.
- Cabinet space: Direct‑interchangeable models can be installed without modification. For performance‑matched models, verify width, height, and depth to avoid door interference or busbar conflict.