Wechat: +86-13184948252  WhatsaApp: 0086-13811255435  E-mail:  kent@bestcontactor.com

About    Contact    |    

Schneider MCCB CVS160F-3P-125A - Contactor,circuit breaker,solar inverter,electric meter,solar batteries

circuit breaker/

Schneider MCCB CVS160F-3P-125A

Schneider CVS Series MCCB (Molded Case Circuit Breaker) Model Explanation: MCCB‑CVS160F‑3P‑125A MCCB: Molded Case Circuit Breaker CVS: Schneider CVS Series MCCB 160: Frame rating current 160A F: Breaking capacity class, Type F: 36kA@400VAC 3P: 3 poles (three‑phase three‑wire) 125A: Rated operational current 125A Basic Parameters Type: Molded Case Circuit Breaker Series: CVS Frame current: 160A ...

  • Product Details

Schneider CVS Series MCCB (Molded Case Circuit Breaker)

Model Explanation: MCCB‑CVS160F‑3P‑125A

MCCB: Molded Case Circuit Breaker

CVS: Schneider CVS Series MCCB

160: Frame rating current 160A

F: Breaking capacity class, Type F: 36kA@400VAC

3P: 3 poles (three‑phase three‑wire)

125A: Rated operational current 125A

Basic Parameters

Type: Molded Case Circuit Breaker

Series: CVS

Frame current: 160A

Rated current: 125A

Poles: 3P

Breaking capacity: 36kA

Application: Three‑phase power distribution protection

Below are the key engineering data for Schneider MCCB‑CVS160F‑3P‑125A (Order No. LV516332) for direct selection, panel layout and replacement.

  1. Dimensions (Fixed Mounted Type)
DimensionValueNotes
Width (W)90mmStandard 3P width
Height (H)185mmIncluding handle
Depth (D)105mmExcl. terminals; approx. 120mm incl. terminals
Mounting hole spacing75mm*150mm4*M6 mounting holes
Degree of protectionIP40Complies with IEC 60529
  1. Connection Method
  2. Standard: Front connection, default, no extra accessories required
  3. Optional:

Rear connection: requires dedicated rear connection base

Plug‑in connection: requires plug‑in base for quick replacement

  1. Connection Specifications:

Copper bar: max. 120mm² (recommended)

Cable: max. 150mm² (copper), cable lugs recommended

Rated torque: M10 bolt, 25N·m

  1. Recommended Replacement Models

3.1 Schneider Direct Replacements

SeriesModelFeaturesCompatibility
CVS OriginalCVS160F TM125D 3P3D (LV516332)Identical, direct replacementFully compatible
NSX (Premium)NSX160F TM125D 3P3D (LV430632)Higher breaking capacity (70kA@400V), optional electronic tripSame dimensions, enhanced functions
EZD (Economic)EZD160E TMD125 3PLower cost, 25kA@400VSame dimensions, lower breaking capacity

3.2 Other Brands

BrandModelMatching Parameters
ABBTmax T2N160 TMD125 3PFrame 160A, In 125A, 36kA
Siemens3VL1716‑1DD33‑0AA0Frame 160A, In 125A, 36kA
ChintNXM‑160S/3300 125AFrame 160A, In 125A, 36kA
  1. Additional Notes
  2. Trip unit: TM‑D thermal‑magnetic, adjustable overload (87.5–125A), fixed short‑circuit (≈10In)
  3. Breaking capacity: 36kA@400VAC, complies with IEC 60947‑2
  4. Mounting: Fixed (standard), plug‑in (optional), withdrawable (optional)

Complete List of Equivalent Replacements for Schneider MCCB‑CVS160F‑3P‑125A

All below match key parameters: frame 160A, In 125A, 3P, 36kA@400V, thermal‑magnetic trip, suitable for direct engineering replacement.

  1. Schneider Direct Replacements (Seamless Compatibility)
SeriesModelOrder No.FeaturesCompatibility
CVS OriginalCVS160F TM125D 3P3DLV516332Identical, direct replacement100% compatible
NSX PremiumNSX160F TM125D 3P3DLV43063270kA@400V, optional electronic tripSame dimensions
EZD EconomicEZD160E TMD125 3PLV510332Cost‑effective, 25kA@400VSame dimensions
  1. International Brand Equivalents

ABB

SeriesModelKey ParametersFeatures
3VL3VL1716‑1DD33‑0AA0160A frame, 125A, 36kAModular design
3VT3VT8116‑1AA03‑0AA0Thermal‑magnetic, 36kA, 3PEconomic, reliable

Siemens

SeriesModelKey ParametersFeatures
3VL3VL1716‑1DD33‑0AA0160A frame, 125A, 36kAModular design
3VT3VT8116‑1AA03‑0AA0Thermal‑magnetic, 36kA, 3PEconomic, reliable

Eaton Moeller

SeriesModelKey ParametersFeatures
NZMNZM2‑160 TM125 3P160A frame, 125A, 36kAHigh reliability for industry
  1. Chinese Domestic Brands (Cost‑Effective)

Chint

SeriesModelKey ParametersFeatures
NXMNXM‑160S/3300 125A160A, 125A, 36kAHigh cost‑performance
CDM6iCDM6i‑160M/3300B 125AThermal‑magnetic, 36kA, fixedSmart options available

Delixi

SeriesModelKey ParametersFeatures
CDM3CDM3‑160S/3300 125A160A, 125A, 36kAStable performance
CDM1CDM1‑160L/3300 125AThermal‑magnetic, 36kA, 3PProven classic

TENGEN

SeriesModelKey ParametersFeatures
TGM1TGM1‑160L/3300 125A160A, 125A, 36kAReliable domestic choice
  1. Key Selection Criteria

4.1 Core Parameter Matching Table

ItemOriginal RequirementReplacement Must Meet
Frame current160A160A
Rated current125A125A
Poles3P3P
Breaking capacity36kA@400V≥ 36kA@400V
Trip typeThermal‑magnetic (TM‑D)Thermal‑magnetic (TMD/TMF)
MountingFixedFixed (or with adapter)
ConnectionFrontFront (or with adapter)

4.2 Replacement Notes

  1. Dimensions: Most replacements: W90mm × H185mm × D105mm, direct fit
  2. Trip characteristics: Overload 87.5–125A, short‑circuit ≈10In must match
  3. Accessories: Check compatibility for auxiliary contacts, undervoltage release, etc.
  4. Certification: IEC / GB certified
  5. Recommended Solutions
ApplicationRecommended ModelReason
Original replacementSchneider CVS160F TM125D 3P3DIdentical, zero risk
Performance upgradeABB T2N160 TMD125 3P or Siemens 3VL1716‑1DD33‑0AA0International brand, reliable
Cost controlChint NXM‑160S/3300 125A or Delixi CDM3‑160S/3300 125ACost‑effective, good local support

Prev:

Leave a Reply

Leave a message