T6V 800 PR221DS|ABB Tmax T6 Series High Performance Moulded Case Circuit Breaker (MCCB)

Full Model: T6V 800 PR221DS-LS/I In=800 (Common Order Codes: 1SDA069432R1, 1SDA069429R1, 3P/4P selectable)

Marca: ABB (SACE Tmax Series)

  1. Detailed Model Interpretation
Model SegmentSignificadoKey Description
T6Series DesignationTmax T6 series, frame current 800A, suitable for medium and high voltage power distribution systems
VClasse de Capacidade de QuebraClass V, ultra-high breaking capacity: 120kA at 400V, 200kA at 220V
800Corrente nominal800UM (same as frame current)
PR221DSTipo de unidade de viagemElectronic intelligent trip unit with LS/I protection (Long-time delay L, Short-time delay S, Instantaneous I)
LS/IProtection ConfigurationStandard three-stage protection; earth fault protection optional (extra configuration required)
F FMounting / ConnectionFirst F: Fixed mounting; Second F: Front connection
  1. Parâmetros técnicos principais
ItemEspecificaçãoObservações
Tensão nominal (Ué)690V eSuitable for industrial high-voltage power distribution systems
Tensão nominal de isolamento (interface do usuário)1000V eHigher than rated operating voltage, large safety margin
Ultimate Breaking Capacity (UTI)120kA@400V, 200kA@220VHighest Class V, adequado para ambientes industriais agressivos
Rated Operational Current (Em)800UMMaximum continuous operating current
Poloneses3P/4P selectable3P for three-phase circuits, 4P includes neutral protection
Trip CharacteristicLS/I three-stage protectionLong-time delay inverse time, short-time / instantaneous definite time
Mounting TypeFixoDraw-out type also available (special model required)
Connection TypeFront connectionCompatible with cables or busbars
Degree of ProtectionIP30Standard switchgear installation protection
Applicable StandardCEI 60947-2International standard for low-voltage switchgear
  1. Key Features & Applications

Principais vantagens

  1. Ultra-high breaking capacity: Class V can withstand severe short-circuit faults and ensure system safety
  2. Intelligent protection: PR221DS trip unit provides accurate overload and short-circuit protection with adjustable parameters
  3. Reliable and durable: ABB Tmax series design, suitable for frequent operation and harsh industrial environments
  4. Flexible extension: Supports various accessories (contatos auxiliares, contatos de alarme, undervoltage release, etc.)

Aplicações Típicas

Main power distribution systems in large industrial plants

690V high-voltage Motor Control Centers (MCC)

Power supply for data centers and critical infrastructure

Combiner box protection for new energy power systems (PV, wind power)

Marine and offshore platform power distribution systems

  1. Reference Replacement Models

Same-brand Upgrades / Replacements

ModeloQuebrando CapacidadeTipo de viagemApplication
T6V 800 PR222DS-LSIG120kA@400VWith earth fault protection (G)Systems requiring earth fault detection
T6V 800 PR223DS120kA@400VAdvanced intelligent trip unitApplications requiring remote monitoring and communication
T6S 800 PR221DS70kA@400VStandard breaking capacityGeneral industrial power distribution, lower cost

Cross-brand Alternatives

MarcaModeloKey Matching Parameters
SchneiderMasterpact MT25H1 800A800UM, 120kA breaking, three-stage protection
Siemens3WL1210-3BB36-4GA4800UM, 100kA breaking, intelligent trip unit
MitsubishiNF800-SEW800UM, 100kA breaking, electronic trip unit
  1. Notas de seleção
  2. Breaking capacity matching: Select V/S/H/N/L classes based on system short-circuit current calculation
  3. Protection function selection: Basic LS/I meets most needs; choose LSIG for earth fault protection
  4. Mounting type: Fixed for standard switchgear, draw-out for easy maintenance and replacement