Conversamos: +86-13184948252 Whatsapp: 0086-13811255435 E-mail: kent@bestcontactor.com

Sobre Contato |

Parâmetros técnicos completos da Siemens 3WL1116/3WL1216 1600A ETU45B-G-LCD-3P - Contator,disjuntor,inversor solar,medidor elétrico,baterias solares

NotíciasNotícias comerciais

Parâmetros técnicos completos da Siemens 3WL1116/3WL1216 1600A ETU45B-G-LCD-3P

Complete Technical Parameters of Siemens 3WL1116/3WL1216 1600A ETU45B-G-LCD-3P

The parameters cover dimensions including basic electrical characteristics, capacidade de interrupção, trip unit, mechanical & environmental performance, communication and installation, facilitating engineering selection and system matching.

  1. Parâmetros Elétricos Básicos
Item de parâmetroSpecification ValueObservações
Série de produtosSiemens SENTRON 3WLDisjuntor de ar (ACB)
Frame Size3WL1116 (Frame I) / 3WL1216 (Frame II)3WL1116: Capacidade de interrupção padrão; 3WL1216: High breaking capacity
Corrente nominal (Em)1600UMFrame size current 1600A, setting range 0.4–1In
Número do pólo3PThree-pole, 3-phase main circuit
Tensão operacional nominal (Ué)690V e50/60Hz, compatível com IEC 60947-2
Tensão nominal de isolamento (interface do usuário)1000V eBenchmark value for insulation withstand capability
Tensão nominal suportável ao impulso (Um)12kVCompatível com IEC 60947-1
Rated Short-time Withstand Current (Icw)Frame I: 66kA/1s; Frame II: 80kA/1sEnsures short-time thermal stability at 500V
Quebrando Capacidade (UTI)Frame I: 55/66o; Frame II: 80/100oUltimate breaking capacity at 500V; Frame II offers higher breaking capacity
  1. Parameters of ETU45B-G-LCD Electronic Trip Unit
Function ModuleSpecification ValueDescrição
Protection TypeLSIG (eu: Overload/Long-time Delay; S: Short-circuit/Short-time Delay; EU: Instantaneous Short-circuit; G: Ground Fault)Complete power distribution protection configuration
Proteção contra sobrecarga (eu)Characteristic Curve: I²t/I⁴t selectable; Setting Range: 0.4–1InI⁴t characteristic improves selectivity with downstream devices
Short-time Delay Short-circuit Protection (S)Setting Current: 2–10 pol.; Time Delay: 0.1–0.4sAdjustable inverse/definite time delay to prevent selective tripping
Instantaneous Short-circuit Protection (EU)Setting Current: 2–10 pol.Rapid short-circuit current interruption without time delay
Proteção contra falta à terra (G)Setting Current: 0.2–0.8In; Time Delay: 0.1–2sDetects ground faults to avoid equipment damage
Display & OperaçãoLCD screen, rotary coding switchReal-time display of current, trip cause and fault records
Método de redefiniçãoManual/Auto selectableQuick power supply recovery after fault clearance

III. Mecânico & Environmental Parameters

Item de parâmetroSpecification ValueObservações
Vida Mecânica150,000 operaçõesNo-load operation, compatível com IEC 60947-2
Vida Elétrica10,000 operações (AC-3, at rated current)On-load breaking life, related to operating frequency
Operating MechanismSpring-loaded energy storage type (manual/electric optional)Electric mechanism suitable for remote control
Contatos AuxiliaresPadrão: 2NÃO+2NC, expandable to 4NO+4NCStatus feedback and control circuit interlocking
Temperatura ambiente-25℃~+70℃ (operating); -40℃~+85℃ (storage)Wide temperature range for industrial applications
Classe de ProteçãoIP30 (body); IP40 (with protective cover)Prevents solid foreign object intrusion
Altitude≤2000m (derating required above 2000m)Rated current derating by 1% for every 100m altitude increase
Método de montagemFixed type/Drawout typeDrawout type enables maintenance without power outage
  1. Comunicação & Measurement Parameters
FunçãoEspecificaçãoInterface/Protocol
Communication ModuleCOM15 (PROFIBUS DP) / COM16 (MODBUS RTU)Opcional, supports data upload to monitoring system
Measurement AccuracyAtual: ±1%; Tensão: ±1.5%; Power: ±2%Compatible with Plus measurement function for energy management
Data Logging100 fault records (trip type, tempo, current value)Fault tracing and system diagnosis
Remote ControlSupports remote opening/closing and parameter settingRealized by electric mechanism + módulo de comunicação
  1. Instalação & Dimension Parameters
Tipo de montagemLargura (C)Altura (H)Profundidade (D)Peso
3WL1116 Fixed Type320milímetros434milímetros291milímetrosAprox.. 45kg
3WL1116 Drawout Type320milímetros434milímetrosAprox.. 450milímetrosAprox.. 55kg
3WL1216 Fixed Type460milímetros434milímetros291milímetrosAprox.. 56kg
3WL1216 Drawout Type460milímetros434milímetrosAprox.. 450milímetrosAprox.. 65kg
Mounting Mode35mm DIN rail/screw mountingFrame I width: 320milímetros; Frame II width: 460milímetros; Unified height: 434milímetros
  1. Key Selection & Application Tips
  2. Breaking Capacity Matching: Select frame size based on the system’s maximum short-circuit current. Frame I is suitable for scenarios ≤66kA, while Frame II is for ≤100kA. UM 20% margin is recommended.
  3. Trip Unit Setting: Enable LSIG protection for motor loads, with the ground fault setting recommended at 0.3–0.5In. LSI protection is sufficient for power distribution loads.
  4. Communication Compatibility: Select COM15/COM16 module for remote monitoring, ensuring protocol compatibility with PLC/SCADA systems (PROFIBUS/MODBUS).
  5. Installation Space: The drawout type occupies approximately 160mm more depth than the fixed type. Reserve sufficient operation and maintenance space during cabinet design.
  6. Replacement & Atualizar: The 3WL series has been upgraded to the 3WA series (por exemplo, 3WA1116-3EG45-4GA4), featuring compatible dimensions and protection functions, plus added Ethernet communication and intelligent diagnosis.

 

 

VII. Conformidade & Certificação

Compliant Standards: GB 14048.2, CEI 60947-2, EM 60947-2

Certificações: CE, UL, CSA (for some models), meeting compliance requirements for global industrial applications

Anterior:

Próximo:

Deixe uma resposta

Deixe um recado