Parâmetros técnicos completos da Siemens 3WL1116/3WL1216 1600A ETU45B-G-LCD-3P - Contator,disjuntor,inversor solar,medidor elétrico,baterias solares

NotíciasNotícias comerciais

Parâmetros técnicos completos da Siemens 3WL1116/3WL1216 1600A ETU45B-G-LCD-3P

Complete Technical Parameters of Siemens 3WL1116/3WL1216 1600A ETU45B-G-LCD-3P

The parameters cover dimensions including basic electrical characteristics, capacidade de interrupção, trip unit, mechanical & environmental performance, communication and installation, facilitating engineering selection and system matching.

  1. Parâmetros Elétricos Básicos
Parameter ItemSpecification ValueObservações
Série de produtosSiemens SENTRON 3WLAir Circuit Breaker (ACB)
Frame Size3WL1116 (Frame I) / 3WL1216 (Frame II)3WL1116: Standard breaking capacity; 3WL1216: High breaking capacity
Corrente nominal (Em)1600UMFrame size current 1600A, setting range 0.4–1In
Número do pólo3PThree-pole, 3-phase main circuit
Rated Operational Voltage (Ué)690V e50/60Hz, compatível com IEC 60947-2
Tensão nominal de isolamento (interface do usuário)1000V eBenchmark value for insulation withstand capability
Tensão nominal suportável ao impulso (Uimp)12kVCompatível com IEC 60947-1
Rated Short-time Withstand Current (Icw)Frame I: 66kA/1s; Frame II: 80kA/1sEnsures short-time thermal stability at 500V
Quebrando Capacidade (UTI)Frame I: 55/66o; Frame II: 80/100oUltimate breaking capacity at 500V; Frame II offers higher breaking capacity
  1. Parameters of ETU45B-G-LCD Electronic Trip Unit
Function ModuleSpecification ValueDescription
Protection TypeLSIG (eu: Overload/Long-time Delay; S: Short-circuit/Short-time Delay; EU: Instantaneous Short-circuit; G: Ground Fault)Complete power distribution protection configuration
Proteção contra sobrecarga (eu)Characteristic Curve: I²t/I⁴t selectable; Setting Range: 0.4–1InI⁴t characteristic improves selectivity with downstream devices
Short-time Delay Short-circuit Protection (S)Setting Current: 2–10In; Time Delay: 0.1–0.4sAdjustable inverse/definite time delay to prevent selective tripping
Instantaneous Short-circuit Protection (EU)Setting Current: 2–10InRapid short-circuit current interruption without time delay
Proteção contra falta à terra (G)Setting Current: 0.2–0.8In; Time Delay: 0.1–2sDetects ground faults to avoid equipment damage
Display & OperationLCD screen, rotary coding switchReal-time display of current, trip cause and fault records
Método de redefiniçãoManual/Auto selectableQuick power supply recovery after fault clearance

III. Mechanical & Environmental Parameters

Parameter ItemSpecification ValueObservações
Vida Mecânica150,000 operaçõesNo-load operation, compatível com IEC 60947-2
Vida Elétrica10,000 operações (AC-3, at rated current)On-load breaking life, related to operating frequency
Operating MechanismSpring-loaded energy storage type (manual/electric optional)Electric mechanism suitable for remote control
Contatos AuxiliaresPadrão: 2NO+2NC, expandable to 4NO+4NCStatus feedback and control circuit interlocking
Temperatura ambiente-25℃~+70℃ (operating); -40℃~+85℃ (storage)Wide temperature range for industrial applications
Classe de ProteçãoIP30 (body); IP40 (with protective cover)Prevents solid foreign object intrusion
Altitude≤2000m (derating required above 2000m)Rated current derating by 1% for every 100m altitude increase
Mounting MethodFixed type/Drawout typeDrawout type enables maintenance without power outage
  1. Comunicação & Measurement Parameters
FunçãoSpecificationInterface/Protocol
Communication ModuleCOM15 (PROFIBUS DP) / COM16 (MODBUS RTU)Opcional, supports data upload to monitoring system
Measurement AccuracyCurrent: ±1%; Voltage: ±1.5%; Poder: ±2%Compatible with Plus measurement function for energy management
Data Logging100 fault records (trip type, tempo, current value)Fault tracing and system diagnosis
Remote ControlSupports remote opening/closing and parameter settingRealized by electric mechanism + communication module
  1. Instalação & Dimension Parameters
Mounting TypeLargura (C)Altura (H)Profundidade (D)Peso
3WL1116 Fixed Type320milímetros434milímetros291milímetrosApprox. 45kg
3WL1116 Drawout Type320milímetros434milímetrosApprox. 450milímetrosApprox. 55kg
3WL1216 Fixed Type460milímetros434milímetros291milímetrosApprox. 56kg
3WL1216 Drawout Type460milímetros434milímetrosApprox. 450milímetrosApprox. 65kg
Mounting Mode35mm DIN rail/screw mountingFrame I width: 320milímetros; Frame II width: 460milímetros; Unified height: 434milímetros
  1. Key Selection & Application Tips
  2. Breaking Capacity Matching: Select frame size based on the system’s maximum short-circuit current. Frame I is suitable for scenarios ≤66kA, while Frame II is for ≤100kA. UM 20% margin is recommended.
  3. Trip Unit Setting: Enable LSIG protection for motor loads, with the ground fault setting recommended at 0.3–0.5In. LSI protection is sufficient for power distribution loads.
  4. Communication Compatibility: Select COM15/COM16 module for remote monitoring, ensuring protocol compatibility with PLC/SCADA systems (PROFIBUS/MODBUS).
  5. Installation Space: The drawout type occupies approximately 160mm more depth than the fixed type. Reserve sufficient operation and maintenance space during cabinet design.
  6. Replacement & Upgrade: The 3WL series has been upgraded to the 3WA series (por exemplo, 3WA1116-3EG45-4GA4), featuring compatible dimensions and protection functions, plus added Ethernet communication and intelligent diagnosis.

 

 

VII. Compliance & Certification

Compliant Standards: GB 14048.2, CEI 60947-2, EM 60947-2

Certifications: CE, UL, CSA (for some models), meeting compliance requirements for global industrial applications