Technical Specifications and Application Guide for ABB MCCB 1SDA050999R1 Model Explanation Model Part Description 1SDA050999R1 Unique global product code for ABB SACE Tmax T series molded case circuit breaker T2S Product series: Tmax T2 series; S stands for standard breaking capacity (50cel) 160 Curent nominal de cadru: 160A TMD Trip unit type: Unitate de declanșare termomagnetică, D-curve ...

  • Detalii despre produs

Technical Specifications and Application Guide for ABB MCCB 1SDA050999R1

  1. Explicația modelului
Partea modeluluiDescriere
1SDA050999R1Unique global product code for ABB SACE Tmax T series întrerupător cu carcasă turnată
T2SSeria de produse: Tmax T2 series; S stands for standard breaking capacity (50cel)
160Curent nominal de cadru: 160O
TMDTip unitate de declanșare: Unitate de declanșare termomagnetică, D-curve (motor protection type)
50-500Trip unit rated current range: 50O (evaluat), 500O (instantaneous trip value)
3pNumărul de poli: 3 stâlpi
F FMontare: Fix; Conexiune: Conexiune frontală
  1. Parametri cheie

Parametrii electrici

ArticolValoare
Tensiune nominală de funcționare (Şi)400V și (50/60Hz), 690V AC optional
Tensiunea nominală de izolație (Ui)690V și
Tensiune nominală de rezistență la impuls (Ump)8kV
Curent nominal (În)50O (adjustable range 50–500A)
Curent nominal de cadru (Icu)160O
Capacitate de rupere50cel (415V și), 36cel (690V și)
Curent de scurtă durată (Icw)16cel (1s)
Trip curveTip D, conform cu IEC 60947-2
Thermal trip range50–500A (reglabil)
Magnetic trip range5-10 in (reglabil)
Frecvența nominală50/60Compatibil cu Hz

Parametri mecanici

ArticolValoare
Mod de operareManual (standard), motor operation optional
Rezistenta mecanica10,000 operațiuni (at rated)
Rezistenta electrica1,000 operațiuni (rated short-circuit breaking)
Grad de protectieIP30 (conform cu IEC 60529)
TerminaleConexiune frontală, suitable for cable cross-section: 16–70mm²
MontareFix, standard 35mm DIN rail mounting
  1. Dimensiuni de montare
ArticolValoare (mm)
Lăţime90
Înălţime150
Adâncime105
Mounting hole pitchSina DIN standard de 35 mm
Distanța între terminaleConform standardelor IEC, suitable for standard cable connections
  1. Note de aplicare

4.1 Ghid de selecție

Suitable for motor protection and general industrial power distribution systems, especially where D-curve tripping is required

Derate when ambient temperature exceeds 40°C: 1% per °C rise; max operating temperature 60°C

Derate at altitudes above 2000m: 1% per 100m rise; max altitude 4000m

Select appropriate trip setting current according to actual load, ensuring I_load ≤ In ≤ I_cable

4.2 Cerințe de instalare

Ensure breaker is OFF and voltage-free with multimeter before installation

Mount on 35mm standard DIN rail, ensure firm fixing to avoid vibration effects

Tighten terminals with suitable torque (recommended 6N·m) to prevent overheating from poor contact

Keep sufficient heat dissipation space: at least 50mm clearance around the breaker

Avoid installation in damp, prăfuită, corrosive gas or heavy vibration environments

4.3 Operare și întreținere

Inspect mechanical operating mechanism regularly (annually recommended) to ensure smooth ON/OFF

Test tripping function regularly (semi-annually recommended) to ensure reliable protection

Clean surface with dry soft cloth; avoid chemical cleaners

Record operation count; replace before reaching mechanical endurance

After short-circuit interruption, check breaker condition and replace if necessary

  1. Depanare
Fault SymptomCauze posibileSoluții
Fails to close1. Undervoltage trip not powered1. Check control power supply
2. Blocaj mecanic2. Operate manually several times to clear jam
3. Defecțiunea unității de declanșare3. Replace trip unit module
Deplasări frecvente1. Supraîncărcare1. Verificați curentul de sarcină
2. Scurt-circuit2. Troubleshoot short circuit
3. Improper trip setting3. Reset trip settings
4. Loose connection causing heating4. Check and tighten terminals
Ablația de contact1. Long-term overload1. Replace with higher-rated breaker
2. Insufficient breaking capacity2. Upgrade to higher breaking capacity model
3. Excessive operating frequency3. Reduce operation frequency or replace suitable model
Trip unit does not operate1. Trip unit damaged1. Înlocuiți unitatea de declanșare
2. Cablaj incorect2. Check wiring correctness
3. Excessively low ambient temperature3. Improve ambient temperature or select low-temperature model
Motor operation mechanism fails1. Control voltage below 85% Şi1. Check control power supply
2. Limit switch not reset2. Manually reset limit switch
3. Motor fault3. Replace operating mechanism motor
  1. Brand Replacement Solutions

6.1 ABB Alternative Models

Upgrade model: XT2S 160 TMA 50–500 3p F F (1SDA067555R1), Tmax XT series, performanță mai mare, compatible mounting dimensions

Economic alternative: Formula A1B 125 TMF 50–500 3p F F (1SDA066702R1), cost mai mic, same basic protection functions

6.2 Competitive Brand Equivalents

MarcaModel de înlocuirePrincipalele diferențe
SchneiderCVS160F TMD50 3P 50kASame breaking capacity, slight dimension difference, consistent trip curve
Siemens3VL160 50A 3P TMDSame frame current, 50kA capacitate de rupere, different operating mechanism design
ChintNM1-160S/3300 50AAlternativă internă, rentabil, basic functions consistent
DeliciosCDM1-160S/3300 50AAlternativă internă, cost-performanță ridicată, compliant with IEC standards

Detailed Mounting Dimensions for ABB MCCB 1SDA050999R1

  1. Basic Model and Mounting Type Confirmation

Model complet: ABB SACE Tmax T2S 160 TMD50–500 3p F F (1SDA050999R1)

Tip de montare: Fix (F), conexiune frontală (F)

Polonii: 3 stâlpi (3p)

Serie: Tmax T series (not XT upgraded series)

  1. Core Mounting Dimensions (Unitate: mm)
ArticolValoareObservații
Lăţime (W)90Standard 3-pole width, DIN rail compatible
Înălţime (H)130Including operating handle, fixed standard height
Adâncime (D)70Standard depth for fixed front connection, excluding terminal extension
MontareSina DIN standard de 35 mmConform IEC 60715, snap-in mounting
Mounting hole pitchFor 35mm DIN railRail thickness 1.0–1.5mm compatible
Distanța între terminalePhase spacing 25mm, N-line spacing 25mmStandard wiring, suitable for 16–70mm² cable
Terminal height45mmFrom rail plane to top of terminals
Handle height130mmFrom rail plane to top of handle
Net weight1.12kgWithout packaging
  1. Detailed Dimension Diagram Description

3.1 Front View Dimensions

Total width: 90mm (3-pol)

Înălțimea totală: 130mm (including handle)

Handle travel: aproximativ. 25mm (ON–OFF difference)

Trip indicator window: 30mm from top, centered

3.2 Side View Dimensions

Total depth: 70mm (fixed front connection)

DIN rail slot: 15mm from bottom, 35mm latime

Terminal connection depth: aproximativ. 15mm from front surface

Terminal tightening torque: 6N·m (for M6 bolts)

3.3 Installation Clearance Requirements

LocationMin. DistanţăDescriere
Left and right50mmFor wiring and heat dissipation
Top and bottom50mmPrevent heat buildup, ensure operating space
Front operating space100mmFor handle operation and maintenance
Spate (in cabinet)30mmFor cable bending radius
  1. Compatibilitate cu instalare

4.1 DIN Rail Compatibility

Compatible with standard 35mm DIN rail (ÎN 60715:2001)

Rail material: steel or aluminum, recommended thickness 1.2mm

Mounting clips: self-contained spring clips, no extra fixings needed

4.2 Dimension Comparison with XT Series

ArticolTmax T2S 160 (1SDA050999R1)Tmax XT2S 160Diferenţă
Lăţime90mm90mmAceleaşi, interchangeable position
Înălţime130mm130mmAceleaşi, panel cutout universal
Adâncime70mm82.5mmXT series deeper; check cabinet space before replacement
MontareAceleaşi (35mm șină DIN)AceleaşiComplet compatibil

4.3 Compatibilitate cablare

Suitable cable cross-section: 16–70mm² (cupru), crimped lugs recommended

Terminal type: plate terminals with lock washers

Connection direction: conexiune frontală, vertical or horizontal incoming

  1. Installation Cautions
  2. Confirm breaker is OFF and voltage-free before installation
  3. Ensure snap-in is fully engaged on DIN rail
  4. Tighten terminals with 6N·m torque to avoid heating
  5. Keep at least 50mm clearance between adjacent breakers
  6. Temperatura mediului ambiant: -5°C până la +40°C; derate above 40°C
  7. Technical Dimensions

Cod produs: 1SDA050999R1

Tip de montare: Fix, conexiune frontală

Polonii: 3P

Lăţime: 90 mm

Înălţime: 130 mm

Adâncime: 70 mm

Sina de montare: 35 mm șină DIN (ÎN 60715)

Terminal Torque: 6 N·m

Greutate netă: 1.12 kg