Wechat: +86-13184948252 Whatsapp: 0086-13811255435 E-mail: kent@bestcontactor.com

Despre Contact |

ABB VBC7-30-01220-240V DC Miniature Reversing Contactor - Contactor,întrerupător de circuit,invertor solar,contor electric,baterii solare

contactor/

ABB VBC7-30-01220-240V DC Miniature Reversing Contactor

Segmentul de modelDescriere
ABBBrand Logo
VBC7Series Name: VBC7 Series Miniature Reversing Contactor (equipped with mechanical interlock, for motor forward and reverse rotation control)
30Main Contact Configuration: 3-pole Normally Open (3NU)
1Auxiliary Contact Configuration: 1 În mod normal închis (1NC)
220-240În DCTensiune de control al bobinei: DC 220-240V
*Special Version Identifier (may be a customized or market-specific version)

  • Detalii despre produs
  1. Interpretarea modelului
Segmentul de modelDescriere
ABBBrand Logo
VBC7Series Name: VBC7 Series Miniature Reversing Contactor (equipped with mechanical interlock, for motor forward and reverse rotation control)
30Main Contact Configuration: 3-pole Normally Open (3NU)
1Auxiliary Contact Configuration: 1 În mod normal închis (1NC)
220-240În DCTensiune de control al bobinei: DC 220-240V
*Special Version Identifier (may be a customized or market-specific version)

Full Model: VBC7-30-01-05 (standard model, corresponding to 220-240V DC coil)

  1. Parametrii tehnici de bază
  2. Basic Electrical Parameters
Element de parametruValoareRemarks
Rated Current of Main Contacts16O (AC-3) / 20O (AC-1)AC-3: Control of 5.5kW three-phase motor at 400V
Rated Operating Voltage690V șiComplies with IEC 60947-4-1 standard
Tensiune de control al bobinei220-240În DCWide voltage range, allowing 卤15% fluctuation
Coil Power ConsumptionPick-up: approx. 5WDC coil operates with no noise or humming
Holding: approx. 5W
Mechanical Service Life10 milioane de operațiuniUnder standard operating conditions
Electrical Service LifeAC-1: 1 milioane de operațiuniUnder rated load
AC-3: 100,000 operațiuni
  1. Indicatori de performanță
Element de parametruValoareApplicable Conditions
Mechanical InterlockBuilt-in reliable mechanical interlockPrevents simultaneous closing of forward and reverse contactors
Overvoltage ProtectionBuilt-in surge suppression diodeProtects coil and control circuit
Switch Position IndicationVisual position markingFacilitates fault diagnosis and status confirmation
Insulation ClassClass FComplies with IEC standards
Evaluare de protecțieIP20Must be installed inside control cabinet
  1. Environmental and Installation Parameters
Element de parametruValoareStandard/Remarks
Temperatura de operare-25℃~+60℃Temperatura de depozitare: -40℃~+85℃
Metoda de montare35mm DIN rail mounting / screw mountingSpace-saving and easy to integrate
Tip terminalScrew terminalsSuitable for 22-10 AWG stranded wires
GreutateApprox. 250gCompact design with light weight

III. Caracteristici funcționale

  1. Dedicated for Reversing Control: Built-in mechanical interlock ensures that forward and reverse contactors cannot be closed simultaneously, ensuring safety and reliability.
  2. Quiet Operation: DC coil design eliminates the humming noise common in AC contactors, enabling silent operation.
  3. Wide Voltage Adaptability: The coil supports a wide voltage range of 220-240V DC, adapting to different power supply conditions.
  4. Overvoltage Protection: Built-in surge suppression diode effectively protects the coil and control circuit from voltage spikes.
  5. Status Indication: Clear switch position indication facilitates on-site operation and fault diagnosis.
  6. Flexible Installation: Supports both DIN rail and screw mounting methods, adapting to various control cabinet layouts.
  7. High Reliability: With a mechanical service life of up to 10 million operations and long electrical service life, it is suitable for frequent operation scenarios.
  8. Domeniul de aplicare
  9. Controlul motorului: Forward and reverse rotation control of three-phase asynchronous motors, ca:

Small conveyors and hoists

Fans and pumps (requiring reversible operation)

Packaging machinery and printing machinery

  1. Automatizare industrială:

Control of auxiliary equipment in production lines

Output actuator for small PLC control systems

Equipment interlock control circuits

  1. Commercial and Building Applications:

Fan control in air conditioning systems

Elevator door motors and small lifting platforms

Automatic door and rolling shutter door control

  1. Other Applications:

Control of battery-powered equipment (compatible with DC coil)

Auxiliary circuits of solar inverters

Small load control in marine and rail transit systems

  1. Selection Suggestions
  2. Potrivirea încărcării:

AC-3 loads (motor starting/operation): Max. 5.5kW (400V), rated current 16A

AC-1 loads (resistive loads): Max. 20O, 690V

  1. Control Voltage Confirmation: Ensure the coil voltage matches the system DC power supply (220-240În DC).
  2. Auxiliary Contact Requirements: Standard configuration is 1NC; for more contacts, select the VBC7-30-10 series (1NU) or expansion modules.
  3. Installation Environment:

Derating is required when the temperature exceeds 40℃ (rated current decreases by 10% for every 10℃ rise)

Additional protective measures are needed in dusty and humid environments

  1. Accessory Selection:

It is recommended to match with a surge suppressor (built-in for DC coils)

Optional auxiliary contact modules and thermal overload relays (de ex., TA25DU series)

  1. Modele alternative:

Non-reversing version: BC7-30-01-05 (without mechanical interlock)

Different coil voltages: VBC7-30-01-01 (24În DC), VBC7-30-01-07 (12În DC)

  1. Depanare
Fenomen de eroareCauze posibileTroubleshooting Methods
Contactor fails to pull in1. No voltage or low voltage at the coil1. Check the control circuit voltage (220-240În DC)
2. Coil burnout2. Measure the coil resistance (approx. 10k惟 under normal conditions)
3. Mechanical jamming3. Inspect contacts and mechanical mechanism, and remove foreign objects
Contactor releases immediately after pulling in1. Excessive voltage fluctuation1. Stabilize the control voltage and check the power supply capacity
2. Poor coil contact2. Tighten the coil terminals
3. Overload protection activation3. Check the status of the thermal overload relay
Contact heating/welding1. Load current exceeds the rated value1. Replace with a contactor of larger capacity or use it with derating
2. Contact oxidation or contamination2. Clean or replace the contacts
3. Frequent overload operation3. Inspect the load and eliminate overload causes
Interlock failure1. Damage to the mechanical interlock mechanism1. Inspect the interlock mechanism and replace if necessary
2. Improper installation leading to interlock release2. Reinstall to ensure proper engagement of the interlock mechanism
Severe coil heating1. Excessively high voltage1. Adjust the control voltage to the rated range
2. Coil short circuit2. Measure the coil resistance and replace the damaged coil
3. High ambient temperature3. Improve heat dissipation conditions and reduce the ambient temperature

VII. Installation and Wiring Key Points

  1. Înainte de instalare, confirm that the coil voltage is 220-240V DC, matching the control power supply.
  2. For reversing control, ensure that the mechanical interlock of the two contactors (forward/reverse) is correctly installed to prevent phase-to-phase short circuit.
  3. Main circuit wiring: Connect L1, L2, L3 to the power supply, and T1, T2, T3 to the motor; pay attention to the phase sequence (when switching between forward and reverse rotation).
  4. Control circuit wiring: Connect coil terminals A1 and A2 to the 220-240V DC power supply; pay attention to polarity (some models have no polarity requirements).
  5. Auxiliary contact wiring: The 1NC contact can be used for interlock control or status indication; pay attention to the rated current of the contact (usually 5A).
  6. Installation spacing: Keep a distance of at least 5mm from other components to ensure good heat dissipation.
  7. Pre-power-on inspection:

Check if the mechanical interlock operates flexibly and reliably

Check if the contacts are in good contact

Check if the coil wiring is correct

ABB VBC7-30-01 Core Parameter and Price Comparison Table with Same Series and Competitor Models

  1. Comparison of ABB Same Series Models (Core Parameters)
Element de parametruVBC7-30-01-05VBC7-30-10-05BC7-30-01-05Difference Description
(220-240În DC)(220-240În DC)(220-240În DC)
TipMiniature reversing contactorMiniature reversing contactorMiniature non-reversing contactorVBC7 with mechanical interlock; BC7 without interlock
Main Contacts3NU (3-stâlp deschis în mod normal)3NU (3-stâlp deschis în mod normal)3NU (3-stâlp deschis în mod normal)Identical
Contacte auxiliare1NC (1 în mod normal închis)1NU (1 deschis în mod normal)1NC (1 în mod normal închis)Different auxiliary contact types
Curent nominal16O (AC-3) / 20O (AC-1)16O (AC-3) / 20O (AC-1)16O (AC-3) / 20O (AC-1)Identical, suitable for 5.5kW (400V) motor
Tensiune nominală690V și690V și690V șiIdentical
Tensiunea bobinei220-240În DC220-240În DC220-240În DCIdentical, DC operation with no noise
Mechanical InterlockBuilt-in reliable mechanical interlockBuilt-in reliable mechanical interlockNoneExclusive to VBC7 series, preventing simultaneous closing of forward and reverse contactors
Surge ProtectionBuilt-in suppression diodeBuilt-in suppression diodeBuilt-in suppression diodeIdentical
Metoda de montareDIN rail / screw mountingDIN rail / screw mountingDIN rail / screw mountingIdentical
Mechanical Service Life10 milioane de operațiuni10 milioane de operațiuni10 milioane de operațiuniIdentical
Electrical Service LifeAC-3: 100,000 operațiuniAC-3: 100,000 operațiuniAC-3: 100,000 operațiuniIdentical
AC-1: 1 milioane de operațiuniAC-1: 1 milioane de operațiuniAC-1: 1 milioane de operațiuni
Evaluare de protecțieIP20IP20IP20Identical, must be installed inside control cabinet
Reference PriceApprox. 380-450Approx. 380-450Approx. 320-380BC7 is slightly cheaper; VBC7-30-01 and 30-10 are similarly priced
  1. Comparison of ABB VBC7-30-01 with Competitor Models (Core Parameters + Preţ)
Element de parametruABB VBC7-30-01-05Schneider LC1D18FDSiemens 3RT2016-1BB41+3RT2016-1BB41Selection Suggestion
(220-240În DC)(Reversing, 220În DC)(Reversing Combination, 220În DC)
Brand SeriesABB VBC7 SeriesSchneider LC1D SeriesSiemens 3RT2 Series
TipIntegrated reversing contactorIntegrated reversing contactorDual-contactor combinationABB/Schneider integrated design saves more space
(with mechanical interlock)(with mechanical interlock)(external mechanical interlock required)
Main Contacts3NU (3-stâlp deschis în mod normal)3NU (3-stâlp deschis în mod normal)3NO+3NO (dual contactors)Identical
Contacte auxiliare1NC1NU+1NC1NU+1NC (per contactor)Schneider/Siemens have more abundant auxiliary contacts
Curent nominal16O (AC-3) / 20O (AC-1)18O (AC-3) / 25O (AC-1)9O (AC-3) / 12O (AC-1)Schneider has higher rated current, suitable for 7.5kW motor
Applicable Motor Power5.5kW (400V AC-3)7.5kW (400V AC-3)4kW (400V AC-3)Schneider supports higher power
Tensiunea bobinei220-240În DC220În DC220În DCIdentical, DC operation with no noise
Mechanical InterlockBuilt-in, reliable and durableBuilt-in, long mechanical service lifeExternal required, increased costABB/Schneider are more convenient to use
Surge ProtectionBuilt-in suppression diodeBuilt-in varistorBuilt-in varistorIdentical protection function
Metoda de montareDIN rail / screw mountingDIN rail / screw mountingDIN rail / screw mountingIdentical
Mechanical Service Life10 milioane de operațiuni10 milioane de operațiuni10 milioane de operațiuniIdentical
Electrical Service LifeAC-3: 100,000 operațiuniAC-3: 100,000 operațiuniAC-3: 100,000 operațiuniIdentical
AC-1: 1 milioane de operațiuniAC-1: 1 milioane de operațiuniAC-1: 1 milioane de operațiuni
Evaluare de protecțieIP20IP20IP20Identical, must be installed inside control cabinet
Width Dimension45mm55mm45mm*2 (dual contactors)ABB has the smallest volume
Reference PriceApprox. 380-450Approx. 420-480Approx. 450-520 (dual contactors)ABB offers the best cost performance
AvantajeIntegrated design, quiet operation, smallest volumeHigh rated current, abundant auxiliary contactsSiemens ecosystem compatibility, strong diagnostic functionsSelect according to load power and space constraints

III. Price and Selection Replacement Summary

  1. Same Series Replacement Recommendations
Original ModelReplacement ModelReplacement ReasonNote
VBC7-30-01-05VBC7-30-10-05Different auxiliary contact type (1NC→1NO)Confirm auxiliary contact requirements in the control circuit
VBC7-30-01-05BC7-30-01-05Lower price for non-reversing applicationsNot suitable for forward/reverse control, no mechanical interlock
VBC7-30-01-05VBC7-30-01-01Different coil voltage (220V DC→24V DC)Must match the system control power supply voltage
  1. Cross-Brand Replacement Recommendations
Original ModelOptimal ReplacementAlternative ReplacementReplacement Advantages
VBC7-30-01-05Schneider LC1D18FDSiemens 3RT2016 CombinationHigher rated current and applicable power
VBC7-30-01-05ABB VBC7-30-10-05Schneider LC1D12FDBetter compatibility with the same brand, no need to adjust installation dimensions
  1. Key Selection Points
  2. Potrivirea încărcării: Select the corresponding rated current for standard loads; for heavy-duty applications, it is recommended to choose one size larger (de ex., VBC7→Schneider LC1D25FD).
  3. Control Voltage: Ensure the coil voltage matches the system DC power supply (220-240În DC).
  4. Contacte auxiliare: Select 1NC/1NO or versions with more contacts according to the control circuit requirements.
  5. Installation Space: Integrated reversing contactors (ABB VBC7/Schneider LC1D) save about 40% space compared to dual-contactor combinations.
  6. Cost Control: Same-brand replacement has the lowest cost; cross-brand replacement needs to consider installation adaptability and system compatibility.

Prev:

Următorul:

Lasă un răspuns

Lăsaţi un mesaj