Protector de supra/subtensiune și supracurent AVP-63

AVP-63 Single-phase Adjustable Dual-display Auto-reset Over/Under Voltage + Overcurrent Protector Note: AVP-63 is a general model, not exclusive to one brand. Many electrical manufacturers in China produce this same design. It is a popular export DIN rail protection module. Tip: Single-phase 2P, Montare pe șină DIN, dual digital display (Voltaj + actual), parametrii reglabili, auto-reset protector ...

  • Detalii despre produs

AVP-63 Single-phase Adjustable Dual-display Auto-reset Over/Under Voltaj + Protector de supracurent

Nota: AVP-63 is a general model, not exclusive to one brand. Many electrical manufacturers in China produce this same design. It is a popular export DIN rail protection module.

Tip: Single-phase 2P, Montare pe șină DIN, dual digital display (Voltaj + actual), parametrii reglabili, auto-reset protector

Funcții: Protecție la supratensiune, protectie la subtensiune, overload overcurrent protection, power restoration delay. It automatically closes after voltage returns to normal, no manual reset required.

Specificații tehnice standard (Mainstream Version)

Tensiune nominală: AC230V / 50Hz (compatible with 220V mains)

Curent nominal: Continuously adjustable from 1~80A, default 63A

Overvoltage Threshold: Adjustable 230~300V (factory default commonly 280V)

Undervoltage Threshold: Adjustable 140~210V (factory default commonly 160/170V)

Restoration Delay: Adjustable 1~400s, default 30s

Consumul de energie: ≤2W

Dimensiuni generale: Aproximativ. 85×36×66 mm

Montare: 35mm șină DIN standard

Certificari: Most versions carry CE; some domestic units can obtain CCC

Cod HS: 8536500000 (switching protection electrical apparatus)

Principiul de funcționare

  1. When voltage/current exceeds the set threshold → trip and cut off power immediately
  2. Fault cleared and voltage back within normal range → wait for configured delay then auto-close to restore power
  3. Dual screens display real-time voltage and output current; panel keys SET + UP/DOWN for parameter configuration

Scenarii tipice de aplicare

Distribuția energiei rezidențiale, photovoltaic grid-tie side, small industrial control, communication power supplies, commercial equipment, overseas single-phase power distribution projects (widely used in Southeast Asia and Central Asia)

Selectarea modelului & Note de înlocuire

Domestic well-known auto-reset over/under voltage protectors (without current display): alternatives from Delixi, Chint, Tengen are available, but they lack current monitoring and adjustable dual-display interface

When replacing AVP-63, confirm three priorities: ① whether overcurrent protection is required ② whether local digital parameter setting is needed ③ whether auto-reset delay is mandatory

Firmware parameter ranges differ between manufacturers (a few versions support undervoltage limit down to 80V). Verify datasheet before purchase.

Defecte comune

Fără afișare după pornire: live/neutral reversed, missing supply voltage

Deplasări false frecvente: thresholds set too close to normal voltage, large line surges

No power restoration after fault clears: delay set to maximum value, internal relay damaged

AVP-63 Panel Key Operation Steps (Mainstream Version, SET / ▲ / ▼ / Power Key)

Panou: Upper screen = Voltage V, Lower screen = Current A; 4 chei: SET, ▲ Up, ▼ Down, ⏻ Manual on/off key

⚠️ Safety Warning: Risk of electric shock during live commissioning; isolate upstream circuit breaker before maintenance

  1. Basic Operation Procedure
  2. Stare de așteptare: After power on, dual screens show real-time voltage and current
  3. Enter Parameter Menu: Long press SET for 3 secunde, screen shows R1 (parameter code) to enter setting mode
  4. Switch Parameter Items: Short press SET to cycle through R1~R12
  5. Modify Value: When the target parameter flashes, press ▲ to increase, ▼ to decrease
  6. Confirm and Next Item: Short press SET to save and jump to next parameter
  7. Exit Setting: After all adjustments, long press SET for 3 seconds to exit, or wait 8~10 seconds for auto-save and exit
  8. Manual Close / excursie: Short press ⏻ power key to directly control output on/off, without modifying protection thresholds
  9. Parameter Sequence (R1~R12, General Domestic Firmware)
Cod parametruNume parametruInterval reglabilDefault Value
R1Power-on Delay (waiting time before closing after energization)1~500s10s
R2Overvoltage Trip Value230~300V270V
R3Overvoltage Recovery Value (voltage must drop below this to enable reset)225~295V265V
R4Overvoltage Restoration Delay1~500s30s
R5Overvoltage Action Delay (delay before tripping once overvoltage threshold is exceeded)0.1~30 de ani1s
R6Undervoltage Trip Value140~210V170V
R7Undervoltage Recovery Value145~215V175V
R8Undervoltage Restoration Delay1~500s30s
R9Undervoltage Action Delay0.1~30 de ani1s
R10Overcurrent Protection Value1~63A63O
R11Overcurrent Restoration Delay1~500s30s
R12Overcurrent Action Delay0.1~30 de ani1s
  1. Funcții suplimentare (Password Lock on Some Versions)

Password item P19 appears at the end of menu; parola implicită 112. If password mismatch, only view access, modification locked

When locked, long pressing SET only allows browsing parameters; intra 112 to unlock editing

Some units support auto-reset toggle: P16, Con = Auto Reset, OFF = Manual Close (must press power key to restore after fault)

  1. Fault Code Indication

OL: Deplasare la supracurent

OH: Overvoltage Trip

UL: Declanșare subtensiune

After fault, power restores automatically when voltage/current returns to normal and delay expires. If manual mode is enabled, press ⏻ key to restore power.

  1. Quick Setting Example (General Household 220V)
  2. Long press SET for 3s to enter menu
  3. R2 Overvoltage: 270V; R6 Undervoltage: 170V
  4. R10 Overcurrent: 63O
  5. R1 Power-on delay 10s, R4/R8/R11 restoration delay 30s
  6. Long press SET to exit, configuration completed
  7. Setting Troubleshooting
  8. SET no response: panel locked by password, faulty key, tensiune de alimentare insuficientă
  9. Settings not saved: do not cut power before exit; wait for auto-exit or long press SET to confirm
  10. Deplasări frecvente: action delay R5/R9/R12 set too short, or thresholds set too close to normal voltage

Avertisment de siguranță: Risk of electric shock during live testing. Professional function test is recommended using adjustable AC power supply (variac). Do NOT forcibly raise mains voltage for overvoltage test.

Testing sequence: Inspecție vizuală & power-on self-test → Display & manual switching test → Parameter read-write verification → Protection function validation → Long-term load stability test

  1. Initial Power-on Check (On-site, No Special Instrument Required)
  2. Porniți, screens light up; upper screen shows voltage, lower screen shows current
  3. Use multimeter to measure input IN voltage, compare with protector reading: deviation normally ≤±5V. Larger deviation indicates faulty sampling circuit
  4. Measure output OUT with multimeter:

Normal closed state: IN and OUT voltage nearly equal

Tripped by protection: 0V at OUT

  1. Indicator definition:

POWER green ON: unit power supply normal

V red ON: Overvoltage fault (OH)

<V red ON: Undervoltage fault (UL)

A red ON: Overcurrent fault (OL)

  1. Manual switching test: short press ⏻ key, output turns on/off accordingly, key response normal

Abnormal conditions: black screen after power-up, garbled flashing, keys unresponsive, green power light ON but no output → likely damaged

  1. Parameter Read-write Verification (Check Mainboard & Memory Integrity)
  2. Long press SET for 3s to enter menu, can cycle through R1~R12 normally
  3. Values can be modified; after saving and exiting, re-enter menu to confirm parameters retained
  4. If password lock activated, modification allowed after correct password input; locked mode only supports viewing, which is normal

Anormal: parameters revert after exit, menu jumps randomly → firmware / eșec de memorie

  1. Protection Function Validation (Precise Test, Variac Required)

1) Overvoltage Protection Test

  1. Connect adjustable power supply to AVP-63 input
  2. Set R2 overvoltage trip value to 270V
  3. Slowly increase input voltage. After exceeding threshold plus action delay, protector trips, shows OH, >V red light ON, output cuts off
  4. Reduce voltage below R3 overvoltage recovery value, wait for restoration delay, auto-close and restore power

2) Undervoltage Protection Test

  1. Set R6 undervoltage trip value to 170V
  2. Slowly reduce input voltage. Below threshold plus action delay, protector trips, shows UL, <V red light ON
  3. Raise voltage above R7 undervoltage recovery value, power restores automatically after delay

3) Overcurrent Protection Test (Adjustable Load / Current Source Required)

  1. Set R10 overcurrent value e.g. 20O
  2. Gradually increase load current. When current exceeds threshold plus action delay, protector trips, shows OL, >A red light ON
  3. Current drops below recovery level, power restores automatically after delay

Acceptance criteria: actual action threshold matches configured value; no missing trip or spurious trip. Auto-restore after fault cleared and delay completed.

  1. Simple Field Test Without Variac (Emergency Site Check)
  2. Power cycle the unit, observe power-on delay: it closes after R1 configured time, not instantly
  3. Run under rated load for a period: current reading stable, no overheating, no random tripping
  4. Apply mild overload for a short time (safety priority) to verify OL trigger

⚠️ Do NOT test by forcing mains voltage high, risk of equipment burnout

  1. Long-term Stability & Inspecție vizuală

No bulging, burn marks on enclosure; terminal blocks no discoloration or overheating

Readings stable under load, no random fault codes

No frequent false tripping: if OH/UL alarms persist with stable mains, either sensitive threshold setting or faulty sampling board

  1. Quick Diagnosis Summary Table
FenomenConcluzie
Power-on display normal, keys responsive, input/output voltage consistent, parameters savedBasically functional
Trips at set thresholds, auto-restores after delayFully functional
Display normal, no output even after manual closeInternal relay failed / welded
Random OH/UL alarms with normal voltage, frequent trippingSampling circuit fault or improper threshold setting
Black screen, garbled display, keys fully unresponsiveMainboard damaged
Modified parameters cannot be savedMemory chip failure
  1. Notă suplimentară

AVP-63 cannot replace circuit breaker for short-circuit protection. It only provides over/under voltage and overload protection. Short-circuit protection must be provided by upstream circuit breaker. Upstream breaker must be retained as backup during testing.