Explicația modelului
Meaning of each part in CJX1-475/22:
| Part | Explanation |
| CJX1 | contactor AC series with design serial number 1 (equivalent to Siemens 3TF series) |
| 475 | Rated operating current of 475A at the rated operating voltage of 380V under AC-3 duty |
| 22 | Auxiliary contact configuration: 2 Deschis normal (NU) + 2 În mod normal închis (NC) |
- Parametrii tehnici de bază
| Parametru | Valoare | Observații |
| Tensiune nominală de izolație | 660V/1000V | Complies with GB/T 14048.4 și IEC 60947-4-1 standardele |
| Tensiune nominală de operare | 380V (Sarcina AC-3) | Suitable for 50Hz/60Hz AC circuits |
| Curent nominal de operare | 475O | Rated value at 380V under AC-3 duty |
| Numărul de pol | 3P (3-pol) | 3 normally open main contacts |
| Contacte auxiliare | 2NU+2NC | Configurație standard |
| Control Coil Voltage | 220VAC/380VAC/110VAC, etc. | Must be clearly specified when placing an order |
| Coil Frequency | 50Hz/60Hz | Adaptable to power grids in different regions |
| Viața mecanică | ≥10 million operations | High reliability design |
| Viața electrică | ≥1 million operations | Under AC-3 duty |
| Metoda de montare | Bolt mounting | Models of 45A and above adopt bolt mounting, DIN rail mounting not supported |
| Sistem de stingere a arcului | Molded arc extinguishing chamber + arc barrier | Effectively extinguishes electric arcs and protects contacts |
| Main Contact Material | Silver alloy | High temperature resistance, arc resistance and corrosion resistance |
III. Caracteristici funcționale
- Scenarii de aplicare: Mainly used for remote making and breaking of circuits, controlling the start, stop and reversal of AC motors. It is suitable for high-power motor control in industrial automation, power transmission, heavy machinery and other fields.
- Structural Advantages:
Modular design for easy maintenance; F3 and F4 auxiliary contact blocks can be assembled for function expansion.
Fully enclosed arc extinguishing system improves operational safety and reduces the impact of electric arcs on surrounding components.
High-strength insulating housing with good flame retardancy, complying with safety standards.
- Avantaje de performanță:
High rated current, capable of controlling three-phase asynchronous motors with a power of about 250kW (380V, AC-3).
Optimally designed electromagnetic system with low power consumption, low noise and reliable operation.
Can form an electromagnetic starter with thermal overload relays to realize motor overload protection.
- Installation and Commissioning Guide
- Installation Preparation
Confirm that the product model and specifications are consistent with the design requirements; check for no appearance damage and complete accessories.
The installation environment shall be free of flammable and explosive gases, no moisture condensation; temperature range -5℃~+40℃, relative humidity ≤90%.
Power must be cut off before installation to ensure safety.
- Etape de instalare
- Select a suitable installation position and reserve sufficient space for heat dissipation and operation.
- Fix the contactor with M8-M10 bolts, and the tightening torque shall comply with the requirements of the product manual.
- Cablajul circuitului principal: Connect the three main contacts to the three-phase power supply and load; fasten the wiring terminals tightly to avoid heating due to loosening.
- Cablajul circuitului de control: Connect the coil terminals to the control power supply, and the auxiliary contacts to the control circuit (precum circuitele de autoblocare și interblocare).
- Check the correctness of wiring to ensure no short circuit or reverse connection in the main and control circuits.
- Commissioning Key Points
- Measure the coil resistance before power-on to confirm no open circuit or short circuit fault of the coil.
- Observe whether the contactor operates smoothly and has no abnormal noise during the first power-on.
- Check whether the on-off state of the main and auxiliary contacts is correct and the contact is good.
- Test the operation of the contactor under rated load and check whether the temperature rise is within the allowable range.
- Defecțiuni comune și depanare
| Fenomen de eroare | Cauze posibile | Troubleshooting Methods |
| Contactor fails to pull in | 1. No voltage or low voltage on the coil | 1. Check the control power supply and wiring |
| 2. Colac ars | 2. Measure the coil resistance and replace the coil if necessary | |
| 3. Blocaj mecanic | 3. Check mechanical components and remove foreign objects | |
| 4. Circuit deschis în circuitul de control | 4. Troubleshoot the control circuit and repair the open circuit point | |
| Loud noise after pull-in | 1. Oil stain or dust on the iron core contact surface | 1. Clean the iron core contact surface |
| 2. Broken short-circuit ring | 2. Replace the iron core or short-circuit ring | |
| 3. Low coil voltage | 3. Adjust the control power supply voltage to the rated value | |
| Overheating or welding of contacts | 1. Poor contact of contacts | 1. Check the contacts, remove the oxide layer and replace if necessary |
| 2. Excessive load current | 2. Verify the load and replace the contactor with a larger capacity | |
| 3. Frecvență de operare excesiv de mare | 3. Reduce the operating frequency or select a suitable contactor | |
| 4. Fault of the arc extinguishing system | 4. Check the arc extinguishing cover and ensure correct installation | |
| Defecțiunea contactelor auxiliare | 1. Severe wear of contacts | 1. Replace the auxiliary contact block |
| 2. Loose wiring | 2. Check and fasten the wiring | |
| 3. Oxidation of contacts | 3. Clean the contact surface |
- Alternative Models and Compatibility
- Intra-series Alternatives:
CJX1-475/02: 0 Deschis normal + 2 Normally Closed auxiliary contacts
CJX1-475/40: 4 Deschis normal + 0 Normally Closed auxiliary contacts
CJX1-475/44: 4 Deschis normal + 4 Normally Closed auxiliary contacts
- Cross-brand Alternatives:
Siemens: 3TF56 series (de ex., 3TF5622-0XQ0), fully compatible in mounting dimensions and electrical performance
Delicios: CJX1-475/22, intra-series product with consistent technical parameters
Schneider: LC1-D series (mounting dimensions and electrical parameters need to be verified)
VII. Ordering and Usage Notes
- The following must be clearly specified when placing an order: complete model (including auxiliary contact configuration), rated control power supply voltage and frequency of the coil, and quantity.
- Example: 10 units of CJX1-475/22 AC contactor with coil voltage of 220V 50Hz.
- F3 and F4 auxiliary contact blocks can be assembled for function expansion, which must be additionally indicated when placing an order.
- Do not touch live parts during use; power must be cut off for maintenance or inspection.
- Do not use the contactor after removing the arc extinguishing cover to avoid arc hazards.
Comprehensive Guide to Cross-brand Equivalent Models of Chint CJX1-475/22
CJX1-475/22 is a Chint AC contactor with 475A 3-pole and 2NO+2NC auxiliary contacts, equivalent to Siemens 3TF57 series. The following is the detailed introduction of precise alternative models and compatibility of mainstream brands.
- Overview of Core Equivalent Models (by Brand)
| Marca | Equivalent Model | Key Matching Points | Compatibility Description |
| Siemens | 3TF5722-0XQ0 | AC-3 475A/380V | Fully compatible in mounting dimensions and electrical performance, the prototype of CJX1 series |
| 3TF5744-0XQ0 | 2NU+2NC (or 4NO+4NC) | ||
| Delicios | CJX1-475/22 | Consistent parameters and series | 100% interchangeable with the same mounting hole positions |
| Shanghai People’s | CJX1-475/22 | Consistent parameters or equivalent capacity | Direct interchange for CJX1 series; mounting dimensions need to be verified for CJX2 series |
| CJX2-D470/22 | |||
| Schneider | LC1-D475/22 | AC-3 475A | Matched electrical parameters with slight differences in mounting dimensions, re-drilling required |
| LC1-F475/22 | 2NU+2NC | ||
| ABB | A500-30-11+AX | Rated current of 500A | Slightly larger capacity, AX series 2NO+2NC auxiliary contact block required |
| A500-30-02+AX | Auxiliary contact block to be additionally installed | ||
| Changshu Switch | CK3-475/22 | AC-3 475A | Co-designed with consistent parameters and compatible mounting dimensions |
| 2NU+2NC | |||
| LS Electric | GMC-400/475 | 400A/475A optional | Matched electrical performance with basically consistent mounting hole positions |
| Standard 2NO+2NC | |||
| Taixi Electric | CJX1-475/22 | Consistent parameters and series | Fully interchangeable with Chint products |
- Detailed Alternative Information of Each Brand
- Siemens (Prototype Brand)
Standard Alternative: 3TF5722-0XQ0 (2NU+2NC), 3TF5744-0XQ0 (4NO+4NC)
Technical Matching: AC-3 475A/380V, rated insulation voltage 1000V, mechanical life 10 milioane de operațiuni, electrical life 1 milioane de operațiuni
Note: The 3TF57 series has been discontinued; the upgraded alternative is the 3RT1076 series (500O), which is compatible in electrical performance but different in mounting dimensions.
- Domestic Intra-series (Direct Interchange)
Delicios: CJX1-475/22, coil voltage optional 220V/380V, fully interchangeable with Chint products, and can share auxiliary contact blocks (F3/F4).
Shanghai People’s/People’s Electric Appliance: CJX1-475/22, intra-series design with the same contact material and arc extinguishing system as Chint.
Other Domestic Brands: CJX1-475/22 of Xinli, Great Wall and other brands are all produced based on Siemens 3TF57 technical standards with good interchangeability.
- International Brand Alternatives (Parameter Matching)
Schneider: LC1-D475/22, rated current 475A, auxiliary contacts 2NO+2NC, fully matched electrical parameters; however, the mounting method is standard DIN rail + bolt mounting, slightly different from the pure bolt mounting of CJX1.
ABB: A500-30-11+AX22 is recommended (AX22 auxiliary contact block needs to be additionally installed to realize 2NO+2NC). The A500 series has a rated current of 500A with slightly larger capacity, suitable for heavy-duty occasions.
LS Electric: GMC-475, rated current 475A, standard configuration of 2NO+2NC auxiliary contacts, mounting dimensions basically compatible with CJX1 with a wide range of optional coil voltages.
- Changshu Switch (Domestic High-end Brand)
Equivalent Model: CK3-475/22, AC-3 475A, 2NO+2NC auxiliary contacts
Caracteristici: Adopts silver-tungsten alloy contacts with excellent arc extinguishing performance; mechanical life up to 12 milioane de operațiuni, higher than the industry standard, suitable for frequent operation occasions.
III. Key Notes for Alternative Model Selection
- Electrical Parameter Matching
Ensure the rated current ≥475A under AC-3 duty and the rated insulation voltage ≥660V.
The control coil voltage must be consistent with the original system (de ex., 220V/380V/110V), compatible with 50Hz/60Hz frequency.
- Mounting Compatibility
Intra-series products such as Siemens 3TF57, Delixi CJX1 and Shanghai People’s CJX1 have completely consistent mounting hole positions and can be directly replaced.
Schneider LC1-D, ABB A series and others need to recheck the mounting dimensions, and the installation position may need to be adjusted.
CJX1-475/22 adopts bolt mounting (DIN rail mounting not supported), so attention should be paid to the matching of mounting methods during replacement.
- Configurarea contactelor auxiliare
Ensure the alternative model is equipped with 2NO+2NC auxiliary contacts; if not, it can be realized by installing additional auxiliary contact blocks (de ex., F3/F4).
The main contactors of some brands (de ex., ABB) are default configured with 1NO+1NC, and additional auxiliary contact modules need to be ordered.
- Arc Extinguishing System and Operating Frequency
The arc extinguishing system of the alternative product shall comply with IEC 60947-4-1 standard to ensure the arc extinguishing effect.
When the operating frequency is higher than 600 operations per hour, it is recommended to derate the usage or select a special high-frequency contactor.
- Priority of Recommended Alternative Schemes
- First Choice: Delixi CJX1-475/22, Shanghai People’s CJX1-475/22 (domestic intra-series, 100% interchangeable with low cost)
- Second Choice: Siemens 3RT1076 series (upgraded model of the original 3TF57, reliable quality, suitable for key equipment)
- Alternative Choice: Schneider LC1-D475/22, ABB A500+AX22 (international brands with excellent performance, suitable for high-end applications)
Contactor,întrerupător de circuit,invertor solar,contor electric,baterii solare



















NH42-63-318x560.png)