Chint NA1-3200X-3200M/3P Air Circuit Breaker

  Code Segment Description NA1 Series code for Chint air circuit breakers (ACB) 3200 Frame rated current: 3200O (maximum current specification of the breaker) X Breaking capacity grade: Class X (100cel); distinguished from standard type (80cel) and Class H (120cel) 3200 Rated operating current: 3200O (actual set working current) M Trip unit type: Intelligent trip ...

  • Detalii despre produs

 

Segment de codDescriere
NA1Series code for Chint air circuit breakers (ACB)
3200Frame rated current: 3200O (maximum current specification of the breaker)
XBreaking capacity grade: Class X (100cel); distinguished from standard type (80cel) and Class H (120cel)
3200Rated operating current: 3200O (actual set working current)
MTrip unit type: Intelligent trip unit (Micrologic); distinguished from standard Type L and high-breaking Type H
3PPole number: 3-pol (3-phase circuit protection, without neutral pole)
  1. Specificații tehnice de bază
Categoria parametrilorTechnical Data
Tip de produsIntelligent low-voltage air circuit breaker (ACB)
Tensiune nominală de funcționareAC 400V/690V, 50Hz
Cadrul curent (Iu)3200O
Curent nominal de operare (În)3200O
Rated Ultimate Short-circuit Breaking Capacity (Icu)100cel (Class X @ 400V)
Rated Service Short-circuit Breaking Capacity (Ics)100cel (equal to Icu)
Curent nominal de rezistență de scurtă durată (Icw)80cel (1s)
Unitatea de deplasareType M intelligent trip unit, featuring long-time delay overload, short-time delay short-circuit and instantaneous short-circuit protection
Tip de montareDraw-out or fixed type (X series is generally draw-out)
Modul de operareManual or motorized (motor operating mechanism optional)
Control Circuit VoltageAC 220V/380V or DC 220V (opțional)
Contacte auxiliareStandard: 5NU + 5NC (expandable)
Ingress ProtectionIP30 (conform GB/T 4942.2)
Standarde aplicabileGB/T 14048.2, IEC/EN 60947-2
Dimensiuni (H×W×D)Tip extras: aproximativ. 600mm×400mm×1000mm (refer to official manual for exact data)
GreutateAproximativ. 80~100kg (varies by mounting type and accessory configuration)
  1. Caracteristici de bază

3.1 Intelligent Protection System

Three-stage protection: Long-time delay for overload (inverse time characteristic), short-time delay for short circuit (selectable fixed/inverse time), and instantaneous short-circuit protection, precisely matching power distribution system requirements.

Earth fault protection: Residual current protection optional, sensitivity adjustable from 0.03A to 1A.

Adjustable protection parameters: Flexible parameter configuration via intelligent controller to adapt to diverse load characteristics.

Fault recording: Automatically stores the latest 10 fault records including fault type, current value and time for rapid troubleshooting.

3.2 High Reliability Design

High Class X breaking capacity: 100kA short-circuit breaking capacity to ensure reliable disconnection under severe short-circuit faults and guarantee equipment safety.

Optimized arc extinguishing system: Adopts multi-break and longitudinal seam arc extinguishing technology for rapid arc extinction and fast recovery after breaking.

Long service life: Mechanical durability up to 10,000 operațiuni; electrical durability up to 5,000 operațiuni.

Vibration and shock resistance: Compliant with GB/T 14048.2 to adapt to harsh industrial environments.

3.3 Flexible Expandability

Rich optional accessories: Excursie cu șunt, declanșare la subtensiune, closing solenoid, motor charging mechanism, contacte auxiliare, contacte de alarmă, key lock, etc.

Extended communication: Optional Modbus-RTU, Profinet, EtherNet/IP modules for remote monitoring and intelligent power distribution management.

Interlock functions: Cable interlock and connecting rod interlock available to meet electrical and mechanical interlock requirements.

  1. Compatible Equipment & Scenarii de aplicare

Compatible Equipment

Distribution transformer: Main protection switch for low-voltage side of transformers

Generator set: Protection switch for generator outgoing circuits

Busbar system: Bus section protection and tie control

Large motor: Incoming switch for Motor Control Center (MCC)

UPS system: Protection switch for UPS input and output circuits

Scenarii de aplicare

  1. Distribuția de energie industrială: Main power distribution systems for factories, workshops and production lines.
  2. Commercial building power distribution: Main and floor power distribution for shopping malls, hotels and high-rise buildings.
  3. Centre de date: Mission-critical areas requiring high power supply reliability such as server rooms and cloud computing centers.
  4. New energy industry: Low-voltage power distribution systems for photovoltaic power stations and wind farms.
  5. Infrastructură: Power distribution systems for transportation hubs including airports, subways and railways.
  6. Comparație de modele
ModelCapacitate de rupereCurent nominalUnitatea de deplasareAplicație
NA1-3200-3200M/3P80cel (Standard)3200OType M IntelligentGeneral industrial distribution with low short-circuit current
NA1-3200X-3200M/3P100cel (Class X)3200OType M IntelligentIndustrial sites with high short-circuit current and high breaking capacity requirements
NA1-3200H-3200M/3P120cel (Class H)3200OType M IntelligentLarge industrial enterprises and grid connection points with extreme short-circuit current
NA1-3200X-2500M/3P100cel (Class X)2500OType M Intelligent3200A frame with actual load current of 2500A
NA1-3200X-3200L/3P100cel (Class X)3200OType L StandardGeneral scenarios with basic protection demands
  1. Cross-Brand Equivalent Model Comparison
ChintSiemensSchneiderABBMitsubishi
NA1-3200X-3200M/3P3WL2N32 ETU25B 3PMT32H1 3P 3200A Micrologic 5.0EMAX2 E3S3200 R100 3PAE3200-SW 3P F 3200A
Capacitate de rupere100cel100cel100cel85cel
Unitatea de deplasareType M IntelligentETU25B IntelligentMicrologic 5.0 IntelligentStandard Intelligent Trip
Tip de montareRetragere / FixRetragere / FixRetragere / FixRetragere / Fix
ComunicareOptional Modbus / ProfinetOptional Profinet / EtherNet/IPOptional Modbus / ProfinetCC-Link opțional / Profinet
  1. Selecţie & Application Guidelines
  2. Breaking capacity matching: Select proper grade according to system short-circuit current calculation (Standard 80kA, Class X 100kA, Class H 120kA).
  3. Rated current selection: Determine operating current based on total load current and future expansion; optional ratings under 3200A frame: 2000O, 2500O, 3200O.
  4. Trip unit selection: Type M intelligent trip for most industrial and commercial applications; Type L standard trip for simple protection requirements.
  5. Tip de montare: Draw-out type for easy maintenance and replacement (critical circuits); fixed type for cost-effective general circuits.
  6. Operation mode: Manual for small-capacity and infrequent operation; motorized for large-capacity, frequent operation and remote control.
  7. Accessory configuration: Select shunt trip, declanșare la subtensiune, auxiliary contacts and communication modules as required by control and protection logic.
  8. Întreţinere: Regularly inspect mechanical mechanisms, arc extinguishing chambers and contact wear to ensure long-term stable operation.

Chint NA1-3200X-3200M/3P Complete Accessory List & Selection Codes

  1. Core Control Accessories (Essential for Control Circuit)

1.1 Shunt Trip (F)

Used for remote breaker tripping, applicable to emergency shutdown and automatic control systems.

TipModelTensiune nominalăConsumul de energieAplicațieSelection Code
Continuu (Implicit)NA1-F-3200XAC220V/230V460VA(AC220V)General industrial control, infrequent operationF-AC220
AC380V/400V400VA(AC380V)F-AC380
DC110V70W(DC110V)F-DC110
DC220V140W(DC220V)F-DC220
Pulse Type (Recomandat)NA1-FP-3200XAC220V/230V880VA(AC220V)Wind & solar power, ATS system, frequent operationFP-AC220
AC380V/400V1800VA(AC380V)FP-AC380
DC110V850W(DC110V)FP-DC110
DC220V880W(DC220V)FP-DC220

Selection Note: Pulse type: single power-on duration ≤ 2s, max 5 times/min; Continuous type: single power-on duration ≤ 2s to avoid component burnout.

1.2 Undervoltage Trip (Q)

Automatically trips the breaker under low grid voltage to prevent equipment overload damage.

TipModelTensiune nominalăOperating CharacteristicDelay TimeSelection Code
Instant Suction (Implicit)NA1-Q-3200XAC230VTrip at 70% Us, reliable trip at 35% UsInstantQ-AC230
AC400VQ-AC400
Delayed SuctionNA1-QD-3200XAC230VSame as above1s/3s/5s (Fix)QD-AC230-1s
AC400VQD-AC400-3s
Self-suction DelayNA1-QZ-3200XAC230VSame as above0.3s~7.5s (Reglabil)QZ-AC230
AC400VQZ-AC400
Under-voltage Delay (UVTZ-1)NA1-UVTZ-1AC230VAutomatic reclosure after voltage recovery1s/3s/5sUVTZ-1-AC230
AC400V

Selection Note: 3200A frame adopts instant suction type as standard; self-suction type features wider delay range for voltage-fluctuation-sensitive equipment.

1.3 Solenoid de închidere (X) / Closing Coil

For remote closing, matched with motor charging mechanism.

TipModelTensiune nominalăConsumul de energieAplicațieSelection Code
Pulse Type (Mandatory for ATS)NA1-X-3200XAC220V/230VSame as shunt tripAutomatic control system, frequent closingX-AC220
AC380V/400VX-AC380
DC110VX-DC110
DC220VX-DC220

1.4 Motor Charging Mechanism (M)

Stores energy for breaker closing and provides closing power.

ModelTensiune nominalăPutereCharging TimeSelection Code
NA1-M-3200XAC220V/230V0.37kW≤15sM-AC220
AC380V/400VM-AC380
DC110VM-DC110
DC220VM-DC220
  1. Intelligent Control & Communication Accessories

2.1 Intelligent Controller Upgrade

Type M is standard; upgraded versions with enhanced functions are optional.

ModelCaracteristiciAplicațieSelection Code
Type 3MAdded voltage measurement and harmonic analysisPower quality monitoring required3M
Tip HAdvanced protection with extended parameter settingsComplex power distribution systems & protecţie precisăH
Type 3HHighest configuration, full 3M+H functions + event loggingCritical circuits & fault analysis3H

2.2 Module de comunicare (Monitorizare de la distanță)

Module TypeModelProtocolFuncţieMatching ComponentSelection Code
Modbus-RTUNA1-COM-MODModbus-RTUAchizitie de date & telecomandaNot requiredCOM-MOD
Profibus-DPNA1-COM-DPProfibus-DPIndustrial fieldbus communicationST-DP protocol moduleCOM-DP+ST-DP
ProfinetNA1-COM-PNProfinetComunicare EthernetPSU-1 power moduleCOM-PN+PSU-1
EtherNet/IPNA1-COM-ENIPEtherNet/IPEtherNet/IP communicationPSU-1 power moduleCOM-ENIP+PSU-1

2.3 Auxiliary Functional Modules

NumeModelFuncţieAplicațieSelection Code
Power Supply UnitPSU-1Stable power supply for communication modulesMandatory for all Ethernet modulesPSU-1
Relay ModuleRU-1Signal amplification & contact expansion (AC250V/10A, DC28V/10A)High-power load controlRU-1
Under-voltage Delay ControllerUVTZ-1Delayed trip during temporary low voltageVoltage-sensitive equipmentUVTZ-1
  1. Auxiliary Contact System (Indicație de stare & Controla)

NA1-3200X standard configuration: 4 sets of transfer contacts (4NO+4NC), expandable.

TipModelConfigurare contactEvaluareAplicațieSelection Code
3 sets TransferNA1-AX-3Z3NO+3NCAC230V/5ABasic controlAX-3Z
4 sets Transfer (Implicit)NA1-AX-4Z4NO+4NCAC230V/5AConfigurație standardAX-4Z
5 sets TransferNA1-AX-5Z5NO+5NCAC230V/5AExtended controlAX-5Z
3NO+3NCNA1-AX-333NO+3NCAC230V/5ACustom control logicAX-33
4NO+4NCNA1-AX-444NO+4NCAC230V/5AConfigurație standardAX-44
5NO+5NCNA1-AX-555NO+5NCAC230V/5AComplex controlAX-55
6NO+6NCNA1-AX-666NO+6NCAC230V/5AOnly for Type M controller, cannot match suction undervoltage delayAX-66
  1. Mechanical Interlock & Safety Accessories

4.1 Mechanical Interlock (Misoperation Prevention)

TipModelFuncţieAplicațieSelection Code
Connecting Rod InterlockNA1-LK-LGMutual interlock for two breakers to prevent simultaneous closingBus tie & ATS systemLK-LG
Cable InterlockNA1-LK-GLRemote mechanical interlock, standard cable length: 2mATS system with large cabinet spacingLK-GL
Blocare cheieNA1-KEYMultiple configurations: 1-lock-1-key, 2-lock-1-keyUnauthorized operation preventionKEY-1-1
KEY-2-1
Button LockNA1-BLLock closing/tripping buttonsAccidental touch preventionBL

4.2 Door Interlock

TipModelFuncţieAplicațieSelection Code
Position Door InterlockNA1-DL-WZCabinet door locked at test/connected positionDraw-out breaker, electric shock preventionDL-WZ
Status Door InterlockNA1-DL-ZTCabinet door locked when breaker closedLive operation prevention for all typesDL-ZT

4.3 Other Safety Accessories

NumeModelFuncţieAplicațieSelection Code
Transparent Protective CoverNA1-TPIP54 protection for operating mechanismDust environments & safety enhancementTP
CounterNA1-CTMechanical operation countingFrequent circuits & predictive maintenanceCT
Position IndicatorNA1-PSDraw-out position indication (Disconnect/Test/Connected)Draw-out breaker status monitoringPS
Bariera de fazăNA1-PSBIsolate three-phase busbars to prevent phase short circuitInsulation improvementPSB
  1. Montare & Connection Accessories

5.1 Main Circuit Accessories

NumeModelEvaluareAplicațieSelection Code
Horizontal BusbarNA1-BUS-H3200OStandard horizontal wiringBUS-H
Vertical L-type BusbarNA1-BUS-V3200OInstalare verticală & space savingBUS-V
Rotatable BusbarNA1-BUS-R3200OFlexible wiring for draw-out breakersBUS-R

5.2 Secondary Circuit Accessories

NumeModelFuncţieAplicațieSelection Code
Secondary ConnectorNA1-SPSecondary circuit connection for draw-out breakersQuick plug & unplugSP
Control FuseNA1-FU6O, control circuit protectionMandatory for all control loopsFU-6A
  1. Complete Configuration Example

Exemplu:

NA1-3200X-3200M/3P, motorized draw-out type, AC220V, with shunt trip / declanșare la subtensiune / closing solenoid + 5 sets transfer contacts + Profinet communication + connecting rod interlock

Complete Order Model:

NA1-3200X-3200M/3P Motorized Draw-out AC220 F-AC220 Q-AC230 X-AC220 AX-5Z COM-PN+PSU-1 LK-LG

  1. Accessory Application Notes
  2. Unified control voltage: Use identical voltage for shunt trip, declanșare la subtensiune, closing solenoid and motor charging mechanism to simplify wiring.
  3. Communication matching: PSU-1 power module required for Profinet/EtherNet/IP; ST-DP module required for Profibus-DP.
  4. Auxiliary contact capacity: 5A@AC230V; use RU-1 relay module for high-power load control.
  5. Undervoltage trip requirement: Undervoltage trip coil must be powered on before breaker closing.
  6. Shunt trip specification: Single energization time ≤ 2s, frequency ≤ 5 times/min to avoid overheating damage.

 