IC65: Represents the Schneider Acti9 series of miniature circuit breakers, with a frame rating current of 63A.

N: Indicates the breaking capacity class. The N - type has a breaking capacity of 6kA (at 230/400V AC).

3P: Denotes a three - proiectarea stâlpului, which is used in three - phase four - wire or three - phase three - wire circuits and can disconnect three phase lines simultaneously.

C16A: Refers to a Type C tripping curve and a rated current of 16A. It is suitable for loads with moderate inrush currents, such as lighting and sockets.

  • Detalii despre produs

The IC65N-3PC16A from Schneider Electric is a Întrerupător în miniatură (MCB) specifically designed for endofline power distribution. It is suitable for protecting threephase circuits against overload and shortcircuit damage. Below is a detailed analysis of its core parameters, application scenarios, and key selection points:

1. Model Meaning and Core Parameters

1.1 Model Breakdown

IC65: Represents the Schneider Acti9 series of miniature circuit breakers, with a frame rating current of 63A.

N: Indicates the breaking capacity class. The Ntype has a breaking capacity of 6kA (at 230/400V AC).

3P: Denotes a three – proiectarea stâlpului, which is used in threephase fourwire or threephase threewire circuits and can disconnect three phase lines simultaneously.

C16A: Refers to a Type C tripping curve and a rated current of 16A. It is suitable for loads with moderate inrush currents, such as lighting and sockets.

1.2 Key Electrical Parameters

Tensiune nominală: 230/400V și, supporting a frequency of 50/60Hz.

Caracteristici de declanșare:

Protecție la suprasarcină: Achieved through the thermal effect of a bimetallic strip. It trips in approximately 30 seconds when the current reaches 1.5 ori mai mare decât curentul nominal (24O).

Scurt – Circuit Protection: The electromagnetic trip unit acts instantaneously when the current is 5 – 10 ori mai mare decât curentul nominal (80 – 160O).

Capacitate de rupere:

Icu (Ultimate ShortCircuit Breaking Capacity): 6cel (at 400V AC), which meets the shortcircuit protection requirements in residential and smallscale commercial scenarios.

Ics (Service ShortCircuit Breaking Capacity): 6cel (100% of Icu), ensuring that the circuit breaker can still be used after a shortcircuit occurs.

1.3 Caracteristici fizice

Dimensiuni: It has a width of 54mm (6 modules) and is suitable for installation on a 35mm DIN rail, saving space in the distribution box.

Clasa de protectie: IP20 (for the terminal part), preventing accidental contact with live components.

Service Life: It has a mechanical life of 20,000 operations and an electrical life of 10,000 operațiuni, ensuring high longterm reliability.

2. Application Scenarios and Load Matching

2.1 Typical Application Fields

Residential Power Distribution: Used for protecting the circuits of highpower electrical appliances such as threephase air conditioners and electric water heaters.

Clădiri Comerciale: Applied in the lighting systems of offices and shopping malls, as well as for small threephase equipment (de ex., elevator control circuits).

Industrial Scenarios: Suitable for endofline power distribution lines of automated production lines and small motors. Cu toate acestea, it should be noted that the Type C curve may not be suitable for highinrush current loads (de ex., directly started motors).

2.2 Load Selection Recommendations

Loads Suitable for Type C Curve:

Lighting fixtures (incandescent lamps, LED lamps, etc.).

Ordinary sockets (for computers, televisions, small household appliances).

Resistive loads (electric heaters, water dispensers).

Scenarios to Avoid:

Motors (the starting current can reach 5 – 10 ori mai mare decât curentul nominal, which may cause false tripping).

Inductive loads such as welding machines and compressors (a Type D curve is recommended).

3. Installation and Expansion Functions

3.1 Metoda de instalare

Rail Installation: It can be directly fixed on a standard 35mm DIN rail using the snapfit on the back. It supports both top and bottom wire entry, with a wiring torque of 2.5N·m.

Wiring Capacity: It can accommodate singlecore hard wires (1 – 25mm²) or flexible wires (1 – 16mm²). The tunneltype terminal design ensures a reliable connection.

3.2 Extensie de accesorii

Earth Leakage Protection: It can be assembled with a Vigi IC65 earth leakage module (de ex., Vigi C16A) to provide 30mA residual current protection. It is suitable for humid environments such as bathrooms and kitchens.

Status Monitoring:

OF Auxiliary Contact: Feeds back the on/off status of the circuit breaker through normally open/normally closed signals, and is used for remote monitoring or PLC systems.

SD Alarm Contact: Triggers an alarm when a fault trip occurs, facilitating quick location of the faulty circuit.

Funcții de control:

MX Shunt Trip: Controls the circuit breaker to open remotely (de ex., for fire alarm linkage).

MN Undervoltage Trip: Automatically disconnects the circuit when the voltage is abnormal, protecting sensitive equipment.

4. Certificare și conformitate

International Certifications: It complies with IEC 60898 – 1 (Circuit Breakers for Household and Similar Purposes) și GB 10963.1 (Chinese Standard). It has obtained CCC and CE certifications, ensuring its applicability in the global market.

Adaptabilitate la mediu:

– Temperatura de operare: – 35°C to + 70°C, suitable for widetemperature environments.

Pollution Degree Resistance: Clasă 3, enabling stable operation in general industrial environments.

5. Key Selection Considerations

5.1 Current Matching

– Curentul nominal (16O) should be greater than the maximum continuous load current of the circuit. It is recommended to calculate based on the load power (de ex., for threephase loads: Power = √3 × Voltage × Current × Power Factor).

Avoid Overload: De exemplu, the maximum resistive load that a 16A circuit breaker can handle is approximately 10.5kW (400V × 16A × 1.5).

5.2 Verification of Breaking Capacity

Ensure that the prospective shortcircuit current at the installation location does not exceed 6kA. If the shortcircuit risk is high (de ex., near a transformer), a type with higher breaking capacity such as Htype (10cel) or Ltype (15cel) should be selected.

5.3 Earth Leakage Protection Requirements

For locations sensitive to personal safety (de ex., residential bathrooms, outdoor equipment), an earth leakage module (Vigi) should be used together, rather than relying solely on the overload/shortcircuit protection of the circuit breaker itself.

6. Price and Market Reference

Preţ: A single – întrerupător de circuit de poli (1P C16A) costs approximately 30 – 50 yuan, and a threepole model (3P C16A) ranges from 80 la 120 yuan. The specific price varies depending on the purchasing channel and quantity.

CostEffectiveness Advantage: Compared with competing products, the IC65N series is renowned for its high reliability, modular design, and wide accessory compatibility. It is suitable for projects with high requirements for stability and expandability.

7. Rezumat

The Schneider IC65N – 3PC16A is a threephase circuit breaker with balanced performance. Relying on its 6kA breaking capacity, Type C tripping curve, and flexible accessory expansion, it has become an ideal choice for endofline power distribution in residential, commercial, and light industrial applications. When selecting, a comprehensive evaluation should be conducted based on the load type, shortcircuit risk, and functional requirements. Priority should be given to purchasing through formal channels to ensure product quality and aftersales support.