Specificatii tehnice & Application Guide
This is a 2‑pole, Tip C, 25O întrerupător miniatural (MCB) din seria Acti9 de la Schneider Electric, with order code A9F18225 and rated breaking capacity 6kA.
It provides overload and short‑circuit protection for lighting, socket, and small motor circuits in AC distribution systems.
Features include 3‑stage current limiting, quick make mechanism, and protection degree IP40 (front) / IP20 (terminals).
It is compatible with iC65 series accessories for functional expansion.
- Model Breakdown
| Code | Sens | Descriere |
| SCHNEIDER | Marca | Schneider Electric (Franţa), global electrical equipment manufacturer |
| iC65N | Serie | Acti9 iC65 MCB, N‑type breaking capacity (6cel) |
| 2P | Number of poles | 2‑pole, breaks phase and neutral simultaneously, for 230V/400V systems |
| C | Tripping curve | Tip C, instantaneous tripping at 5~10×In (5In~10In) |
| 25O | Curent nominal | 25 amperes continuous at 30°C ambient |
| A9F18225 | Full order code | Official unique identifier |
- Specificații de bază
| Articol | Caietul de sarcini | Note |
| Basic | ||
| Tip | Întrerupător în miniatură (MCB) | Conform IEC 60898-1 / GB 10963.1 |
| Tripping type | Thermal‑magnetic | Overload (thermal) + short‑circuit (magnetic) protecţie |
| Capacitate de rupere | 6cel | Max breaking current at rated voltage |
| Rated operational voltage | AC 230V/400V | For 2‑pole version |
| Tensiunea nominală de izolație | 500V | Max withstand voltage of insulation |
| Rated impulse withstand voltage | 6kV | Surge voltage immunity |
| Rated frequency | 50/60Hz | Global grid compatible |
| Tripping characteristics | ||
| Protectie la suprasarcina | 1.13În (no trip in 1h), 1.45În (trip within 1h) | Meets IEC requirements |
| Short‑circuit protection | Instantaneous at 5In~10In | Tip C, suitable for lighting, sarcini rezistive, small motors |
| Physical & environmental | ||
| Dimensiuni (W×H×D) | 18mm×86mm×62mm | Standard modular, 2P = 2 modules (18mm/pole) |
| Protection degree | IP40 (front), IP20 (terminals) | Solid object and moisture protection |
| Temperatura de functionare | -35°C ~ +70°C | Suitable for harsh industrial environments |
| Mounting | 35mm șină DIN | Standard panel mounting |
| Certificari | CCC, CE, RoHS | Meets Chinese and international safety & environmental standards |
- Caracteristici
- Protection performance
3‑stage current limiting: Quickly limits peak current during short circuit, reduces thermal stress, protects equipment and cables.
Selective protection: Coordinates with upstream breakers for selective tripping, limits fault area.
Fault indication: Red window shows tripped status for quick diagnosis.
- Structural advantages
Dual‑lock clip: Secures firmly on DIN rail, prevents vibration loosening.
Quick make mechanism: Improves closing speed, reduces arcing, extends life.
Design modular: Accepts auxiliary contacts, alarm contacts, excursie cu șunt, declanșare la subtensiune, etc.
- Safety design
Isolation function: Safe isolation distance in OFF position, meets electrical safety rules.
Anti‑misoperation: Handle design prevents accidental closing.
Flame‑retardant housing: V0 grade material improves cabinet safety.
- Instalare & Întreţinere
Installation Rules
- Mount vertically (±15°) for proper tripping.
- Cablaj: Copper 1.5~35mm², Aluminium 2.5~35mm², torque 1.2~4N·m (depends on cross‑section).
- Environment: Avoid damp, prăfuită, corrosive or high‑vibration locations.
- Spacing: Maintain clearance for heat dissipation; follow installation manual.
Maintenance Guide
| Articol | Interval | Criterion | Soluţie |
| Visual inspection | Monthly | No damage, no overheating, tight connections | Clean, tighten loose terminals |
| Function test | Quarterly | Manual ON/OFF smooth, no sticking | Operate 3–5 times, check mechanism |
| Trip test | Annually | Overload & short‑circuit protection functional | Test with dedicated equipment or simulate overload |
| Accessory check | Annually | Auxiliary & alarm contacts working | Check contact condition, înlocuiți piesele deteriorate |
Depanare
- Deplasări frecvente: Check overload → short circuit → high ambient temperature → aging.
- Cannot close: Check short circuit → handle position → trip reset → loose wiring.
- Overheating: Check terminal torque → overload → ventilation.
- Upgrade & Replacement
5.1 Same‑series Upgrades
iC65H-2P-C25A (A9F28225): H‑type, 10cel, for higher short‑circuit current.
iC65L-2P-C25A (A9F38225): L‑type, 15cel, for heavy industrial use.
iC65N-2P-C25A‑Vigi (A9V58225): With residual current protection (RCCB), prevents electric shock.
5.2 Functional Accessories
| Accessory | Typical Model | Funcţie |
| Contact auxiliar | A9A26924 | 1NU+1NC, remote status indication |
| Shunt trip | A9X16224 | Remote tripping, de ex., fire alarm |
| Undervoltage trip | A9X16624 | Auto‑trip on low voltage |
| Alarm contact | A9A27924 | Signal when breaker trips |
5.3 Cross‑series Alternatives
| Serie | Replacement | Compatibilitate |
| Easy9 | EA9AN 2P C25A | Same dimensions, 6cel, economical |
| Acti9 CVS | CVS100B 2P C25A | MCCB, capacitate de rupere mai mare (10cel), main circuit use |
| Merlin Gerin | C65N 2P C25A | Fully compatible with iC65 |
- Applications
- Commercial buildings: Offices, magazine, hotels – lighting & socket circuits.
- Automatizare industrială: Control panels, small motors (≤5,5kW), VFD input protection.
- Rezidențial: Home distribution – air conditioners, kitchen appliances.
- Public facilities: Schools, hospitals, stadiums – electrical safety.
- Selecţie & Purchasing Tips
- Potrivirea încărcării: Type C for lighting, prize, small motors (≤5,5kW). Use Type B for pure resistive, Type D for large motors.
- Capacitate de rupere: Choose N (6cel), H (10cel), L (15cel) based on system short‑circuit current.
- Poles: 2P for 230V single‑phase where phase + neutral must be disconnected.
- Accessories: Add aux, shunt, undervoltage for smart systems.
- Authenticity: Buy from authorized Schneider distributors.
- Quick Fault Guide
| Symptom | Possible Cause | Soluţie |
| Trips immediately after closing | Short circuit / suprasarcina | Locate short, reduce load or upsize breaker |
| Trips after running a while | Overload / temperatură ridicată | Reduce load, improve ventilation, check cable size |
| Handle cannot be pushed to ON | Not reset / wiring fault | Pull to OFF first, then ON; check circuit |
| Terminal overheating | Loose connection | Retorque after power off, check terminals |
| No operation | Thermal‑magnetic unit failed | Replace MCB, check coordination |
SCHNEIDER iC65N-2P-C25A
Cross‑Brand Replacement Guide
Core Summary: The iC65N-2P-C25A (A9F18225) can be directly replaced by equivalent MCBs from major international and domestic brands.
Key matching requirements:
2P, Tip C, 25O, 6cel, 35mm DIN rail mounting.
- International Brand Direct Replacements
ABB
| Replacement | Order Code | Breaking | Compatibilitate |
| S202-C25 | 2CDS252001R0254 | 6cel | Best match, same dimensions, direct swap |
| S202M-C25 | 2CDS262001R0254 | 10cel | Higher breaking capacity |
| S202L-C25 | 2CDS242701R0254 | 4.5cel | Economy option |
Siemens
| Replacement | Serie | Breaking | Compatibilitate |
| 5SL6225-7 | 5SL | 6cel | Direct replacement, IEC 60898-1 |
| 5SY6225-7 | 5SY | 6cel | Economy range |
| 5SN6225-7CN | 5SN | 6cel | Classic, reliable |
Eaton
| Replacement | Serie | Breaking | Compatibilitate |
| FAZ6-C25/2 | FAZ | 6cel | Same dimensions & mounting |
| PL9-C25/2 | PL9 | 6cel | High performance, fast limiting |
Moeller
| Replacement | Serie | Breaking | Compatibilitate |
| FAZ6-C25/2 | FAZ | 6cel | Same dimensions & mounting |
| PL9-C25/2 | PL9 | 6cel | High performance, fast limiting |
- Chinese Domestic Brands
| Marca | Replacement | Breaking | Compatibilitate |
| CHINT | NXB-63-2P C25 | 6cel | Cost‑effective, direct fit |
| DELIXI | CDM3-63C25/2P | 6cel | Same dimensions |
| Liangxin | NDM1-63C25/2P | 6cel | High quality domestic |
| TENGEN | TGM1-63C25/2P | 6cel | Basic protection, economical |
- Critical Parameter Matching
| Articol | Original (iC65N-2P-C25A) | Must Match | Reglabil | Note |
| Poles | 2P | 2P | – | Disconnect phase + neutral |
| Curve | Tip C (5~10In) | Tip C | – | For lighting & small motors |
| Actual | 25O | 25O | – | Continuous rating |
| Breaking | 6cel | ≥6kA | Can be higher (10cel) | Ensure safe short‑circuit interruption |
| Mounting | 35mm șină DIN | 35mm șină DIN | – | Standard panel mount |
| Lăţime | 18mm | 18mm | H/D may vary | Fits standard spacing |
| Voltaj | AC 230V/400V | AC 230V/400V | – | Universal AC system |
- Replacement Notes & Best Practice
Before Replacement
System short‑circuit current ≤ breaking capacity of replacement.
35mm șină DIN, space, terminal size compatible.
Protection coordination with upstream/downstream devices.
Accessory mounting interface compatible.
Replacement has valid certifications (CCC, CE).
Procedure
- Power off and verify voltage absence.
- Remove wiring and old breaker.
- Clip replacement onto DIN rail.
- Torque terminals correctly.
- Test ON/OFF and tripping.
- Update labeling and drawings.
When NOT to replace
Original uses dedicated Schneider accessories (de ex., Vigi modules).
System short‑circuit current exceeds replacement rating.
Load inrush >10În (unsuitable for Type C).
Extreme environment outside replacement specs.
- Recommended Replacement Levels
| Nivel | Recommended Models | Application | Advantage |
| 1st | ABB S202-C25 | Industry, comerţ | Full performance, global support |
| Siemens 5SL6225-7 | |||
| 2nd | Eaton FAZ6-C25/2 | Control panels | Good value, easy install |
| Moeller DIL M9-25 C/2 | |||
| 3rd | CHINT NXB-63-2P C25 | Rezidențial, economy | Low cost, fast local supply |
| DELIXI CDM3-63C25/2P |
- Common Issues & Soluții
| Issue | Cauza | Soluţie |
| Frequent tripping after replacement | Wrong curve / suprasarcina | Confirm Type C, check load, upsize if needed |
| Will not fit | Wrong rail / lăţime | Use 35mm DIN rail, 18mm width model |
| Wiring difficult | Incompatible terminals | Use suitable lugs or select compatible model |
| Insufficient breaking capacity | Replacement < system short鈥慶ircuit current | Use higher version (de ex., ABB S202M-C25, 10cel) |
Cross‑brand replacement for SCHNEIDER iC65N-2P-C25A depends on parameter matching + mechanical compatibility + protection coordination.
Top international brands (ABB, Siemens) give identical performance.
Domestic brands (CHINT, DELIXI) offer cost savings.
Always verify specifications and follow electrical safety standards.
Contactor,întrerupător de circuit,invertor solar,contor electric,baterii solare