(Secvența fazelor / Pierdere de fază / 3-Phase Voltage Unbalance)
Serie: Zelio Control / Harmony RM17T Series, Montat pe șină DIN 3-phase monitoring relay, commonly known as phase sequence protector.
✅ Monitoring Functions
Phase sequence detection (L1-L2-L3): Instant trip upon reverse phase sequence
Phase loss detection: Instant trip if any phase is lost (including phase loss with regenerated voltage from motors)
3-phase voltage asymmetry (dezechilibra): Adjustable threshold from 5% la 15% of Un, with time-delayed tripping
Logic rule: Inversarea fazelor / phase loss → instantaneous trip; voltage unbalance → delayed trip.
📌 Key Electrical Specifications
Monitoring voltage range: AC 208~480V (operating limit: 183~528V AC)
Frecvenţă: 50/60 Hz (±10%)
Output contact: 1 C/O (SPDT), 5O / 250VAC
Time delay adjustment: 0.1~10s (only for unbalance faults)
Reset delay: Aproximativ. 1.5s
Consumul de energie: ≤22VA @ 400V 50Hz
Montare: DIN 35mm rail; width 17.5mm (1 lățimea modulului)
Indicaţie: Status LED; sealed transparent cover prevents accidental parameter changes
🧮 RM17T Series Selection Comparison (Key for Model Selection)
RM17TT00: Secvența fazelor + pierdere de fază (NO unbalance monitoring)
RM17TA00 (Current Model): Secvența fazelor + pierdere de fază + 3-phase voltage asymmetry
RM17TU00: Secvența fazelor + pierdere de fază + subtensiune
RM17TE00: Secvența fazelor + pierdere de fază + asymmetry + supratensiune + subtensiune (full-function model)
🛠️ Typical Application Scenarios
Lifturi, ridicarea & conveying equipment, compresoare de aer, pompe de apa, unități frigorifice, utilaje de ambalare; prevents motor reverse rotation, burnout from phase loss, and overheating caused by three-phase unbalance.
🔌 Wiring Guidelines
- Connect L1/L2/L3 directly to the monitored three-phase supply (self-powered, no separate auxiliary supply required).
- Terminale 15/16/18 form one changeover contact: 15-16 = normally closed; 15-18 = normally open.
- Panel setting: First select rated voltage (208/220/380/400/415/480V), then set unbalance threshold and fault delay time.
- Fault recovery: Automatic reset once power returns to normal; no manual reset button.
⚠️ Troubleshooting
Relay does not energize after power-up: Check phase sequence, pierdere de fază, and voltage range dip switch setting.
Frequent tripping during normal operation: Increase unbalance percentage threshold, extend time delay, and investigate single-phase load current imbalance.
No LED illumination: Three-phase input voltage exceeds the 183~528V operating range.
📎 Replacement Options
Direct upgraded replacement within the same product line: RM22TA33 (RM22 series, same functions with 2 C/O contacts).
Alternative interne: Chint / Delixi three-phase phase-sequence & unbalance monitoring relays.
- Full Model List of RM17T Series
(3-phase supply monitoring relays, 17.5mm single-module width, Montare pe șină DIN)
1) Model de bază: RM17TG (Only phase sequence + pierdere de fază; no unbalance / undervoltage monitoring)
RM17TG00: 1 C/O changeover contact, 208~480V AC
RM17TG20: 2 C/O dual changeover contacts, 208~440V AC
2) Multifunction Models (RM17TT / FATA / TU / THE, 208~480V AC, 1 C/O contact uniformly)
| Model | Core Monitoring Functions |
| RM17TT00 | Secvența fazelor + pierdere de fază (basic version, no unbalance / subtensiune) |
| RM17TA00 (Current Model) | Secvența fazelor + pierdere de fază + 3-phase voltage unbalance (asymmetry) |
| RM17TU00 | Secvența fazelor + pierdere de fază + subtensiune |
| RM17TE00 | Secvența fazelor + pierdere de fază + dezechilibra + supratensiune + subtensiune (full function) |
Abbreviation explanation:
TU = T + Subtensiune
TE = T + Everything (funcții complete)
III. Common Specifications for the Whole Series (All Models Identical)
Gama de tensiune: AC 208~480V (operating limit 183~528V)
Evaluarea contactului: 5O / 250VAC; RM17TG00/TT/TA/TU/TE = 1 C/O; only RM17TG20 = 2 C/O
Lăţime: 17.5mm (1P module)
Modul de resetare: Automatic reset after fault clears; no manual reset button
- Upgraded Replacement Models (RM22 Series with Extra Contacts)
RM17TA00 → RM22TA33 (2 C/O contacts)
RM17TU00 → RM22TU23
RM17TE00 → RM22TE33
RM17TA00 Overall Dimensions (L × H × D)
17.5 mm × 90 mm × 72 mm
Lăţime: 17.5 mm (1-pole module, same width as 1P MCB)
Înălţime: 90 mm
Adâncime (from DIN rail front face): 72 mm
Montare: DIN35 standard rail
Greutate netă: Aproximativ. 0.13 kg
✅ All models in RM17T series (RM17TT00 / RM17TU00 / RM17TE00 / RM17TG00) share identical dimensions.
Core Positioning of RM17TA00
It provides phase sequence + pierdere de fază + three-phase voltage unbalance protection, mainly for three-phase asynchronous motors. It prevents reverse rotation, motor burnout from phase loss, and overheating caused by long-term voltage imbalance. Autoalimentat, compact 1-module DIN rail design, ideal for compact control cabinets and retrofitting projects where no PLC signal collection is needed.
- Industrie & Equipment Applications
- Ridicare & Transmiterea (Aplicație primară)
Macarale rulante, electric hoists, transportoare cu bandă, stivuitoare, lifturi; prevents motor reverse rotation after phase reconnection and overheating damage to gearboxes and motors due to long-term unbalance.
- Lifturi & Platforme de ridicare
Freight elevators, simple lifting platforms, parking lift power circuits; wrong phase sequence causes reverse car movement; voltage unbalance leads to excessive temperature rise of traction motors.
- Pompe de apă & Pumping Stations
High-power centrifugal pumps, submersible sewage pumps, pre-power monitoring before variable-frequency drives; unbalance is frequently caused by mixed single-phase loads in water supply, sewage treatment and chiller pump systems.
- Compresoare de aer & HVAC Refrigeration Units
Compresoare de aer cu șurub, răcitoare de apă, air-source heat pumps, compresoare frigorifice; compressors are highly sensitive to three-phase unbalance, which easily burns out motor windings.
- Ambalare, Textile & Woodworking Automation
Linii de ambalare, utilaje textile, extrudere, injection molding auxiliary equipment; frequent power maintenance and phase swapping require phase sequence verification before power-on.
- Fan Loads
Ventilatoare de evacuare, induced draft fans, drying fans; large inertia fans produce regenerated voltage after phase loss; this model supports phase loss detection under regenerated voltage conditions.
- Control Panels & OEM Equipment Matching
380V three-phase control cabinets, non-standard automation OEM factory-fitted protection; old equipment retrofits, hard-contact interlock without adding PLC analog modules.
- Selection Boundary: Potrivit / Scenarii nepotrivite
✅ Recomandat:
Three-phase motor loads with risks of voltage asymmetry overheating (core advantage over RM17TT00)
Supply voltage AC 208~480V, 50/60Hz
Spațiu limitat pentru cabinet, numai 1 module width available
Hard-contact interlock directly wired into main contactor coil circuit
❌ Not recommended:
Supratensiune + undervoltage monitoring required → choose RM17TE00
Only undervoltage protection without unbalance → choose RM17TU00
Dual independent alarm contacts required → upgrade to RM22TA33 (2C/O)
Motors behind variable-frequency drives: VFDs already have built-in phase loss & protecție împotriva dezechilibrului; extra relay is generally unnecessary.
III. Typical Control Logic
Contact wired in series with the main contactor coil circuit:
Normal power supply → relay energizes and closes, contactor power permitted;
Inversarea fazelor / pierdere de fază / voltage unbalance detected → relay de-energizes and opens, cutting off main power, with dry contacts available for PLC or audible-visual alarm signals.
Contactor,întrerupător de circuit,senzor,Codificator,PLC,Convertor