Siemens 3TX4001-2A Auxiliary Contact Block

This legacy Siemens SIRIUS front-mounted auxiliary contact features 1 În mod normal închis (NC) contact, compatible with 3TF3 / 3TF4 contactors. Original production discontinued on Oct 01, 2021 with no identical OEM replacement. Recommended drop-in alternative: domestic compatible 3TY7561-1AA00, or upgrade to 3RH2911-1AA01 for 3RT6 series contactors. Model Code Breakdown Code Segment Definition 3TX Base designation for ...

  • Detalii despre produs

This legacy Siemens SIRIUS front-mounted auxiliary contact features 1 În mod normal închis (NC) contact, compatible with 3TF3 / 3TF4 contactors. Original production discontinued on Oct 01, 2021 with no identical OEM replacement. Recommended drop-in alternative: domestic compatible 3TY7561-1AA00, or upgrade to 3RH2911-1AA01 for 3RT6 series contactors.

  1. Defalcarea codului de model
Segment de codDefiniţie
3TXBase designation for Siemens SIRIUS snap-on front auxiliary contact blocks
4001Contact configuration code: 1NC (single normally closed); 4010 = 1NO (single normally open)
-2OMontare & terminal specs: front snap-in installation, no contact status indicator window, captive screw clamp terminals (exclusively designed for 3TF3/3TF4 contactors)
StareDiscontinued from Oct 01, 2021; OEM note: Product was deleted without replacement
  1. Specificații electrice de bază
ArticolValoareObservații
Configurare contact1NC, positively drivenDesigned for safety circuit compliance
Curent termic convențional (Ith)10 ORated continuous operating current
AC-15 Breaking Capacity5.6 A @ 230 VACBreaking capacity for control circuits
3.6 A @ 400 VAC
2.2 A @ 690 VAC
Tensiune nominală de izolație (Ui)690 VMaximum permissible operating voltage
Tensiune de rezistență la impuls6 kVElectrical isolation safety rating
Rezistenta mecanica10 milioane de operațiuniFar exceeds service life of base contactor
Rezistenta electrica1 milioane de operațiuni (AC-15 duty)Under rated cyclic load
ÎncetareaCaptive clamping screwsFor solid conductors: 0.75~2.5 mm²
Protecție la intrareIP20Finger-safe & rezistent la praf
Temperatura de operare-25℃ ~ +55℃Depozitare: -55℃ ~ +80℃
Standarde de conformitateIEC60947-5-1, GB14048.5CE & RoHS certified
  1. Full Same-housing Model List (3TX4 Series)
Cod de comandăContact LayoutMounting StyleMatching ContactorStare
3TX4001-2A1NCFront snap-on3TF30~3TF34 / 3TF40~3TF45Întrerupt
3TX4010-2A1NUFront snap-onLa fel ca mai susÎntrerupt
3TX3001-2A1NCSide-mountedLegacy 3TB contactorsÎntrerupt
3TX3010-2A1NUSide-mountedLa fel ca mai susÎntrerupt
3TX4002-2A2NCFront snap-onHigh-current 3TF rangeÎntrerupt
3TX4012-2A1NU+1NCFront snap-onLa fel ca mai susÎntrerupt
  1. Full Compatible Contactor List (Exclusive for Front Snap Fit)

Only applicable to below 3TF series, incompatible with newer 3RT / 3RV ranges:

3TF30: 3TF3000~3TF3090 (9A~12A)

3TF31: 3TF3100~3TF3190 (12A~16A)

3TF32: 3TF3200~3TF3290 (16A~25A)

3TF33: 3TF3300~3TF3390 (25A~32A)

3TF34: 3TF3400~3TF3490 (32A~40A)

3TF40~45: 3TF4000~3TF4590 (40A~95A)

> Nota: One contactor can mount 1 front block + 2 side auxiliary blocks simultaneously, max expansion up to 6 contacte auxiliare (3NO +3NC).

  1. Replacement Selection Guide for Obsolete Item

5.1 Direct Drop-in Replacement (No Contactor Modification)

Replacement PNMarcaContactCompatibilitateAvantaje
3TY7561-1AA00Siemens domestic alternative1NCIdentical snap dimensionPlug-and-play, rentabil
3TX4001-2BLegacy Siemens1NCSame function with indicator lampObsolete stock only, cost ridicat
LC1-D Auxiliary ContactSchneider Electric1NCRequires adapter bracketEstablished brand, performanță stabilă

5.2 Full Unit Upgrade (3TF → 3RT6)

Opțiune de upgradeNew ContactorMatching Auxiliary ContactAvantajeAplicație
Standard Upgrade3RT6026~3RT60363RH2911-1AA01 (1NC)Durată lungă de viață, intelligent monitoringNew construction & equipment retrofit
Extinderea funcției3RT6040~3RT60563RH2911-1AA01 + 3RH2911-1BA01Multi-contact combinationComplex control circuits
  1. Mediul de aplicare & Industrial Cases

✅ Approved Application Scenarios

  1. Motor Control Circuits: Fault feedback & star-delta interlock for 3TF contactors of fans & pompe de apa
  2. PLC Interface: NC contact feeds contactor open/closed status into PLC digital input modules
  3. Interblocare de siguranță: Oprire de urgență & access door protection; NC forced opening cuts control supply (conform EN 60204-1)
  4. Indicație de stare: Pilot lamp power switching; NC opens to turn off indicator when contactor energizes

❌ Forbidden Applications

  1. Direct main-circuit loading: Designed exclusively for control loops (bobine, pilot lamps, PLC signals); never connect to power main circuit
  2. Harsh ambient: Avoid >60℃, praf greu, corrosive chemical & non-enclosed cabinets (accelerates contact oxidation)
  3. High-frequency cycling: >10 cicluri/min; use solid-state relays instead
  4. DC heavy-load circuits: AC-15 rating invalid for DC-13 duty; select dedicated DC auxiliary contacts

Cazuri de aplicații industriale

IndustrieAplicațieContact Function
HVACAC compressor contactorFault stop signal to building automation system
Tratarea apeiWater pump motor controlOverload interlock with main contactor
General MachineryConveyor controlEmergency stop cut-off for safe shutdown
Distribuția energieiBackup power transferContactor status monitoring to prevent faulty switching
  1. Depanarea defecțiunilor comune
VinaRoot CauseRemedy
Open circuit / contact slab1. Contact oxidation under humid condition1. Replace with compatible 3TY7561
2. Cabluri slăbite2. Retighten terminal screws
Contactor pulls in but NC fails to open1. Loose & fallen snap clip1. Reinstall and lock into position
2. Mechanical blockage inside block2. Replace block; inspect deformed contactor shaft
Contact arcing & epuizare1. Exceeding AC-15 rated current1. Add intermediate relay for load expansion
2. High inductive surge from load2. Fit RC snubber circuit for surge suppression
Abnormal overheating1. High contact resistance at terminals1. Clean terminals & re-terminate
2. Excessive ambient temperature2. Improve ventilation or use high-temperature variant
  1. Quick Selection Mnemonic

4001 = NC, 4010 = NU; front snap exclusively for 3TF;<br>Obsolete → swap to 3TY; upgrade to 3RT with 3RH;<br>Only for control circuit, never main power, excellent for safety interlock!

  1. Cod HS & Conformitatea transportului aerian

Cod HS: 85365000 (Electrical switching apparatus for circuit protection)

Clasificarea transportului aerian: Mărfuri nepericuloase, purely mechanical contacts with no lithium battery/supercapacitor, compliant with IATA DGR

Certificare CE: Complies with Low Voltage Directive 2014/35/EU; Certificate of Conformity available upon request

Application Scope of 3TX4001-2A (Front-mounted 1NC Auxiliary Contact)

Caracteristica produsului: Snap-on external 1NC contact for 3TF3/3TF4 contactors, rated AC-15, dedicated for secondary control circuit only, NOT permitted in main power circuit.

  1. Standard Common Applications

1.1 Motor Start-Stop Control (Fani, Pompe de apă, Air Compressors)

  1. Passive running status feedback

Contactor coil energizes → NC opens, sends closing/running feedback signal to PLC DI module; coil de-energizes → NC resets closed to transmit stop signal.

Typical usage: Chilled water pumps, cooling blowers, pompe de circulatie, central air-conditioning units.

  1. Electrical interlock protection

Mutual NC interlock between two contactors (forward/reverse or star-delta) to avoid simultaneous closing and phase short-circuit.

Exemplu: Star-delta motor starter interlock between star & delta contactors.

1.2 Mașină-uneltă & Automation Equipment (Strung, Transportor, Injection Molding Machine)

  1. Cabinet door interlock: NC of main contactor wired into safety loop; if contactor is welded closed, NC stays open to block equipment restart.
  2. Conveyor sequential interlock: Interlock between upstream & downstream conveyor contactors to prevent mechanical collision from misoperation.
  3. Fault alarm: Normally closed NC in series with fault indicator lamp; lamp lights at standby/shutdown and goes off when contactor pulls in.

1.3 HVAC Industry (Central AC, Fresh Air Unit, Smoke Exhaust Fan)

  1. BA system signal collection: Fan contactor NC feeds start/stop remote data to building management controller.
  2. Fire smoke exhaust interlock: NC links with fire damper; damper shutdown cuts fan control circuit.

1.4 Water Treatment Equipment (Dosing Pump, Sewage Pump, Aeration Blower)

  1. Pump overload linkage: Thermal relay trip resets contactor, closed NC triggers audible-visual fault alarm.
  2. Duty/standby pump auto-switch: Main pump fault closes NC to activate backup pump automatically.

1.5 LV Power Distribution Panels

  1. Capacitor compensation cabinet: NC of switching contactor feeds capacitor switching status to reactive power regulator.
  2. ATS cabinet: Electrical interlock between normal & backup supply contactors to eliminate cross-source short-circuit risk.

1.6 Hoisting & Elevator Auxiliary Control

Brake contactor NC of overhead crane feeds brake open/closed feedback; also for cooling fan contactor status monitoring on elevators.

  1. Safety Circuit Exclusive Usage (Positively Driven Contact per Machinery Safety Standards)
  2. Emergency stop monitoring: Detects welded contactor fault; mechanically stuck contactor keeps NC open to lock control power off.
  3. Safety guard circuit: Equipment door opening de-energizes main contactor, closed NC locks startup circuit.
  4. Low-power Indicator & Small Relay Driving
  5. Standby pilot lamp: NC closed to light indicator at idle; NC opens to turn lamp off during equipment operation.
  6. Mini intermediate relay drive: NC switching controls relay coil to amplify load capacity.
  7. Prohibited Application List
  8. ❌ Never connect to 220V/380V main power loop; AC-15 rating only for control loads, cannot directly drive motor/heater high-power loads.
  9. ❌ Evitați >55℃, strong acid/alkali corrosion & unprotected open-air cabinets (accelerates contact oxidation & bad conduction).
  10. ❌ Unsuitable for heavy DC loads (no DC-13 rating; DC breaking easily causes arc burnout).
  11. ❌ Ban over 15 switching cycles per minute (fast mechanical wear; replace with solid-state relay).