Schneider A9DA2616

Schneider A9DA2616 (Acti9 iDD40T 1P+N C16 30mA AC) Residual Current Operated Circuit Breaker with Overcurrent Protection (RCBO)

  1. Interpretarea modelului

A9DA2616 = Acti9 Series iDD40T Product Type 1P+N Pole Configuration C-type Tripping Curve 16A Rated Current 30mA Residual Current AC-type Residual Current Detection

  1. Parametrii tehnici de bază (Compliant with IEC 61009-1/GB 16917.1)
ParametruCaietul de sarcini
Product TypeResidual Current Operated Circuit Breaker with Overcurrent Protection (RCBO, integrating three protections: suprasarcina, scurtcircuit, and residual current)
Pole Configuration1P+N (1 Pole + Neutral, phase line breaks, neutral line remains conducting permanently)
Curent nominal (În)16O
Tripping CurveC-type (instantaneous tripping at 5~10 In), suitable for lighting, socket, and general motor loads
Rated Residual Operating Current (IΔn)30mA (personal safety protection level)
Residual Current TypeAC-type (detects sinusoidal AC leakage current, suitable for conventional environments)
Tensiune nominală (Ue)230V AC (1P+N), 50/60Hz
Short-circuit Breaking Capacity (Icn)6cel (400V) / 4500O (230V)
Rated Residual Operating Time (at IΔn)≤0.3s
Mechanical Service Life10,000 operațiuni
Electrical Service Life5,000 operațiuni
Metoda de montare35mm DIN rail (18mm width)
Wiring SpecificationSolid wire: 1~25 mm²; Flexible wire: 1~16 mm² (with cable lugs)
Terminal Torque2.0 N·m
Temperatura de operare-25℃ ~ +70℃
Clasa de protectieIP20 (for use inside distribution boxes)
Rated Impulse Withstand Voltage (Uimp)4kV
  1. Functions & Applications

Core Functions

Protecție la suprasarcină: Realizes inverse-time protection via the thermal bending of bimetallic strips.

Short-circuit Protection: Achieves instantaneous protection through electromagnetic release.

Residual Current Protection: Rapidly trips within ≤0.3s when detected residual current exceeds 30mA, preventing electric shock accidents.

Scenarii tipice de aplicare

  1. Branch circuit protection for residential/commercial buildings (de ex., lighting and socket circuits)
  2. Electrical safety protection for crowded places such as offices and shops
  3. Power supply protection for small household appliances and office equipment
  4. Replacement for traditional MCB + RCCB combinations, economisind spațiu în cutia de distribuție

Selection Tips

AC-type is suitable for pure AC load environments, such as traditional lighting and resistive loads.

For loads containing DC components (de ex., switching power supplies, LED lighting), A-type or B-type residual current circuit breakers are recommended.

30mA is the standard value for personal safety protection and shall not be used for equipment protection (300mA is usually selected for equipment protection).

  1. Instalare & Maintenance Key Points
  2. Specificații de cablare: Top-in bottom-out (bidirectional wiring with bottom-in top-out supported). Connect phase line to L pole and neutral line to N pole; reverse connection is strictly prohibited.
  3. Residual Current Test: După instalare, press the test button (T button) to confirm the normal operation of the residual current protection function.
  4. Inspecție regulată: Press the test button once a quarter to verify the effectiveness of the residual current protection function.
  5. Tratarea defecțiunilor:

Overload/Short-circuit Tripping: Troubleshoot load or line faults before closing the breaker directly.

Residual Current Tripping: First disconnect all loads, check for leakage points one by one, and close the breaker only after repairs; forced closing with faults is strictly prohibited.

  1. Spacing Requirement: Maintain a gap of ≥3mm from adjacent components to ensure heat dissipation and wiring space.
  2. Corresponding Chint Product & Replacement Comparison

Chint Equivalent Model: NXBLE-63 1P+N C16 30mA AC

Parameter CategorySchneider A9DA2616Chint NXBLE-63 1P+N C16 30mACompatibilitate de înlocuire
Core ProtectionOverload + Short-circuit + Residual Current (RCBO)Overload + Short-circuit + Residual Current (RCBO)✅ Fully Matched
Pole Configuration/Tripping Curve/In1P+N/C-type/16A1P+N/C-type/16A✅ Fully Matched
IΔn/IΔ Type30mA/AC30mA/AC✅ Fully Matched
Capacitate de rupere6cel6cel✅ Fully Matched
Installation Dimensions18mm (lăţime) × 91mm (height) × 65mm (depth)18mm (lăţime) × 91mm (height) × 65mm (depth)✅ Identical Dimensions
Wiring SpecificationSolid wire: 1~25 mm²Solid wire: 10~16 mm²⚠️ Schneider Terminals Have Larger Capacity
Temperatura de operare-25℃ ~ +70℃-30℃ ~ +70℃✅ Chint Has Better Low-temperature Adaptability
Additional FunctionsVisiTrip Fault IndicationRed-Green Window Indication (Red for Closed, Green for Open)⚠️ Different Indication Methods
Warranty Period24 Months18 Months⚠️ Warranty Difference

Key Replacement Precautions

  1. ✅ Installation Compatibility: Both are mounted on 35mm DIN rails with 18mm width, enabling direct interchange.
  2. ✅ Protection Characteristics: C-type curve, 16A rated current, and 30mA residual current protection are fully consistent; no load adjustment is required.
  3. ⚠️ Wiring Adaptation: Schneider terminals support larger wire diameters; keep the original wire diameter during replacement to avoid loose connections.
  4. ⚠️ Function Identification: The VisiTrip indication window of Schneider shows red after tripping; it is necessary to train operators to recognize the new marks.
  5. Rezumat & Selection Recommendations

Schneider A9DA2616 is a 1P+N 16A RCBO in the Acti9 series iDD40T product line. It integrates triple protection functions and is suitable for personal safety protection in conventional environments.

Selection Recommendations:

For international brand reputation and reliable performance: Choose Schneider A9DA2616, which provides more comprehensive fault indication and bidirectional wiring functions.

For cost-effectiveness: Choose Chint NXBLE-63 1P+N C16 30mA, which features more favorable pricing and performance meeting national standards.

For special environments (de ex., low temperature < -25): Prioritize Chint products for their better low-temperature adaptability.