Schneider A9DA2616 (Acti9 iDD40T 1P+N C16 30mA AC) Întrerupător acționat cu curent rezidual with Overcurrent Protection (RCBO)
- Interpretarea modelului
A9DA2616 = Acti9 Series iDD40T Product Type 1P+N Pole Configuration C-type Tripping Curve 16A Rated Current 30mA Residual Current AC-type Residual Current Detection
- Parametrii tehnici de bază (Compliant with IEC 61009-1/GB 16917.1)
| Parametru | Caietul de sarcini |
| Product Type | Residual Current Operated Circuit Breaker with Overcurrent Protection (RCBO, integrating three protections: suprasarcina, scurtcircuit, and residual current) |
| Configurația stâlpului | 1P+N (1 Pole + Neutru, phase line breaks, neutral line remains conducting permanently) |
| Curent nominal (În) | 16O |
| Curba de declanșare | de tip C (instantaneous tripping at 5~10 In), suitable for lighting, socket, and general motor loads |
| Rated Residual Operating Current (IΔn) | 30mA (personal safety protection level) |
| Residual Current Type | AC-type (detects sinusoidal AC leakage current, suitable for conventional environments) |
| Tensiune nominală (Ue) | 230V și (1P+N), 50/60Hz |
| Short-circuit Breaking Capacity (Icn) | 6cel (400V) / 4500O (230V) |
| Rated Residual Operating Time (at IΔn) | ≤0.3s |
| Durată de viață mecanică | 10,000 operațiuni |
| Durată de viață electrică | 5,000 operațiuni |
| Metoda de montare | 35mm șină DIN (18mm latime) |
| Specificații de cablare | Solid wire: 1~25 mm²; Flexible wire: 1~16 mm² (with cable lugs) |
| Terminal Torque | 2.0 N·m |
| Temperatura de operare | -25℃ ~ +70℃ |
| Clasa de protectie | IP20 (for use inside distribution boxes) |
| Tensiune nominală de rezistență la impuls (Ump) | 4kV |
- Functions & Applications
Funcții de bază
Protecție la suprasarcină: Realizes inverse-time protection via the thermal bending of bimetallic strips.
Short-circuit Protection: Achieves instantaneous protection through electromagnetic release.
Residual Current Protection: Rapidly trips within ≤0.3s when detected residual current exceeds 30mA, preventing electric shock accidents.
Scenarii tipice de aplicare
- Branch circuit protection for residential/commercial buildings (de ex., lighting and socket circuits)
- Electrical safety protection for crowded places such as offices and shops
- Power supply protection for small household appliances and office equipment
- Replacement for traditional MCB + RCCB combinations, economisind spațiu în cutia de distribuție
Selection Tips
AC-type is suitable for pure AC load environments, such as traditional lighting and resistive loads.
For loads containing DC components (de ex., switching power supplies, LED lighting), A-type or B-type residual current circuit breakers are recommended.
30mA is the standard value for personal safety protection and shall not be used for equipment protection (300mA is usually selected for equipment protection).
- Instalare & Maintenance Key Points
- Specificații de cablare: Top-in bottom-out (bidirectional wiring with bottom-in top-out supported). Connect phase line to L pole and neutral line to N pole; reverse connection is strictly prohibited.
- Residual Current Test: După instalare, press the test button (T button) to confirm the normal operation of the residual current protection function.
- Inspecție regulată: Press the test button once a quarter to verify the effectiveness of the residual current protection function.
- Tratarea defecțiunilor:
Overload/Short-circuit Tripping: Troubleshoot load or line faults before closing the breaker directly.
Residual Current Tripping: First disconnect all loads, check for leakage points one by one, and close the breaker only after repairs; forced closing with faults is strictly prohibited.
- Spacing Requirement: Maintain a gap of ≥3mm from adjacent components to ensure heat dissipation and wiring space.
- Corresponding Chint Product & Replacement Comparison
Chint Equivalent Model: NXBLE-63 1P+N C16 30mA AC
| Categoria parametrilor | Schneider A9DA2616 | Chint NXBLE-63 1P+N C16 30mA | Compatibilitate de înlocuire |
| Core Protection | Overload + Short-circuit + Residual Current (RCBO) | Overload + Short-circuit + Residual Current (RCBO) | ✅ Fully Matched |
| Pole Configuration/Tripping Curve/In | 1P+N/C-type/16A | 1P+N/C-type/16A | ✅ Fully Matched |
| IΔn/IΔ Type | 30mA/AC | 30mA/AC | ✅ Fully Matched |
| Capacitate de rupere | 6cel | 6cel | ✅ Fully Matched |
| Installation Dimensions | 18mm (lăţime) × 91mm (înălţime) × 65mm (adâncime) | 18mm (lăţime) × 91mm (înălţime) × 65mm (adâncime) | ✅ Identical Dimensions |
| Specificații de cablare | Solid wire: 1~25 mm² | Solid wire: 10~16 mm² | ⚠️ Schneider Terminals Have Larger Capacity |
| Temperatura de operare | -25℃ ~ +70℃ | -30℃ ~ +70℃ | ✅ Chint Has Better Low-temperature Adaptability |
| Additional Functions | VisiTrip Fault Indication | Red-Green Window Indication (Red for Closed, Green for Open) | ⚠️ Different Indication Methods |
| Warranty Period | 24 Months | 18 Months | ⚠️ Warranty Difference |
Key Replacement Precautions
- ✅ Installation Compatibility: Both are mounted on 35mm DIN rails with 18mm width, enabling direct interchange.
- ✅ Protection Characteristics: C-type curve, 16A rated current, and 30mA residual current protection are fully consistent; no load adjustment is required.
- ⚠️ Wiring Adaptation: Schneider terminals support larger wire diameters; keep the original wire diameter during replacement to avoid loose connections.
- ⚠️ Function Identification: The VisiTrip indication window of Schneider shows red after tripping; it is necessary to train operators to recognize the new marks.
- Rezumat & Recomandări de selecție
Schneider A9DA2616 is a 1P+N 16A RCBO in the Acti9 series iDD40T product line. It integrates triple protection functions and is suitable for personal safety protection in conventional environments.
Recomandări de selecție:
For international brand reputation and reliable performance: Choose Schneider A9DA2616, which provides more comprehensive fault indication and bidirectional wiring functions.
For cost-effectiveness: Choose Chint NXBLE-63 1P+N C16 30mA, which features more favorable pricing and performance meeting national standards.
For special environments (de ex., low temperature < -25℃): Prioritize Chint products for their better low-temperature adaptability.